Not for
Reproduction
18 BRIGGSandSTRATTON.COM
Symphony
®
II Power Monitor (Optional)
For your convenience, a Symphony® II Power Monitor is available,
which provides a visual “on/off” status of each managed appliance/
load. A series of LED lights are ON when an appliance has
generator power and OFF when the appliance is in a shed mode or
does not have power. When on generator power, the consumer can
see which appliances are being managed.
POWER LIGHT (
E
)
When lit, indicates that monitor
detects outlet power.
When not lit, indicates that no
power is present at outlet.
COMM (communication status)
LIGHT (
F
)
When lit, indicates that unit
is receiving signals from the
Symphony® II controller.
When not lit, indicates that utility
power is present or a fault in
Symphony® II controller.
A decal is provided that can be labeled with the managed
appliances/loads and placed next to each priority LED.
The monitor is plugged into any convenient standard outlet within
the home and constantly receives system status via the power line
communication technology utilized by the Symphony® II Power
Management System during generator power.
Status LED’s
Described below are the system’s LED indicators and the conditions
each LED color represents:
Transfer Switch Control Board
STATUS LED
RED (
A
) means GENERATOR power is present.
GREEN (
B
) means UTILITY power is present.
Symphony® II System Control Board
STATUS LED (
C
)
Single Blink-Pause means unit is operating on GENERATOR power.
Double Blink–Pause means unit is operating on UTILITY power.
PRIORITY LIGHTS/LED’s (
D & G
)
When green LED is lit, indicates that optional remote module set to
that priority is supplying power to connected load during generator
power.
When not lit, indicates that optional remote module set to that
priority is set to OFF (being managed and Symphony® II System is
not allowing power to the unit).
All lights/LED’s are OFF when utility power is present.
CT1
CT2
DPSW2
DPSW1
J6
J5
J4
J3
J2
J1
A
B
E
F
G
312113
LED
LED
LED
LED
LED
LED
LED
LED
LED
C
D
Содержание 071132
Страница 22: ...N o t f o r R e p r o d u c t i o n 22 BRIGGSandSTRATTON COM Transfer Switch Schematic Diagram ...
Страница 23: ...N o t f o r R e p r o d u c t i o n 23 Transfer Switch Schematic Diagram continued ...
Страница 47: ...N o t f o r R e p r o d u c t i o n 23 Diagrama esquemático del interruptor de transferencia ...
Страница 70: ...N o t f o r R e p r o d u c t i o n 22 BRIGGSandSTRATTON COM Schéma du commutateur de transfert ...
Страница 71: ...N o t f o r R e p r o d u c t i o n 23 Schéma du commutateur de transfert suite ...