12
4.3 External Installation
4.3.1 Service Clearances
Front/Back
A minimum of 500mm must be provided at the side facing away from the house.
End
A minimum of 300mm must be provided at each end of the heater.
Top
A minimum of 1000mm must be provided above the heater roof. This clearance must be maintained for the entire
surface area of the heater roof.
4.3.2 Installation of Flashing
The flashing must be fitted to ensure the ductwork is adequately weather protected.
4.3.3 Installation of Flue Terminal
On one end of the heater you will find the flue outlet socket under an installer instruction label.
Remove the label and insert the flue terminal firmly into the flue outlet socket in the correct orientation to ensure the
flue gases are expelled away from the house (see Diagram 9 on page 9).
Note:
The flue terminal must be ordered separately when SP4 is used externally, Brivis Part No. B021385.
Note:
The flue terminal must always be installed before starting the heater.
4.3.4 Flue Terminal Clearances
Heaters should be positioned so that when measured from the edges of the flue the following minimum clearances
exist.
75mm
• From the wall against which the heater is mounted.
• From a drain or soil pipe.
300mm
• From a flue terminal, cowl or combustion air intake.
• Below eaves, balconies or other projections.
• From the ground, above a balcony or other surface.
• To a return wall or external corner.
• Measured horizontally, from an opening window, door, non-mechanical air inlet or any other opening into the
building (except sub floor ventilation) or 1500mm in direction of discharge.
500mm
• From an electricity meter or fuse box (prohibited area extends to ground level).
1000mm
• Measured vertically, from an opening window, door, non-mechanical air inlet or any other opening into the
building (except sub floor ventilation).
• From a gas meter.
• From a mechanical air inlet, including a spa blower, measured both vertically and horizontally.
• A flue terminal of this type shall not be located under a roofed area, unless the roofed area is fully open on at
least two sides, and a free flow of air at the appliance is achieved.