7.4 Installation of Flue Terminal
The flue terminal is supplied and fitted to the heater as seen in Diagram 16. The flue terminal must be
orientated correctly to ensure flue gases are expelled away from the house (see Diagram 9, page 9).
Note:
The flue terminal must always be installed before starting the heater.
7.5 Flue Terminal Clearances
Heaters should be positioned so that when measured from the edges of the flue the following minimum
clearances exist.
75mm
• From the wall against which the heater is mounted.
• From a drain pipe or soil pipe.
300mm
• From a flue terminal, cowl or combustion air intake.
• Below eaves, balconies or other projections.
• From the ground, above a balcony or other surface.
• To a return wall or external corner.
• Measured horizontally, from an openable window, door, non-mechanical air inlet or any other opening into a
building with the exception sub-floor ventilation.
500mm
• From an electricity meter or fuse box (prohibited area extends to ground level).
• Horizontally from any building structure
1000mm
• Measured vertically, from an openable window, door, non-mechanical air inlet or any other opening into a
building with the exception of sub-floor ventilation.
• From a gas meter.
• From a mechanical air inlet, including a spa blower, measured both vertically and horizontally.
• A flue terminal of this type shall not be located under a roofed area, unless the roofed area is fully open on at
least two sides, and a free flow of air at the appliance is achieved.
8. SP4, SP5, SP6 & BX5 - Adaptive Zoning & Add-On Air Conditioning
All Brivis StarPro Series Heaters (SP4, SP5, SP6 & BX5) fitted with an NG-2 PCB, will require
the use of a Brivis Network 516 Module (Part no. B023178) when used with Brivis ICE Add-
on Cooling.
StarPro heaters can be configured for adaptive zoning and/or Add-On Refrigerative Air Conditioning.
There are two 24 Vac relays on the heater’s control module, which can be configured for control of up to two
zone motors, shown in the Diagram 17 below.
For Add-on refrigerative air conditioning and control of up to three zones a ‘Brivis Network 516 module’ (Part
No. B023178) must be fitted.
Diagram 17.
StarPro Control module
Note:
Refer to Brivis Network 516 module installation instructions for further information.
Refer to Brivis Networker Advanced Programming manual for zone setup on the Brivis Networker Thermostat.
For Brivis ZonePlus configuration, please refer to the ZonePlus Installation Manual.