FIGURE 52 Fan module led indicators
1.
Power LED
2.
Fault LED
2. Interpret the LED indicators and take the appropriate action.
TABLE 15 Fan LED descriptions
LED purpose
Color
Status
Recommended action
OK
No light (LED is off)
Fan does not have power.
Ensure that the fan is firmly
seated and has power.
Steady green
Fan has power.
No action required.
Fault
No light (LED is off)
Fan is either healthy or does not
have power.
Ensure that the fan has power.
Steady amber
Fan has a failure (full or partial).
Replace the fan.
3. Determine the fan status using the show environment fan command. (Alternately, you can use the show system command. )
System Monitoring
Brocade VDX 8770-4 Hardware Installation Guide
53-1002563-10
99