6 720 643 256 (2010/05)
70
|
Menu settings INSTALLER SETTINGS (for installers only)
US/CA
•
Base line
: Use this menu option to set the
base point of the heating curve according to
the traditional base point/end point method
Heating circuit 1
and/or
Heating circuit 2
.
•
Design Temp
: Use this menu option to set the
base point of the heating curve according to
the traditional base point/end point method
Heating circuit 1
and/or
Heating circuit 2
.
•
Design supply temp.
: Use this menu option to
adapt the supply temperature setting to the
heating type for the
Heating circuit 1
and/or
Heating circuit 2
.
–
For
Radiant Floor
e.g. 114 °F (45 °C)
supply temperature setting.
–
For
Radiators
e.g. 168 °F (75 °C) supply
temperature setting.
–
For
Baseboard
e.g. 176 °F (80 °C) supply
temperature setting.
•
Maximum heating supply temperature
: Use
this menu option to adapt the supply
temperature setting to the heating type for the
Heating circuit 1
and/or
Heating circuit 2
.
–
For
Radiant Floor
e.g. 132 °F (55 °C)
maximum supply temperature.
–
For
Radiators
e.g. 176 °F (80 °C)
maximum supply temperature.
–
For
Baseboard
e.g. 176 °F (80 °C)
maximum supply temperature.
•
Room influence
: This menu option only
appears if the controls are wall-mounted.
Use this menu option to set the room
temperature influence on the heating curve
for the
Heating circuit 1
and/or
Heating
circuit 2
.
–
0%
: No room temperature influence
–
100%
: Maximum room temperature
influence
•
Room influence enabled for modes
: Use this
menu option to select the operating modes
where the room temperature influence is to
be active for
Heating circuit 1
and/or
Heating
circuit 2
.
–
Eco/Frost
: Room temperature influence is
only active in these operating modes.
–
Comfort/Eco/Frost
: Room temperature
influence is always active.
•
Room temperature offset
: Use this menu
option to set the permanent increase in
required room temperature for the
Heating
circuit 1
and/or
Heating circuit 2
, e.g. to
correct system-related variations.
Factory setting of parameters for
heating curve
Baseline/Design
temp
Radiant Floor
Radiators
Baseboard
Heating surface exponent (fixed
value), curvature of heating curve
–
1.1
1.3
1.4
Minimum outdoor temperature
–
6 °F ( – 15 °C)
6 °F ( – 15 °C) 6 °F ( – 15 °C)
Base line
78 °F (25 °C)
– –
–
Design Temp
168 °F (75 °C)
– –
–
Design supply temp.
–
114 °F (45 °C)
168 °F (75 °C) 176 °F (80 °C)
Maximum heating supply
temperature
176 °F (80 °C)
132 °F (55 °C)
176 °F (80 °C) 176 °F (80 °C)
Room temperature offset
0 °F (0.0 °C)
0 °F (0.0 °C)
0 °F (0.0 °C)
0 °F (0.0 °C)
Heating OFF at outdoor
temperature
68 °F (20 °C)
68 °F (20 °C)
68 °F (20 °C)
68 °F (20 °C)
Tab. 7