Bosch Security Systems | 10/03 | 43488E
EN |
48
D9412G/D7412G
| Operation & Installation Guide | 8.0 Off-Board Points
8.5
Testing Off-Board Points
Use the Service Walk Test to test off-board points. See
the D9412G/D7412G/D7212G Installation and
Troubleshooting Quick Reference Guide for instructions. Test
to ensure all off-board points operate properly.
Walk Test Does Not Show Extra Point:
Only the
Service Walk Test shows extra points. If the point
assignment switches on a POPIT or OctoPOPIT are set
incorrectly, it can create both missing and extra points.
If the same point number is assigned to two or more
POPITs or OctoPOPITs, none of the points with that
number test correctly.
Figure 21: D81282D OctoPOPIT Sensor Loops
COM IN OUT+12V P1 COM P2
P3 COM P4
P5 COM P6
P7 COM P8
1
4
3
2
5
1 - D8128D OctoPOPIT
2 - To control panel
3 - To additional OctoPOPIT sensor loops
4 - OctoPOPIT sensor loops
5 - 1 k
Ω
EOL resistor (D105BL)
Содержание D7412G
Страница 1: ...D9412G D7412G EN Operation Installation Guide Control Panels ...
Страница 2: ...Bosch Security Systems 10 03 43488E EN 2 D9412G D7412G Operation Installation Guide ...
Страница 10: ...Bosch Security Systems 10 03 43488E EN 10 D9412G D7412G Operation Installation Guide 1 0 Introduction Notes ...
Страница 36: ...Bosch Security Systems 10 03 43488E EN 36 D9412G D7412G Operation Installation Guide 7 0 On Board Points Notes ...
Страница 56: ...Bosch Security Systems 10 03 43488E EN 56 D9412G D7412G Operation Installation Guide Notes 10 0 Arming Devices ...
Страница 60: ...Bosch Security Systems 10 03 43488E EN 60 D9412G D7412G Operation Installation Guide Notes 11 0 SDI Devices ...