Fault in the air flow NTC sensor
Component Characteristic: NTC temperature sensor (220 kΩ)
Lock Out Error
Burner shutdown
The Air NTC sensor is
interrupted or in short
circuit
Assure NTC cable harness is connected
in control unit
Unplug the NTC connection and measure
the NTC electrical resistance [R] (Ω)
[R] > 1300 kΩ or < 8.2 kΩ
[R] = ∞ Ω
NTC values out of
range
NTC interrupted
Change wiring
Plug connection wire
and turn ON unit
Problem solved?
End
Change wiring
Problem solved?
Replace control unit
See spare part list
See spare part list
Refer to table with
values in Service
Manual
Yes
No
No
Yes
No
No
Yes
Yes