174
GUIDE SPECIFICATIONS — 581C024-060 (cont)
For the EconoMi$er2, the power exhaust shall be
controlled by the or third party controls.
23. Outdoor Air Enthalpy Sensor (EconoMi$er IV or
EconoMi$er2):
The outdoor air enthalpy sensor shall be used with
the EconoMi$er IV or EconoMi$er2 device to pro-
vide single enthalpy control. When used in conjunc-
tion with a return air enthalpy sensor, the
EconoMi$er IV or EconoMi$er2 device will provide
differential enthalpy control. The sensor allows the
EconoMi$er IV or EconoMi$er2 controller to deter-
mine if outside air is suitable for free cooling.
24. Return Air Enthalpy Sensor (EconoMi$er IV or
EconoMi$er2):
The return air enthalpy sensor shall be used with
the EconoMi$er IV or EconoMi$er2 device. When
used in conjunction with an outdoor air enthalpy
sensor, the EconoMi$er IV or EconoMi$er2 device
will provide differential enthalpy control.
25. Return Air Temperature Sensor (EconoMi$er IV or
EconoMi$er2):
The return air temperature sensor shall be used
with the EconoMi$er IV or EconoMi$er2 device.
When used in conjunction with the standard outdoor
air temperature sensor, the EconoMi$er IV or
EconoMi$er2 device will provide differential temper-
ature control.
26. Indoor Air Quality (CO
2
) Sensor (EconoMi$er2):
a. Shall have the ability to provide demand ventila-
tion indoor air quality (IAQ) control through the
EconoMi$er2 with an IAQ sensor.
b. The IAQ sensor shall be available in duct mount,
wall mount, and wall mount with LED display.
The set point shall have adjustment capability.
c. Requires EconoMi$er2, or Apollo control
options.
27. Indoor Air Quality (CO
2
) Room Sensor (EconoMi$er
IV):
Sensor shall have the ability to provide demand
ventilation control through the EconoMi$er IV. The
IAQ sensor shall be wall mounted with an LED dis-
play in parts per million. The set point shall have
adjustment capability.
28. Return Air CO
2
Sensor (EconoMi$er IV):
Sensor shall have the ability to provide demand
ventilation control through the EconoMi$er IV. The
IAQ sensor shall be duct mounted. The set point
shall have adjustment capability.
29. Gas Heat options (sizes 036-060):
a. Single-stage gas heat shall be provided in lieu of
two-stage heat.
b. NOx reduction shall be provided to reduce
nitrous oxide emissions to meet the California
Air Quality Management NOx requirement of 40
nanograms/joule or less.
c. Primary tubes on low NOx units shall be 409
stainless steel. Other components shall be alu-
minized steel.
30. Ultraviolet Germicidal Lamps:
Ultraviolet germicidal lamps are designed to elimi-
nate odor causing mold and fungus that may
develop in the wet area of the evaporator section of
the unit. The high output, low temperature germi-
cidal lamps are field installed in the evaporator sec-
tion of the unit, aimed at the evaporator coil and
condensate pan. The short wavelength ultraviolet
light inhibits and kills mold, fungus and microbial
growth. The lamps have an output rating at 45F in
400 fpm airflow of 120 microwatts/cm
2
at 1 meter.
31. Perfect Humidity™ Adaptive Dehumidification Sys-
tem:
a. The Perfect Humidity dehumidification system
shall be factory-installed in the rooftop unit, and
shall provide greater dehumidification of the
occupied space by two modes of dehumidifica-
tion operations beside its normal design cooling
mode:
1) Subcooling mode further subcools the hot
liquid refrigerant leaving the condenser coil
when both temperature and humidity in the
space are not satisfied.
2) Hot gas reheat mode shall mix a portion of
the hot gas from the discharge of the com-
pressor with the hot liquid refrigerant leav-
ing the condenser coil to create a two-
phase heat transfer in the system, resulting
in a neutral leaving-air temperature when
only humidity in the space is not satisfied.
b. The system shall consist of a subcooling/ reheat
dehumidification coil located downstream of the
standard evaporator coil. This dehumidification
coil is a two-row coil on the 005 and 006 units,
and a one-row coil on 003 and 004 units.
c. The system shall include crankcase heater(s) for
the scroll compressor(s).
d. The system shall include a low outdoor air tem-
perature switch to lock out both subcooling and
hot gas reheat mode when the outdoor-air tem-
perature is below 40 F.
e. The system shall include a Motormaster® low
ambient control to ensure the normal design
cooling mode capable of down to 0° F low ambi-
ent operation.
f. The system shall include a low-pressure switch
on the suction line to ensure low pressure start-
up of hot gas reheat mode at lower outdoor tem-
perature condition.
g. The system operation may be controlled by a
field-installed, wall-mounted humidistat. The
dehumidification circuit will then operate only
when needed. Field connections for the humidis-
tat are made in the low-voltage compartment of
the unit control box. The sensor can be set for
any level between 55% and 80% relative humid-
ity.
h. The system shall include a Thermal Expansion
Valve (TXV) to ensure a positive superheat con-
dition and a balance of pressure drop.
32. Humidistat:
Field-installed, wall-mounted humidistat is used to
control activation of the dehumidification package.
The humidistat can be set for humidity levels
between 20% and 80% relative humidity.
33. Hinged Panel Option:
Hinged panel option provides hinged access panels
for the filter, compressor, evaporator fan, and con-
trol box areas. Filter hinged panels permit tool-less
entry for changing filters. Each hinged panel is per-
manently attached to the rooftop unit.
58
1C02
4-
060
Содержание 581A
Страница 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Страница 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Страница 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Страница 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Страница 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Страница 139: ...139 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 580F036 151 AND 581B036 150 ...
Страница 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Страница 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Страница 202: ...202 TYPICAL PIPING AND WIRING 579F180 300 579F180 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Страница 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Страница 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Страница 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Страница 227: ...227 TYPICAL PIPING AND WIRING 580F180 300 LEGEND NEC National Electrical Code b48 1258 580F180 300 ...
Страница 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Страница 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Страница 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 297: ...297 ...