38
en | Maintenance / troubleshooting
Radio gateway
2019.10 | 2.0 | F.01U.373.488
Operation Manual
Bosch Sicherheitssysteme GmbH
The search for the radio network starts. During the search, the internal alarm indicator
briefly flashes green twice, at an interval of 2 seconds.
Once the radio device has successfully been logged on to the radio gateway, the network
search stops and the internal alarm indicator goes out.
8.
If the logon process has not been successful after a long period of time has passed,
briefly remove the radio device from the base/housing and then re-insert it.
The search for the radio network starts again.
9.
Finish the process of logging the radio devices on to the radio gateway.
10. Check that the process of logging on to the radio gateway is complete.
Wait until the LED
(H4) on the radio gateway goes out.
1.
Check that the number of logged-on radio devices in the radio cell is complete.
2.
Check the internal alarm indicator for the new radio device. It must not flash.
The radio cell is complete and the radio devices are logged on.
3.
Switch the radio gateway to normal operation.
4.
Press and hold button
(S1) for at least 2 seconds.
LED indicator (H2) goes out.
The radio gateway is in normal operation.
5.
Close the radio gateway housing.
6.
Activate the LSN line on the panel controller and read in the new radio device in
accordance with the fire control panel documentation.
7.
Make a note of the change in your documents.
P
The new radio device has now been added.
Refer to
–
Replacing the battery pack on the radio gateway, page 44
7.4.2
Removing radio devices temporarily
An individual radio device may be removed temporarily, for
example, if renovation work is
being carried out.
WARNING
Risk of injury due to undetected fire
When parts of the system are switched off, they are not monitored
and no fire alarm signals are issued for them.
Keep the amount of time during which parts are switched off to a
minimum.
Put the intended safety measures in place.
NOTICE
Do not remove multiple radio devices at the same time
This may cause other radio devices to lose their connection to the
radio gateway and be displayed as missing devices.
When the devices are switched back on, faults may be reported at
the station.
Proceed as follows to remove a radio device temporarily: