QmB Series IP40, IP65, IP65XP
Section 5 Specifications
5-6
Installation and Operation Manual
X-CM-QmB-eng
Part Number: 541B029AHG
June, 2008
Power Requirements:
Voltage:
+14 to 27 Vdc.
Nominal Current:
Controller: 300 mA to 400 mA
Meter: 100 mA to 150 mA
Maximum Current:
Controller: 715 mA @ 14 Vdc
Meter: 470 mA @ 14 Vdc
Maximum Power:
Controller: 10.0 W
Meter: 6.6 W
Additional Functions and Outputs
Damping:
Factory set time constant from 0 to 10 seconds.
Alarms and Warnings:
Alarms accessed via HART or the Brooks Service Tool can be
configured
to monitor the following variables:
•
Mass Flow
•
Density
•
Volumetric Flow
•
Temperature
•
Slug Flow
•
Diagnostic Failure
•
Setpoint Deviation
•
Valve Drive
LED's:
(11)
'STAT'
solid green: system operative.
solid red: system fault.
'AL'
flashing green: warning
flashing red: alarm
Pushbutton:
(12)
'ZERO' setting pushbutton.
Notes (continued)
(10)
If QUANTIM is configured for HART
®
communication protocol, only 4-20 mA I/O option is available.
(11)
IP65 and IP65XP Series external housing cover must be removed to gain access to status LED's.
(12)
IP65XP series external housing cover must be removed to gain access to zero push button.