Table 12 —Menu Structure* (cont)
LEGEND
* Table 12 illustrates the complete hierarchy. Your menu
parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
2
) sensor, then none
of the DCV parameters appear.
† When values are displayed, pressing and holding the
or
button causes the display to automatically increment.
** N/A = Not Applicable.
†† ERV Operation: When in cooling mode AND the conditions are
NOT OK for economizing - the ERV terminal will be energized.
In the Heating mode, the ERV terminal will be energized when
the OA is below the ERV OAT setpoint in the setpoint menu.
NOTES:
1.
STATUS —> OCCUPIED — The factory-standard Occupancy sig-
nal originates with a thermostat or other controller call for indoor
fan operation at CTB terminal G. This signal passes through the
Central Terminal Board’s OCCUPIED jumper JMP1 to the
ECONO connector and to the W7220’s OCC input terminal. An
external timeclock or relay is required to implement an Occu-
pancy schedule on the economizer damper position.
2.
STATUS —> MA TEMP, SETPOINTS —> MAT SET — The W7220
menu parameters and labels include designations MA, MAT and
Mixed Air for the economizer cooling control sensor. On these roof-
top units, the economizer control sensor is located downstream of
the evaporator/indoor coil in the supply fan section where this sensor
is designated as Supply Air Temperature (SAT) sensor.
3.
SETPOINTS —> DRYBLB SET — This point is not displayed if a
Return Air (differential) temperature sensor or an Outdoor Air enthal-
py sensor is connected.
4.
SYSTEM SETUP parameters must be configured as noted for
2-Speed unit operation:
EQUIPMENT = CONV
AUX2 I = W
FAN SPEED = 2SPEED
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
NOTES
ALARMS
(CONT)
SHUTDOWN ACTIVE
N/A
N/A
AUX2 IN is programmed for SHUTDOWN and 24 V has been applied to
AUX2 IN terminal.
DMP CAL RUNNING
N/A
N/A
DAMPER CALIBRATION ROUTINE RUNNING
If DCV Auto enable has been programmed, when the W7220 is complet-
ing a calibration on the dampers, this alarm will display. Wait until the
calibration is completed and the alarm will go away. Must have OA, MA
and RA sensors for DCV calibration; set up in the Advanced setup
menu.
DA SENS ALM
N/A
N/A
DISCHARGE AIR TEMPERATURE SENSOR ALARM
Discharge air temperature is out of the range set in the ADVANCED
SETUP Menu. Check the temperature of the discharge air.
SYS ALARM
N/A
N/A
When AUX1-0 is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX1-0 terminal has 24 Vac out.
ACT UNDER V
N/A
N/A
ACTUATOR VOLTAGE LOW
Voltage received by actuator is above expected range.
ACT OVER V
N/A
N/A
ACTUATOR VOLTAGE HIGH
Voltage received by actuator is below expected range.
ACT STALLED
N/A
N/A
ACTUATOR STALLED
Actuator stopped before achieving commanded position.
CLO —
Compressor Lockout
ERV
—
Energy Recovery Ventilator
LCD
—
Liquid Crystal Display
MA
—
Mixed Air
MAT —
Mixed Air Temperature
N/A
—
Not Applicable
OA
—
Outdoor Air
OAT —
Outdoor Air Temperature
OCC —
Occupied
RA
—
Return Air
RAT
—
Return Air Temperature
RTU
—
Rooftop Unit
SYS
—
System
Содержание 580J*16D Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing Size 14 ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing Size 14 cont ...
Страница 8: ...8 Fig 4 Unit Dimensional Drawing Size 16 ...
Страница 9: ...9 Fig 4 Unit Dimensional Drawing Size 16 cont ...
Страница 15: ...15 Fig 9 580J 16 Roof Curb Details ...
Страница 32: ...32 Fig 58 580J 08 14 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 33: ...33 Fig 59 580J 16 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 48: ...48 Fig 67 580J 08 12N P Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 68 580J 08 14 Typical RTU Open System Control Wiring Diagram ...
Страница 50: ...50 Fig 69 580J 16 Typical RTU Open System Control Wiring Diagram ...
Страница 51: ...51 Fig 70 580J 8 14 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...
Страница 52: ...52 Fig 71 580J 16 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...