6 720 817 281 (2017/05)
Greentherm 9800 SEO 160/199 | SECO 199
Troubleshooting | 35
▶ Record the
L1
gas adjustment value in table 16, when the
display starts blinking (as sign of confirmation).
▶ Press
button to finish the L1 gas adjust (U1).
▶ Press
or
until
P1
appears.
▶ Press the button
.
Display with indication "E".
▶ Press the button
until the display shows "
A1
".
▶ Press .
The appliance is now in the position for adjustment of the
maximum air flow.
▶ Press the buttons
or
until the CO
2
analyzer
shows the value indicated in tab. 17.
▶ Press the button
for 3 seconds.
The value flashes as a sign of confirmation.
▶ Press the button
to come out of this function.
Display with indication "A1".
▶ Close the hot water tap.
▶ Press
until the display shows "E".
▶ Press the button
.
Display with indication P1.
The adjustment of the maximum gas flow is finalized.
10.11.3Adjusting the minimum flow (Parameter P2)
▶ Press
until the display shows "P2".
Appliance will ramp down to low fire and the water flow
should decrease. Wait a few minutes until stabilize.
▶ Press
or
until
U2
appears.
▶ Press the button
.
The appliance will start the auto adjustment of the
minimum gas flow.
▶ Record the
L2
gas adjustment value in table 16, when the
display starts blinking (as sign of confirmation).
▶ Press
button to finnish the L2 gas adjust (U2).
▶ Press
or
until
P2
appears.
▶ Press the button
.
Display with indication "E".
▶ Press the button
until the display shows "
A2
".
▶ Press .
The appliance is now in the position for adjustment of the
maximum air flow.
▶ Press the buttons
or
until the CO
2
analyzer
shows the value indicated in tab. 17.
▶ Press the button
for 3 seconds.
The value flashes as a sign of confirmation.
▶ Press the button
to come out of this function.
Display with indication "A2".
▶ Close the hot water tap.
▶ Press
until the display shows "E".
▶ Press the button
.
Display with indication P2.
The adjustment of the maximum gas flow is finalized.
▶ Press simultaneously buttons
,
and
for 3
seconds.
Display with indication of temperature selected.
▶ Remove CO
2
analyzer probe from the appliance.
The auto adjust process takes several
minutes.
▶ Do not interfere with the appliance
during the auto adjustment process.
After adjusting parameter
P1
and to avoid
damaging the CO
2
analyzer remove and
allow the unit to operate in P2 mode for 1 or
2 minutes before measuring and adjusting
parameter
P2
.
The auto adjust process takes several
minutes.
▶ Do not interfere with the appliance
during the auto adjustment process.
Readings Gas parameter
Air Adjustment
Max.
Power
L1 value:_____
A1 value:_____ CO
2
value:_____
Min.
Power
L2 value:_____
A2 value:_____ CO
2
value:_____
Table 16