For damper minimum position settings and checkout menu
readings, see Table 13. For dry bulb operation with a 1 speed in-
door fan, with or without DCV, see Tables 14 and 15. For enthalpy
operation with a 1 speed indoor fan, with or without DCV, see
Tables 16 and 17. For dry bulb operation with a 2 speed indoor
fan, with or without DCV, see Tables 18 and 19. For enthalpy op-
eration with a 2 speed indoor fan, with or without DCV, see Tables
Table 13 — Damper Minimum Position Settings and Readings on Checkout Menu
Table 14 — Dry Bulb Operation No DCV (CO
2
Sensor) — 1 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
Table 15 — Dry Bulb Operation With DCV (CO
2
Sensor) — 1 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
DEMAND CONTROLLED
VENTILATION
(CO
2
SENSOR)
FAN SPEED
SETPOINTS
CHECKOUT
NO
1
MIN POS
VMAX–HS
N/A
N/A
2
MIN POS H
VMAX–HS
MIN POS L
VMAX–LS
YES
1
VENT MIN
VMAX–HS
VENT MAX
VMAX–HS
2
VENT MIN H
VMAX–HS
VENT MAX H
VMAX–LS
VENT MIN L
N/A
VENT MAX L
N/A
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NONE
NO
OFF
OFF
HIGH
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
HIGH
24v/On
0v/Off
MIN POS
Closed
ON
ON
HIGH
24v/On
24v/On
MIN POS
Closed
NONE
YES
OFF
OFF
HIGH
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
HIGH
0v/Off
0v/Off
MIN POS to Full
Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off*
MIN POS to Full
Open
Closed to Full-Open
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below CO
2
Set
No
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
HIGH
24v/On
0v/Off
VENTMIN
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN
Closed
Yes
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
Above CO
2
Set
No
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
HIGH
24v/On
0v/Off
VENTMIN to
VENTMAX
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN to
VENTMAX
Closed
Yes
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off*
VENTMIN to
Full-Open
Closed to Full-Open
Содержание 580J*16D Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing Size 14 ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing Size 14 cont ...
Страница 8: ...8 Fig 4 Unit Dimensional Drawing Size 16 ...
Страница 9: ...9 Fig 4 Unit Dimensional Drawing Size 16 cont ...
Страница 15: ...15 Fig 9 580J 16 Roof Curb Details ...
Страница 32: ...32 Fig 58 580J 08 14 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 33: ...33 Fig 59 580J 16 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 48: ...48 Fig 67 580J 08 12N P Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 68 580J 08 14 Typical RTU Open System Control Wiring Diagram ...
Страница 50: ...50 Fig 69 580J 16 Typical RTU Open System Control Wiring Diagram ...
Страница 51: ...51 Fig 70 580J 8 14 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...
Страница 52: ...52 Fig 71 580J 16 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...