14
en | Structure and function
Radio gateway
2019.10 | 2.0 | F.01U.373.488
Operation Manual
Bosch Sicherheitssysteme GmbH
Indication
Meaning
Graphic
H3
H4
H3 or H3
and H4
flash yellow
twice every
second
Hardware trouble
The radio module has failed. There is
no connection to the radio devices.
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
H3
H3 flashes
yellow every
second
Battery trouble (critical or missing)
Battery notification (low)
The battery pack needs to be
replaced.
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
H3
H3 flashes
yellow every
two
seconds
Configuration trouble
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
H4
H4 flashes
yellow every
two
seconds
The radio cell is not yet ready for
operation.
Not all the radio devices are being
monitored yet, or not all of them
have been read in by the radio
gateway yet.
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
3.3
Power supply
Power supply via the AUX supply voltage
In normal operation the gateway is powered via the LSN AUX supply voltage. Auxiliary power
supply from the battery controller module (BCM-0000-B) is also possible.
Power supply from battery pack BAT3.6-10
When the battery pack is supplying power, the radio network
remains active even if the auxiliary power supply is switched off.
–
For commissioning the radio cell for the first time
–
If the power supply via the LSN AUX line is interrupted
–
If the LSN AUX line is temporarily switched off
When the battery is full, the operating life is around one week if no power is supplied via the
LSN AUX line.
3.4
Accessories
3.4.1
Battery pack BAT3.6-10