background image

5

space, the number of windows and ventilation openings, the
number of doors to the outside, internal doors which can close off

unconfined space, and overall tightness of building construction.
Consideration must also be given to the amount of storage items

(furniture, boxes, etc.) within the unconfined space which take

away from the air volume. (Refer to Table 2.)

Table 2 – Minimum Floor Area For Unconfined Space

FURNACE

INPUT BTUH / kW

MINIMUM FT

2

(M

2

) WITH

7---1/2 FT (2.3 M) CEILING

70,000

467 (43.4)

91,000

607 (56.3)

105,000

700 (65.0)

119,000

793 (73.6)

140,000

933 (86.6)

154,000

1026 (95.3)

Many new buildings and homes (and older ones that have been
weatherized) MUST BE considered as being of tight construction,

therefore infiltration will not be sufficient to supply necessary air
for combustion and ventilation.
A building can be considered as being of tight construction when:

1. Walls and ceilings exposed to outside atmosphere have a

continuous water vapor retarder with a rating of 1 perm or
less with openings gasketed or sealed; and/or

2. Weatherstripping has been added on operable windows and

doors, and/or caulking or sealants are applied to areas such

as joints around windows and door frames; between sole
plates and floors; between wall--ceiling joints; between wall
panels; at penetrations for plumbing, electrical, and fuel

lines; and at other openings.

If combustion and ventilation air must be supplied to an

unconfined space from outside, an opening with a FREE AREA of
not less than 1 in.

2

per 5,000 BTUH (4400 mm

2

/ kW)of total

input of all appliances within unconfined space (but not less than

100 in.

2

(64516 mm

2

) must be provided. This opening must be

located such that it cannot be blocked at any time.

Confined Space

A confined space has a volume of less than 50 ft

3

(1.4 M

3

) per

1,000 BTUH of the total input rating for all appliances installed in
that space.

NOTE

: In calculating free area, consideration shall be given to

blocking effect of louvers, grilles, or screens protecting openings.
Screens used shall not be smaller than 1/4--in. (6 mm) mesh and
shall be readily accessible for cleaning. If free area through a louver
or grille is known, it shall be used in calculating size and free area
specified. If design and free area are not known, it may be assumed
that wood louvers have 20% free area and metal louvers and grilles
have 60% free area. Louvers shall be fixed in open position or
interlocked with furnace so they open automatically at furnace
start--up and remain open during furnace operation.
The size of the openings depends upon whether the air comes from

outside of the structure or an unconfined space inside the structure.

All Air From Inside the Structure

For a confined space, where air is taken from an interior space, 2
permanent openings of equal area are required. One opening must

be within 12 in. (305 mm) of ceiling and the other within 12 in.

(305 mm) of floor.

All Air From Outside of Structure

If outside air is supplied to a confined space, then the 2 openings

must be equal and located as above.

1. If combustion air is taken through a permanent opening

directly communicating with the outdoors, the opening shall
have a minimum free area of 1 in.

2

per 4,000 BTUH (550

mm

2

/kW)of total input rating for all equipment in the

enclosure.

2. If combustion air is taken from outdoors through vertical

ducts, the openings and ducts MUST have at least 1 in.

2

of

free area per 4,000 BTUH of the total input for all
equipment within the confined space. (See Fig. 4 and 5.)

3. If combustion air is taken from outdoors through horizontal

ducts, the openings and ducts MUST have at least 1 in.

2

of

free area per 2,000 BTUH (1100 mm

2

/kW)of the total input

for all equipment within the confined space. (See Fig. 6.)

When ducts are used to supply air, they must be of the same cross

sectional area as free area of openings to which they connect. (See
Fig. 7.)
The minimum dimension of rectangular air ducts must not be less
than 3 in. (76 mm).

Step 3 — Ductwork Recommendations

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury

or death.
When supply ducts carry air circulated by furnace to areas

outside spaces containing furnace, return air MUST also be

handled by a duct sealed to furnace casing and terminating

outside space containing furnace.

!

WARNING

UNIT MAY NOT OPERATE

Failure to follow this caution may result in intermittent unit

operation.
Return--air grilles and warm air registers MUST NOT be

obstructed.

CAUTION

!

The proper sizing of warm air ducts is necessary to ensure
satisfactory furnace operation. Ductwork should be in accordance

with the latest editions of NFPA--90A (Installation of Air
Conditioning and Ventilating Systems) and NFPA--90B (Warm Air

Heating and Air Conditioning Systems) or Canadian equivalent.
The supply ductwork should be attached to flanged front opening

provided at discharge end of furnace. The return--air ductwork

should be attached to flanged rear opening of furnace. See Fig. 2
for dimensions of these openings.

NOTE

: The blower access opening should not be used for return

air.
The following recommendations should be followed when

installing ductwork:

1. Install locking--type dampers in all branches of individual

ducts to balance out system. Dampers should be adjusted to
impose proper static at outlet of furnace.

2. A flexible duct connector of noncombustible material

should be installed at unit on both supply-- and return--air

systems. In applications where extremely quiet operation is
necessary, the first 10 ft. (3.0 M) (if possible) of supply and

return ducts should be internally lined with acoustical
material.

3. In cases where return--air grille is located close to fan inlet,

there should be at least one 90

_

air turn between fan inlet

and grille. Further reduction in sound level can be

accomplished by installing acoustical air--turning vanes or
lining duct as described in item 2 above.

4. When a single air grille is used, duct between grille and

furnace must be the same size as return opening in furnace.

374RAN

Содержание 374RAN

Страница 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Страница 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Страница 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Страница 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Страница 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Страница 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Страница 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Страница 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Страница 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Страница 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Страница 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Страница 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Страница 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Страница 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Страница 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Страница 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Страница 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Страница 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Страница 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Страница 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Страница 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Страница 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Отзывы: