background image

17

Table 7 – 374RAN105 Dip Switch Adjustment for Oil Heating

Mode

SW1---HEAT DIP SWITCH

POSITION

INPUT

USGPH

SW4---DELAY DIP

SWITCH POSITION

INPUT

USGPH

1

2

1

2

Off

Off

0.75

Off

Off

0.75

On

Off

0.65

On

Off

0.65

Off

On

0.5

Off

On

0.5

On

On

N/A

On

On

NA

Table 8 – 374RAN105 Size Dip Switch Adjustments for Heat

Pump and Cooling Mode

SW2---COOL DIP SWITCH POSITION

A/C SIZE (TONS)

1

2

Off

Off

3.0

On

Off

2.5

Off

On

2.0

On

On

1.5

Table 9 – 374RAN105 Size Dip Switch CFM Adjustments in

All Modes

SW3---ADJUST DIP SWITCH

POSITION

HEATING CFM %

INCREASE OR

DECREASE

COOLING CFM %

INCREASE OR

DECREASE

1

2

Off

Off

0

0

On

Off

+13

+10

Off

On

---15

---10

On

On

N/A

0

Table 10 – 374RAN120 Size Dip Switch Adjustment for Oil

Heating Mode

SW1---HEAT DIP SWITCH

POSITION

INPUT

USGPH

SW4---DELAY DIP

SWITCH POSITION

INPUT

USGPH

1

2

1

2

Off

Off

0.85

Off

Off

0.85

On

Off

1.00

On

Off

1.0

Off

On

1.10

Off

On

1.10

On

On

N/A

On

On

NA

Table 11 – 374RAN120 Size Dip Switch Adjustments for Heat

Pump and Cooling Mode

SW2---COOL DIP SWITCH POSITION

A/C SIZE (TONS)

1

2

Off

Off

5.0

On

Off

4.0

Off

On

3.5

On

On

3.0

Table 12 – 374RAN120 Size Dip Switch CFM Adjustments in

All Modes

SW3---ADJUST DIP SWITCH

POSITION

HEATING CFM %

INCREASE OR

DECREASE

COOLING CFM %

INCREASE OR

DECREASE

1

2

Off

Off

0

0

On

Off

+13

+10

Off

On

---15

---10

On

On

N/A

0

FIRE HAZARD AND UNIT RELIABILITY

Failure to follow this warning could result in property

damage, personal injury, or death.
When operating furnace in heating mode, static pressure

and temperature rise (supply--air temperature minus

return--air temperature) must be within those limits specified

on rating label.

!

WARNING

Step 5 — Limit--Control Check

After furnace has been in operation for at least 15 minutes, restrict

return--air supply by blocking filters or closing return registers and
allow furnace to shut down on high limit. The burner should shut

off and main blower should continue to run.

Step 6 — For Year--Round Air Conditioning

This furnace is designed for use in conjunction with cooling
equipment to provide year--round air conditioning. The blower has

been sized for both heating and cooling, however fan--motor
setting may need to be changed to obtain necessary cooling

airflow.

CARE AND MAINTENANCE

ELECTRICAL SHOCK, FIRE, EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
The ability to properly perform maintenance on this equipment

requires certain expertise, mechanical skills, tools, and

equipment.

If you do not possess these, do not attempt to

perform any maintenance on this equipment other than those

procedures recommended in the User’s Manual.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before performing any service functions, unless operations

specifically require power to be on, make sure all utilities

are turned off upstream of appliance.

!

WARNING

Step 1 — General

In order to keep this furnace in good operating condition and to

maintain its warranty, the furnace MUST be serviced on an annual
basis. This servicing includes a nozzle change, a burner inspection,

a visual check of tube passages through flue outlet and clean--out
ports, and a visual inspection of combustion chamber when burner

is removed.

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal

injury or death.
Failure to replace any heat exchanger gaskets with new

gaskets when any heat exchanger plates or covers are

removed could lead to heat exchanger leakage or sooting.

!

WARNING

374RAN

Содержание 374RAN

Страница 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Страница 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Страница 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Страница 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Страница 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Страница 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Страница 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Страница 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Страница 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Страница 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Страница 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Страница 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Страница 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Страница 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Страница 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Страница 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Страница 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Страница 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Страница 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Страница 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Страница 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Страница 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Отзывы: