10
en | Introduction
MAP 5000
2019-09 | 25 | F.01U.168.332
Installation manual
Bosch Security Systems B.V.
Figure
1.5: Up to 8 control centers
Key
Description
1
Current limitation
2
4-wire connection, take into account cable length, refer to , page 10
3
3-wire connection to the next power supply segment
4
Short-time current limitation to 3.2 A per output A / B
Cable length
The maximum number of control centers that can be supplied by one power supply depends
greatly on the length and diameter of the cable used.
Wire diameter
Wire cross-
section
Length A
Length B
Length C
Length D
0.8 mm
0.503 mm
2
.
325 m
- - -
- - -
- - -
0.8 mm
0.503 mm
2
.
100 m
135 m
- - -
- - -
0.8 mm
0.503 mm
2
.
50 m
225 m
- - -
- - -
0.8 mm
0.503 mm
2
.
50 m
50 m
50 m
- - -
1.0 mm
0.785 mm
2
.
500 m
- - -
- - -
- - -
1.0 mm
0.785 mm
2
.
175 m
175 m
- - -
- - -
1.0 mm
0.785 mm
2
.
100 m
325 m
- - -
- - -
1.0 mm
0.785 mm
2
.
100 m
75 m
75 m
- - -
1.0 mm
0.785 mm
2
.
50 m
400 m
- - -
- - -
1.0 mm
0.785 mm
2
.
50 m
125 m
125 m
- - -
1.0 mm
0.785 mm
2
.
50 m
50 m
50 m
50 m
Tab.
1.1:
Cable lengths
The following applies for VdS
For remote operation of the IPP-MAP0005 power supply, a control center assigned to the
same area must be provided for indication of power supply trouble (trouble in mains supply /
battery).
Содержание ICP-MAP5000-2
Страница 1: ...MAP 5000 ICP MAP5000 2 ICP MAP5000 COM ICP MAP5000 S ICP MAP5000 SC en Installation manual ...
Страница 2: ......
Страница 87: ...MAP 5000 Appendices 87 Bosch Security Systems B V Installation manual 2019 09 25 F 01U 168 332 ...
Страница 88: ...88 Appendices MAP 5000 2019 09 25 F 01U 168 332 Installation manual Bosch Security Systems B V ...
Страница 89: ......