SN2004/IR, SN2024/IR
Installation
4
6/29/12
Bradley
• 215-1071 Rev. J; ECN 12-00-011
Supplies from Above
Supplies from Below or Through Wall
Standard height floor-mounted models
with Infrared or hand control are ADA
compliant.
Rough-In Dimensions for Supplies and Drain
Notes
Maximum flow rate required to washfountain is 1.5 GPM. Size supply lines accordingly.
Supplies from Below: Stub up 2-1/2" (64).
Supplies from Above: Supplies must be located on centers of dimaensions shown to pass
through washfountain shroud and sprayhead.
Drain through floor: Stub up 3" (76).
Type B
Centrally rising vent
(P-Trap furnished with unit.)
Type O
Off-line vent
(P-Trap supplied by Installer.)
Type A
Off-line vent
(P-Trap supplied by Installer.)
Type H
Centrally rising vent
(P-Trap furnished with unit.)
Top View
Top View
1/2" Supply: Nominal Copper Tube
1/2" Supply Through Wall (Optional): Nominal Copper Tube
1-1/2" NPT Drain
1-1/2" NPT Vent
Key
When running supplies and drain through wall, use same horizontal measurements as shown in Top View.
Postion openings above the finished floor, at the following dimensions (to center):
Drain:
Standard Height: 19-1/4" (305)
Juvenile Height: 15-1/4" (387)
Supplies: Standard Height: 12" (305)
Juvenile Height: 8" (203)
Floor-mounted units: UPC and IPC restrict the vertical
distance from the fixture outlet to the trap weir to not more
than 24" (610). Check state and local codes for variances.
H
H
C
C
H
H
C
C
(mm)
5"
(127)
5"
(127)
4-1/2"
(114)
2-3/4"
(70)
CL
5"
(127)
9-1/4"
(235)
4-1/2"
(114)
4-1/2"
(114)
2-3/4"
(70)
CL
8-1/16"
(205)
2-3/4"
(70)
27/32"
(21)
27/32"
(21)
CL
9-1/4"
(235)
8-1/16"
(205)
2-3/4"
(70)
27/32"
(21)
27/32"
(21)
CL