MAP 5000
Appendices | en
75
Bosch Security Systems B.V.
Installation manual
2019-09 | 25 | F.01U.168.332
2.
Using the wizard, program one output with the behavior item
Area Armed
and a second
output with the behavior item
Area Disarmed
.
3.
The signal must be time-limited. Enter a corresponding time (typically 10 sec. / maximum
30 seconds) for
Activation Duration
.
Securing access route against unauthorized entry in armed state, e.g. by installing a
blocking element
1.
Connect a free output with the device
LED
.
2.
Variant A: Blocking element is actively controlled CLOSED. Using the wizard, program an
output with the behavior item
Area Armed
or
Variant B: Blocking element is actively controlled OPEN. Using the wizard, program an
output with the behavior item
Area Disarmed
.
3.
The signal must be static; enter 00:00:00 for
Activation Duration
.
4.
Refer to the manufacturer's connection instructions for further information.
8.2.4
Arming / disarming with entry / exit delay
Arming inside the secured area, e.g. with control center
1.
Include a new area if not yet present.
2.
Include a control center if not yet present.
3.
Include the area in the scope of the control center:
Local Area
.
4.
Program control center for arming with exit delay:
Use Area Normal Delay Time
.
5.
The value for the entry / exit delay can be adapted if required:
Area Manager > Area >
Timing and Delays
:
normal entry delay (typically 45 sec. / at least 30 sec.)
normal exit delay (typically 60 sec.)
Programming entry / exit route
1.
Program all points of the entry / exit route to the point type intrusion.
2.
Select the type of exit point optionally for exit route points:
Exit point type
Behavior
Initial follower
1
Point without prevention of arming readiness, e.g. PIR that has the
control center in the detection area. Important: point must be in
normal state after exit, otherwise an alarm will be tripped
Follower
1
Point that does not trip an alarm as long as the exit delay is
running. Only relevant for option
MAP5000 Panel > Armed State At
Exit Delay Start
Exit
Door point that must be mandatorily tripped once upon leaving the
area. The option
MAP5000 Panel > Unvacated Premises
must be
activated
Interrupt
Door point that shortens the running exit delay to 10 sec.
(recommended)
Restart
Point that restarts the exit delay; possible only once during the exit
Tab.
8.3:
Exit point types
1)
Not for EN 50131
Содержание ICP-MAP5000-2
Страница 1: ...MAP 5000 ICP MAP5000 2 ICP MAP5000 COM ICP MAP5000 S ICP MAP5000 SC en Installation manual ...
Страница 2: ......
Страница 87: ...MAP 5000 Appendices 87 Bosch Security Systems B V Installation manual 2019 09 25 F 01U 168 332 ...
Страница 88: ...88 Appendices MAP 5000 2019 09 25 F 01U 168 332 Installation manual Bosch Security Systems B V ...
Страница 89: ......