Radio gateway
Maintenance / troubleshooting | en
37
Bosch Sicherheitssysteme GmbH
Operation Manual
2019.10 | 2.0 | F.01U.373.488
S2
S1
H2
H2
H3
H4
Figure
7.4: Radio gateway FWI-270
H2
LED (yellow) for maintenance mode (MC-
State)
S1
Button for maintenance mode
H3
LED (yellow) for trouble indication (Fault/
Bat)
S2
Reset button
H4
LED (yellow) for radio network (Network)
You have the new radio device and its battery pack to hand.
You have a device location plan showing the locations of the radio devices in the radio cell.
It is possible to access the gateway and the radio devices.
Consider the corresponding panel controller documentation.
1.
Set the radio gateway to maintenance mode.
2.
Press and hold button
(S1) for at least 2
seconds until LED
(H2) flashes.
3.
The radio gateway and its radio cell are in maintenance mode.
LED
(H2) flashes at 1-second intervals.
4.
Remove the adhesive label from the radio device and use it to mark the installation
location on the device location plan.
5.
Connect the power supply for the radio device.
The internal alarm indicator of the radio device flashes.
If it flashes red, this indicates the factory settings.
If it flashes green, this indicates that the radio device has already been logged on to a
radio gateway and needs to be set to the factory settings.
6.
To set a radio device to the factory settings, press the 'new' button on the radio device
until the internal alarm indicator flashes red.
The radio device is set to the factory settings.
7.
Mount the radio device in the appropriate base (FDOOT271-O) or in the appropriate
housing (FDMH-273-R) or back box (FDM275-O).