E9
Failure in the thermal fuse that opens circuit (Temp = 114 ºC)
Characteristic: Thermal fuse (located at control unit back cover)
Lock Out Error
Burner shutdown and manual reset needed after repair
EA
No ionization signal detected in the burner
Characteristic: Gas Valve + Electrodes
Permanent open
circuit due to over
temperature
Thermal fuse damaged
(melts at 114ºC)
Measure continuity:
R = ∞?
Check origin for high
temperature occurrence
Replace sensor (see
spare part list)
Yes
Inspect main heat
exchanger
– fins
obstructed?
Yes
Remove part and
clean external fins
Evidences of leakages
through sealing’s or HE
overheat?
End
Correct problem by
inspecting and/or
replacing gaskets /
sealings in Heat Cell
No
Yes
Heat Cell includes heat
exchanger sealing with
burner / flue collector
Problem solved?
Yes
No
Excessive burner
power
Check CO2
emissions and reduce
power in L1 / A1 to
correct ΔP1