Fig. 45 — Location of Non-Fused Disconnect Enclosure
(Sizes 16)
To field install the NFD shaft and handle (see Fig.46 and 47):
1. Remove the unit front panel (see Fig. 2-4).
2. Remove (3) hex screws on the NFD enclosure - (2) on the
face of the cover and (1) on the left side cover.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at OFF posi-
tion (the arrow on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the shaft in
the horizontal position.
6. For sizes 08 to 14, measure from the tip of the shaft to the top
surface of the black pointer; the measurement should be 3.75
to 3.88 in. (95 to 99 mm). For size 16, measure the tip of the
shaft to the top surface of the pointer to be 3.75 to 3.88 in.
(95 to 99 mm) for 80A and 100A NFD and 3.43 to 3.56 in.
(87 to 90 mm) for 200A NFD.
7. Tighten the locking screw to secure the shaft to the NFD.
8. Turn the handle to the OFF position with red arrow pointing
at OFF.
9. Install the handle on to the painted cover horizontally with
the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws and
lock washers supplied.
11. Engaging the shaft into the handle socket, re-install (3) hex
screws on the NFD enclosure.
12. Re-install the unit front panel.
UNITS WITHOUT FACTORY-INSTALLED NON-
FUSED DISCONNECT —
When installing units, provide a
disconnect switch per NEC (National Electrical Code) of ade-
quate size. Disconnect sizing data is provided on the unit informa-
tive plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative plate if
mounting the disconnect on the unit cabinet.
Fig. 46 — Handle and Shaft Assembly for NFD
(Sizes 08-14)
Fig. 47 — Handle and Shaft Assembly for NFD (Size 16)
ALL UNITS —
Field wiring must comply with NEC and all lo-
cal codes. Size wire based on MCA (Minimum Circuit Amps) on
the unit informative plate. See Fig. 37 and 38 and the unit label di-
agram for power wiring connections to the unit power terminal
blocks and equipment ground. Maximum wire size is #2 ga AWG
per pole.
Provide a ground-fault and short-circuit over-current protection
device (fuse or breaker) per NEC Article 440 (or local codes). Re-
fer to unit informative data plate for MOCP (Maximum Over-cur-
rent Protection) device size.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is to be
connected to a 208-v power supply, the control transformer must
be rewired by moving the black wire with the
1
/
4
-in. female
spade connector from the 230-v connection and moving it to the
200-v
1
/
4
-in. male terminal on the primary side of the transform-
er. Refer to unit label diagram for additional information.
Содержание 580J*16D Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing Size 14 ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing Size 14 cont ...
Страница 8: ...8 Fig 4 Unit Dimensional Drawing Size 16 ...
Страница 9: ...9 Fig 4 Unit Dimensional Drawing Size 16 cont ...
Страница 15: ...15 Fig 9 580J 16 Roof Curb Details ...
Страница 32: ...32 Fig 58 580J 08 14 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 33: ...33 Fig 59 580J 16 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 48: ...48 Fig 67 580J 08 12N P Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 68 580J 08 14 Typical RTU Open System Control Wiring Diagram ...
Страница 50: ...50 Fig 69 580J 16 Typical RTU Open System Control Wiring Diagram ...
Страница 51: ...51 Fig 70 580J 8 14 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...
Страница 52: ...52 Fig 71 580J 16 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...