Greentherm 9800 SEO 160/199 | SECO 199
36 | Troubleshooting
10.12 Factory default settings
Restore factory values for P1 Max. Power
▶ Access to menu
P1 Max. Power
.
▶ Press symbols
or
to select
Reset Parameters
.
▶ Press the symbol
.
The display blinks to confirm change.
▶ Press the symbol
.
The factory default values for
P1
are restored.
Restore factory values for P2 Max. Power
▶ Access to menu
P2 Min. Power
.
▶ Press symbols
or
to select
Reset Parameters
.
▶ Press the symbol
.
The display blinks to confirm change.
▶ Press the symbol
.
The factory default values for
P2
are restored.
10.13 Converting Gas Type
▶ Turn Off the appliance.
▶ Remove the front cover from the appliance (section 3.3.2).
▶ Remove the four screws that retain the cover plate to the
gas manifold, see fig. 31 (plate in grey color).
Fig. 31
Gas manifold
▶ Remove metal plate and seal.
▶ The 3 restrictor plates should be pre-assembled onto their
tray, but if loose in box, follow installation instruction, as
shown in fig. 32 [1].
▶ Insert the LP conversion plate in the appropriate location
shown in Fig. 32 [2].
CO
2
range (%)
Max. CO level
(measured)
Greentherm 9800 SE/SEC O
199 000 BTU
Nat. Gas
max. input
P1
8.5 % - 8.9 %
< 250 ppm
min. input
P2
2.3 % - 2.5 %
< 30 ppm
LP Gas
max. input
P1
9.8 % - 10.2 %
< 250 ppm
min. input
P2
2.8 % - 3.0 %
< 30 ppm
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact
CO and CO
2
values. Changes in these inputs can result in
different CO and CO
2
values on the same appliance.
Table 17 CO
2
& CO target numbers
CO
2
range (%)
Max. CO level
(measured)
Greentherm 9800 SE O
160 000 BTU
Nat. Gas
max. input
P1
8.6 % - 9.0 %
< 250 ppm
min. input
P2
3.3 % - 3.5 %
< 30 ppm
LP Gas
max. input
P1
9.7 % - 10.1 %
< 250 ppm
min. input
P2
3.6 % - 3.8 %
< 30 ppm
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact
CO and CO
2
values. Changes in these inputs can result in
different CO and CO
2
values on the same appliance.
Table 18 CO
2
& CO target numbers
DANGER:
Fatal accidents!
Before any service or testing in the
appliance,
▶ Turn off the appliance.
▶ Disconnect the power supply cord.
▶ Shut off the gas supply.
The gas type conversion must only be carried
out by a qualified contractor.
CAUTION:
▶ All three flow restrictors and seal must
be assembled according to the Fig. 32,
to assure correct appliance
performance.