6
en | Introduction
MAP 5000
2019-09 | 25 | F.01U.168.332
Installation manual
Bosch Security Systems B.V.
–
Follow anti-static procedures when handling system components. Ensure that you are
properly grounded to discharge any static charge before you work with system
components.
–
Install all components in dry, maintained interior rooms.
–
Install the system in a centrally located room that is near the AC Power MAINS.
–
Because the panel is permanently connected equipment, a readily accessible disconnect
device must be included into the building installation wiring.
Danger!
Electric shock
Danger of electric shock if live parts are touched. The alarm system is designed for an IT-
power distribution system (230 V). Switch off the power supply of the alarm system before
carrying out maintenance or installation work.
1.5
Planning the system
MAP control panel enclosure kit
The ICP-MAP0111 panel enclosure kit is the main system enclosure. This enclosure is designed
to contain the following components:
–
ICP-MAP5000 main panel
1
–
ICP-MAP0007 DE module
1
–
ICP-MAP0010 LSN gateway
1
–
ICP-MAP0012 CAN splitter
1
–
AT 2000 communicator
2
–
IPP-MAP0005 power supply
3
–
ICP-MAP0065 AC terminal block
4
–
ICP-MAP0050 control panel enclosure tamper switch
–
Two batteries (maximum 45 Ah each)
Use the ICP-MAP0120 expansion enclosure kit when the system requirements for power and /
or other remote devices exceed the capacity provided by the ICP-MAP0111 panel enclosure
kit
6.
MAP expansion enclosure kit
The ICP-MAP0120 expansion enclosure kit is designed to contain the following components:
–
IPP-MAP0005 power supply
3
–
ICP-MAP0010 LSN gateway
5
–
ICP-MAP0012 CAN splitter
1
–
ICP-MAP0065 AC terminal block
4
–
ICP-MAP0055 expansion enclosure tamper switch
–
Two batteries (maximum 18 Ah each)
Use the ICP-MAP0115 power enclosure kit when system power requirements exceed the
power capacity of the ICP-MAP0111 panel enclosure kit
6
.
MAP power enclosure kit
The ICP-MAP0115 power enclosure kit is designed to contain the following components:
–
IPP-MAP0005 power supply
3
–
ICP-MAP0065 AC terminal block
4
–
ICP-MAP0050 control panel enclosure tamper switch
–
Four batteries (maximum 40 Ah each)
Содержание ICP-MAP5000-2
Страница 1: ...MAP 5000 ICP MAP5000 2 ICP MAP5000 COM ICP MAP5000 S ICP MAP5000 SC en Installation manual ...
Страница 2: ......
Страница 87: ...MAP 5000 Appendices 87 Bosch Security Systems B V Installation manual 2019 09 25 F 01U 168 332 ...
Страница 88: ...88 Appendices MAP 5000 2019 09 25 F 01U 168 332 Installation manual Bosch Security Systems B V ...
Страница 89: ......