Not for
Reproduction
12 BRIGGSandSTRATTON.COM
12. Connect conductor from transfer switch neutral terminal to
generator NEUTRAL terminal. Observe generator control panel
labeling for terminal identification.
13. Connect conductor from transfer switch “GND” terminal to
generator control panel “GROUND” terminal.
Assure generator equipment grounding conductor is
connected per applicable federal, state and local codes,
standards and regulations.
14. Using minimum #14 AWG conductors, connect the transfer
switch “UTILITY 240 VAC” terminals (
L
) to generator’s “240
VAC” terminals via two-pole connector (
M
) supplied with
generator (refer to the illustration on the transfer switch
wiring diagram).
NOTICE
TxRx and TxRx GND communication wiring must be connected
for the Symphony® II System to operate properly.
15. Using minimum #18 AWG twisted pair copper or aluminum
conductors, no greater than 200 ft. in length, 300 volt
75°C-90°C, connect “T/R” and “GND” terminals on transfer
switch control board (
B
) to the generator’s control panel (
A
)
“TxRx” and “TxRx GND” terminals via ten pin connector or
eight pin terminal. Count down to the proper pin location on
the generator control board since visual alignment with its
decal can be misleading:
16. Install optional remote modules using the installation
instructions provided with each module. Set each module to
the agreed-upon priority setting.
17. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure or values listed in
remote module installation instructions for proper
torque values.
Supervisory Control Terminals
To avoid undesirable operation, we recommend loads be managed
only with low voltage or 50 Amp remote modules. Do not use the
transfer switch control board supervisory control terminals
(if present).
The illustration on the following page shows a completed transfer
switch installation. Your actual layout will vary.
Illustration callouts are:
A
- From utility watt-hour meter
B
- Current transformers
C
- Transfer switch enclosure
D
- Symphony® II system control board
E
- T/R and GND to Generator
F
- Transfer switch control board
G
- Neutral terminal
H
- Neutral bus
J
- Ground bus
K
- Main distribution panel
L
- UTILITY 240VAC to Generator
M
- Two pin connector or Two pin terminal block
N
- Ten pin connector or Eight pin terminal block
P
- Generator circuit breaker
R
- Generator
S
- Generator Neutral terminal
T
- Generator Ground terminal
U
- Transfer switch ground terminal
V
- Load connection to distribution panel
W
- Utility disconnect circuit breaker
X
- Utility connection
Y
- Generator connection
Z
- Neutral to ground bond
AA
- Compartment for utility connections
A
B
A
B
OR
Содержание 071132
Страница 22: ...N o t f o r R e p r o d u c t i o n 22 BRIGGSandSTRATTON COM Transfer Switch Schematic Diagram ...
Страница 23: ...N o t f o r R e p r o d u c t i o n 23 Transfer Switch Schematic Diagram continued ...
Страница 47: ...N o t f o r R e p r o d u c t i o n 23 Diagrama esquemático del interruptor de transferencia ...
Страница 70: ...N o t f o r R e p r o d u c t i o n 22 BRIGGSandSTRATTON COM Schéma du commutateur de transfert ...
Страница 71: ...N o t f o r R e p r o d u c t i o n 23 Schéma du commutateur de transfert suite ...