3.4

Installing the Assembly

1.

Place the assembly over the inside back of the
enclosure, aligning the large rectangular openings of
the mounting skirt with the mounting hooks of the
enclosure. Slide the assembly down so it hangs on
the hooks. See Figure 2.

2. Remove the tape from the #6 x 1/4-in. screw in the

mounting tab on the assembly. The screw passes
through the mounting tab and into the skirt
mounting hole in the enclosure. Tighten the screw
to secure the assembly in the enclosure.

3. Connect earth ground to the panel before making

any other connections. See Section 3.5 Connecting
Earth Ground.

3.5

Connecting Earth Ground

3.5.1

Terminal 

To help prevent damage from electrostatic charges or
other transient electrical surges, connect the system to
earth ground at Terminal 10 before making other
connections. A grounding rod or cold water pipe are
recommended earth ground references.

Do not use 

telephone or electrical ground

for the earth ground connection. Use
1.8 mm (14 AWG) to 1.5 mm (16 AWG)
wire when making the connection.

Do not connect

 other panel terminals to

earth ground.

3.5.2

Ground Fault Detect Enable

Ground fault detect capability is available
only on firmware versions 6.10 or higher.

Ground Fault is defined as “a circuit impedance to Earth
Ground of approximately 95 kilohms or less.” The
panel detects a ground fault on Terminals 1 to 9 and
Terminals 11 to 32 if the Ground Fault Detect Enable
jumper (S4) (see Figure 3) is locked (closed) and a non-
zero value is entered in Area 5 Silent Alarm Relay. See
the D9412G/D7412G Program Entry Guide. When the
jumper is in the unlocked (open) position, the panel does
not detect ground fault conditions. If a ground fault
condition occurs, the command centers display 

SERVC

GND FAULT

 and the panel transmits a Trouble Report

Ground Fault Area

 

(Modem IIIa

 format only). For the

panel to detect a ground fault condition, the panel must
see the ground fault for a minimum of 30 consecutive
seconds. When the panel recognizes the ground fault
condition is corrected, a Restoral Report is sent. For the
restoral condition to be met, the ground fault must be
corrected for between 5 and 45 consecutive seconds.

3.0 Installation

The 9000 Series Control Panels log and
print a Ground Fault event as a Trouble
Point 256.

3.5.3

Locking the Reset Pin

Locking the reset pin disables the panel (see Figure 4).
The system ignores the command centers and points
while disabled. 

CALL FOR SERVICE

 appears in

command center displays while the pin is locked down.

On-board relays (Terminals 6, 7, and 8) and off-board
relays deactivate when the panel is reset. There is power
at Terminal 8 when the relay is deactivated. Activation
interrupts power at that terminal. The relays remain
deactivated while the reset pin is locked in the disable
position.

Releasing the reset pin from the closed position resets
the panel. The panel resets all its timers, counters,
indexes, and buffers. Any points that restore after a reset
is performed do not generate Restoral Reports.

If the reset pin is placed in the disable position when all
areas are armed, there must be an entry in the Answer
Armed program item. See RAM Parameters in the
D9412G/D7412G Program Entry Guide).

Locking the pin in the disable position allows powering
up of the panel and charging the battery while the
detection devices and command centers are being
installed.

Figure 3: Ground Fault Detect

GROUND FAULT DETECT

Enabled
Disabled

PHONE
LED

RED

ON WHEN
COMMUNICATING
OFF WHEN IDLE

LOOP START

PHONE MONITOR SELECT

GROUND START

Requires

Relay Model

D136 in Ground

Start Socket

GND START

1

3

2

1 - With S4 closed, panel detects ground faults.

2 - With S4 open, panel does not detect ground faults.

3 - S4, Ground fault detect enable.

Содержание D7412G

Страница 1: ...D9412G D7412G EN Operation Installation Guide Control Panels ...

Страница 2: ...Bosch Security Systems 10 03 43488E EN 2 D9412G D7412G Operation Installation Guide ...

Страница 3: ...tection Devices 19 3 6 3 Install Modules and Relays 19 3 6 4 Make the Telephone Connections 19 3 6 5 Connect the On board Points and Command Centers 19 3 6 6 Power Up 20 3 7 Programming the Panel 20 3 8 Install the Point Chart Label 20 3 9 Testing the System 20 4 0 Power Supply 22 4 1 Primary Power Terminals 21 4 1 1 Primary AC Power Circuit 21 4 1 2 Installing the Transformer 21 4 2 Secondary Pow...

Страница 4: ...s 53 10 1 Description 53 10 2 Command Center Terminals 53 10 2 1 Assigning the command center an address 53 10 2 2 Installation 53 10 3 D268 D269 Independent Zone Control D279A Independent Zone Control 55 10 4 Keyswitch 55 10 4 1 Description 55 10 4 2 Programming 55 10 4 3 Installation 55 10 4 4 Keyswitch Operation 55 11 0 SDI Devices 57 11 1 Description 57 11 2 Installation 57 11 3 D9131A Paralle...

Страница 5: ... Centers 54 Figure 27 Keyswitch Wiring 55 Figure 28 D9133 Jumper Settings 58 Figure 29 D9133TTL E Jumper Settings 59 Figure 30 Reset Pin 61 Figure 31 Programmer and Accessory Connections 61 Figure 32 D9412G Faceplate 63 Figure 33 D7412G Faceplate 64 Figure 34 D9412G System Wiring Diagram 1 of 3 65 Figure 35 D9412G System Wiring Diagram 2 of 3 66 Figure 36 D9412G System Wiring Diagram 3 of 3 67 Fig...

Страница 6: ...Bosch Security Systems 10 03 43488E EN 6 D9412G D7412G Operation Installation Guide Notes Table of Contents ...

Страница 7: ...ich they comply 2 Overview Summary of the D9412G D7412G Control Panels including operational specifications standards and new features 3 Installation Instructions for connecting the power terminals plus the status and battery LEDs 4 Power Supply Information on the primary and secondary modules Instructions on connecting and programming them 5 Power Outputs Information on the power outputs and inst...

Страница 8: ...s for records the user will create Courier Text Indicates what may appear on the D5200 Programmer display command center keypad or internal printer CAPITALIZED TEXT Indicates a specific key that should be pressed Table 3 Text Type Styles Table 2 Related Documentation Name of Documentation Part Number D1255 Installation Instructions 74 06819 000 D1256 D1257 Installation Instructions 74 06925 000 D1...

Страница 9: ...d five To be certain of the number of devices that may be connected to the line as determined by the RENs contact the telephone company to determine the maximum REN for the calling area 1 0 Introduction If trouble is experienced with the D9412G D7412G Control Panels please contact Bosch Security Systems Customer Service for repair and or warranty information If the trouble is causing harm to the t...

Страница 10: ...Bosch Security Systems 10 03 43488E EN 10 D9412G D7412G Operation Installation Guide 1 0 Introduction Notes ...

Страница 11: ...keyswitches to arm the panel by area Each panel can have up to eight areas Each area can have its own account number or areas can be grouped together with a common account number Points of protection are assigned to areas Control Panel On Board Points 1 to 8 D9131A Module connects to a parallel printer to print the event log D928 Module allows the panel to monitor two phonelines D8125 or D8125MUX ...

Страница 12: ...ns must be limited to 1 4 A 1400 mA provided by the primary power supply rectified AC If current draw for the system exceeds 1 4 A remove connected devices until the current draw falls below 1 4 A Then connect the removed devices to a D8132 Battery Charger Module or to an external power supply see Figure 26 Minimum Operating Voltage 10 2 VDC SDI Bus SDI Bus A SDI Bus B 9 VDC 4572 m 15000 ft maximu...

Страница 13: ...l Title Model Title D122 Dual Battery Harness D1257 Fire Annunciator D125B Powered Loop Interface Module D1260 Alpha V Command Center D127 Reversing Relay D1640 16 5 VAC 40 VA Transformer D129 Dual Class A Initiation Circuit Module D5500 Remote Account Manager IV D130 Relay Module D8004 Transformer Enclosure D136 Plug In Relay D8124A D8122 Derived Channel STU D161 Phone Cord D8125 POPEX Module D16...

Страница 14: ...y separate fire and burglary outputs and multiple opening and closing windows Area type can be used to create area interdependencies 2 4 3 Communicator The control panel uses a built in digital communicator to send reports to the receiver The panel transmits reports in either the Modem IIIa2 or BFSK format The D6500 receiver s MPU and line cards must have software revision 8 00 or greater installe...

Страница 15: ... showing the previous arming state All events and their modifiers can be stored even if the panel does not send a report for them The log can be viewed at a command center printed locally using the D9131A Parallel Printer Interface Module and a parallel printer or uploaded to the Remote Account Manager RAM IV See the appendix in the command center s User s Guide for a listing of log events and eve...

Страница 16: ...G D7412G Program Record Sheet 2 0 Overview 2 4 14 Listings and Approvals The D9412G D7412G Literature Pack includes the D9412G D7412G Approved Applications Compliance Guide Refer to this guide for additional guidelines on installing the control panels in Underwriters Laboratories UL and fire specific applications see Table 8 Fire UL UL lists the D9412G D7412G Control Panels as Signal System Contro...

Страница 17: ...2 Enclosure Options Mount the control panel assembly in any of the Bosch Security Systems enclosures listed D8103 Universal Enclosure tan D8109 Fire Enclosure red D8108A Attack Resistant Enclosure tan Refer to the D9412G D7412G Approved Applications Compliance Guide to determine if the application requires a specific enclosure 3 3 Beginning the Installation 1 Mount the enclosure in the desired loc...

Страница 18: ...enters display SERVC GND FAULT and the panel transmits a Trouble Report Ground Fault Area Modem IIIa2 format only For the panel to detect a ground fault condition the panel must see the ground fault for a minimum of 30 consecutive seconds When the panel recognizes the ground fault condition is corrected a Restoral Report is sent For the restoral condition to be met the ground fault must be correct...

Страница 19: ... to detection devices Section 10 0 Arming Devices contains instructions for wiring the command centers Instructions for wiring the off board point POPIT sensor loops are found in the instructions packaged with the POPIT modules 3 6 3 Install Modules and Relays 1 Power down the unit by unplugging the transformer and disconnecting the battery Always power down the unit when installing modules or rel...

Страница 20: ...l the point chart label for fire or combined fire burglary systems using verification points Use the D9412G D7412G Program Record Sheet to gather the information needed to complete the point chart Install the label on the enclosure door seen in Figure 2 Avoid smearing the entries on the chart by using the label s peel off backing to press the label in place 3 0 Installation 3 9 Testing the System ...

Страница 21: ...h the screw provided D8004 Transformer Enclosure Required for Fire Systems Use the D8004 Transformer Enclosure for the D1640 Transformer in fire and combined fire burglary applications Check with the Authority Having Jurisdiction AHJ on mounting transformers on specific circuits 4 0 Power Supply 4 2 Secondary Power Terminals 4 2 1 Secondary DC Power A 12 V 7 Ah up to 14 Ah sealed lead acid recharg...

Страница 22: ...is determined by the number of available outlets on the same circuit Refer to the Standby Battery and Current Rating Chart in the D9412G D7412G Approved Applications Compliance Guide for battery standby time calculations In applications where the supervision of two batteries is required by the AHJ use a D113 Battery Supervision Module 4 Option wires 5 Output or zone wires 6 Standby battery EARTH G...

Страница 23: ... AC power loss the battery supplies all power to the security system If the battery voltage falls below 10 2 V during an AC power loss a load shed relay isolates the battery from the panel and disables the panel Load shed protects the battery from being damaged by deep discharge When AC power restores the load shed relay resets and battery voltage is again available Overcharge Load Shed With AC Pr...

Страница 24: ... sirens or bells drawing more than 1 4 A If the LED lights regularly for extended periods or does not go out check the current draw for devices connected to the power outputs Refer to Section 5 0 Power Outputs for instructions Yellow Flash once per minute System is checking the battery Yellow and Red Flash once per minute Indicates when the current draw for devices connected to the power outputs e...

Страница 25: ...ate over a range of 10 2 VDC to 13 9 VDC Power Restricted for Fire and Combined Fire Burglary Systems Use the Fire System Power Formula to calculate the current available for fire and combined fire burglary systems see section 5 4 Programmable Power Outputs Terminals 5 4 Programmable Power Outputs Terminals 5 4 1 Programming The power outputs at Terminals 6 7 and 8 are programmed as Relays A B and...

Страница 26: ...3 8 24 and 32 and the accessory connector This is the total current required for the Normal Standby Condition NSC 2 The current available for NSC is 1 4 A Subtract the NSC current required calculated in Step 1 from the NSC current available 1 4 A The difference is the alarm current available for Terminals 6 and 7 In formula format 1 4 A NSC current required Step 1 Alarm current available Refer to ...

Страница 27: ...ore the in house phone system to support line seizure see Figure 8 Install the jack on the street side of the phone switch wired ahead of any PBX equipment Line seizure provides for a temporary interruption of normal phone usage while the communicator transmits data After installation confirm the panel seizes the line acquires dial tone reports correctly to the receiver and releases the phone line...

Страница 28: ...or the phone line Bad Line May Test OK The telephone line monitor uses voltage levels to test the status of the phone line In some instances a given telephone line may be out of service without affecting the voltage on the line The phone line monitor cannot recognize this trouble condition 6 0 Telephone Connections 6 9 Called Party Disconnect Telephone companies provide called party disconnect to ...

Страница 29: ...one lines The panel monitors both lines If a signal is generated and the panel senses that a line is bad then it attempts to use the other phone line to send the message If trouble is detected the panel keeps the faulty phone line in memory Set the Ring Count Above 2 on Answering Machines The panel s RPS line monitor feature may not operate correctly if an answering machine with a ring count of le...

Страница 30: ...ower and the black lead provides surge protection for the two incoming phone lines The black lead is also the ground reference for the AC PowerLED 1 Connect the green lead from the D928 to Terminal 1 2 Connect the black lead from the D928 to Terminal 9 Phone Connections 1 Plug one end of the ribbon cable provided with the D928 into J4 on the D928 Plug the other end into the accessory connector on ...

Страница 31: ... AC power at Terminals 1 and 2 on the panel Phone Line Fail LEDs Two yellow Phone Line Status LEDs one for the primary phone line one for the secondary phone line light when phone line voltage drops below 3 0 VDC The panel monitors the faulty phone line for the programmed interval before indicating a trouble condition See Section 6 8 Phone Line Monitor for a description of phone line monitor opera...

Страница 32: ...Bosch Security Systems 10 03 43488E EN 32 D9412G D7412G Operation Installation Guide 6 0 Telephone Connections Notes ...

Страница 33: ...ally closed and or in parallel normally open to any of these loops 7 0 On Board Points The number of normally open and or normally closed detection devices each sensor loop can supervise is limited only by the resistance on the loop The total resistance for the wire length and contacts minus the end of line EOL resistor must not exceed 100 Ω 7 3 Point Parameters The condition of on board Points 1 ...

Страница 34: ...evices may go into alarm and reset without exceeding the point response time Bosch Security Systems recommends a debounce count of 2 for all points except for Interior Follower points which should be programmed as a 3 In addition door points connected to a D9210B Access Control Interface Module should be programmed with a debounce of 4 7 0 On Board Points 7 5 Wiring Information for Installations U...

Страница 35: ... Can Be a Fire Hazard Battery Replace Every 3 to 5 years with Model D126 12 V 7 Amp Hr Lead Acid Battery This equipment should be installed in accordance with the NFPA 70 National Electrical Code and NFPA 72 National Fire Alarm Code for Local Central Station Remote Station and Household Fire Warning Systems and under the limits of the Local Authority Having Jurisdiction National Fire Protection As...

Страница 36: ...Bosch Security Systems 10 03 43488E EN 36 D9412G D7412G Operation Installation Guide 7 0 On Board Points Notes ...

Страница 37: ... open or shorted state the command center neither annunciates nor displays a trouble condition No Extra Point event is generated 8 0 Off Board Points the system is presently in a Service Walk Test and the point input goes from an electrically normal state to an open or shorted state the command center neither annunciates nor displays a trouble condition However an Extra Point event is logged and p...

Страница 38: ...nting To install the D8125 in the enclosure with the panel 1 Align the D8125 POPEX Module with any of the four mounting locations in the enclosure see Figure 2 2 Using the screws provided with the module secure it in the enclosure 8 3 2 Wiring the D8125 to the Control Panel To wire one or two D8125 Modules to the panel see Figure 14 and Figure 15 8 0 Off Board Points Power Down First Power down th...

Страница 39: ...urity Systems 10 03 43488E 8 0 Off Board Points Figure 14 Connecting the D8125 POPEX to the D9412G Panel 1 D8125 POPEX Module 2 Switch block 3 D9127 Sensor Loop 4 33 k Ω EOL resistor 5 Zone expansion loop 6 Up to 119 POPITs 7 On board points 8 Expansion zones ...

Страница 40: ... D7412G Operation Installation Guide 8 0 Off Board Points Figure 15 Connecting the D8125 POPEX to the D7412G Panel 1 D8125 POPEX Module 2 Switch block 3 D9127 Sensor Loop 4 33 k Ω EOL resistor 5 Zone expansion loop 6 Up to 67 POPITs 7 Expansion zones ...

Страница 41: ...nect the negative data terminal from the first POPIT on the data expansion loop to one of the D8125 s negative terminals 8 0 Off Board Points 8 3 5 POPIT Sensor Loops The number of normally open and or normally closed detection devices each sensor loop can supervise is limited only by the resistance on the loop Resistance on each sensor loop must be less than 100 Ω not including the EOL resistor C...

Страница 42: ...s are supplied with the D8125 POPEX Module Use the sheet marked Bank1 for Points 9 to 127 Use the sheet marked Bank2 for Points 129 to 247 Each label has two parts Place the smaller part with only the point number on the chip Place the larger part with the switch settings on the base of the POPIT Set the switches and cover the POPIT Do not program two POPITs for the same point number After program...

Страница 43: ...72 The D8128D is also suitable for fire supervisory applications such as indicating circuit supervision using the D192C D192G Bell Circuit Supervision Module sprinkler supervision and valve tamper protection Requirements for Fire Initiation Applications Non powered fire initiating devices such as pull stations heat detectors and UL Listed four wire smoke detectors can be connected directly to the ...

Страница 44: ...ed to Points 17 through 24 Moving the DIP switch for Point 4 to the OFF position would effectively disable Point 20 allowing normal operation of the D9210B and the OctoPOPIT Terminate each OctoPOPIT sensor loop with a 1 kΩ EOL resistor Attach a resistor even if you don t enable the loop 8 4 5 Mounting The D8128D OctoPOPIT Module can be installed in the enclosure with the panel using standard four ...

Страница 45: ...r to Table 14 Figure 18 and Figure 19 when connecting the D8128D to the control panel via the OctoPOPIT s terminal strip GRN Reset Pin Disable All Except Battery Charging And Programming PERIPHERAL DEVICE CONNECTIONS RED POWER YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 N F P A Style 3 5 Signaling Line Circuits 32 31 30 29 28 27 PROG CONN Point 8 GND FAULT Detect E N A B...

Страница 46: ...C AUX PO 1 2 3 4 5 6 7 8 9 10 CLASS 2 TRANS 16 5 VAC 40 VAC Model D1640 Internally Fuse Requires Unsw Do Not Share Low Battery RED PR AL Re GROUND FAUL Pin Battery amming E CONNECTIONS POWER DATA BUS A DATA BUS B COMMON ZONEX OUT 1 ZONEX IN 1 32 31 30 29 28 27 PROG CONN 1 2 1 2 1 2 1 2 Note Refer to Address Switches in Section 8 4 7 Setting the OctoPOPIT Switches for information on how these switc...

Страница 47: ...oPOPIT detects open short closed normal and grounded circuit conditions on its sensor loops and transmits the conditions to the panel Each sensor loop is assigned a point number and transmits to the panel separately Use twisted pair wire for the OctoPOPIT sensor loops to avoid EMI problems Run wires away from the premises telephone and AC wiring If you suspect a noisy environment use shielded cabl...

Страница 48: ...Does Not Show Extra Point Only the Service Walk Test shows extra points If the point assignment switches on a POPIT or OctoPOPIT are set incorrectly it can create both missing and extra points If the same point number is assigned to two or more POPITs or OctoPOPITs none of the points with that number test correctly Figure 21 D81282D OctoPOPIT Sensor Loops COM IN OUT 12V P1 COM P2 P3 COM P4 P5 COM ...

Страница 49: ...re installing it in the enclosure See Section 9 1 1 Configuring the D8129 OctoRelay Install the OctoRelay in the enclosure with the panel see Figure 2 or in an adjacent enclosure that is no more than 1 5 m 5 ft from the panel Use 1 5 mm 16 AWG to 0 8 mm 22 AWG wire To install OctoRelays in the enclosure with the panel 1 Align the module with one of the mounting locations in the enclosure see Figur...

Страница 50: ...umbers 1 to 64 Connect OctoRelays in parallel 3 Power limited 4 Supervised Figure 22 D8129 Connections to the D9412G 1 5 2 GRN Reset Pin Disable All Except Battery Charging And Programming PERIPHERAL DEVICE CONNECTIONS RED POWER YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 N F P A Style 3 5 Signaling Line Circuits 32 31 30 29 28 27 PROG CONN Point 8 GND FAULT Detect E N A...

Страница 51: ... used in fire or combined fire burglary installations for primary indication devices 9 2 1 Relay Output Table 16 Number of D8128Ds Used with D8129s If the Number of D8128Ds Connected to a Single Zonex Bus Is Do Not Connect More Than this Number of D8129s 9 6 10 5 11 4 12 3 13 1 14 1 Each D811 relay output provides a Form C dry contact rated for 1 0 A at 12 VDC Normally open common and normally clo...

Страница 52: ...ONEX POWER 24 ZONEX COMMON 23 21 22 1 3 2 1 2 3 4 5 6 7 8 GND AUX DATA 1 2 3 4 5 6 7 8 GND AUX DATA 1 D811 for relay number 53 2 D811 for relay number 117 3 On board points Figure 25 D811 Module Wiring to the D7412G 5 GND AUX DATA EARTH GRO COMMON BATTERY N Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY A RELAY B RELAY C AUX PO 1 2 3 4 5 6 7 8 9 10 CLASS 2 TRANS 16 5 VAC 40 VAC Part...

Страница 53: ...n LED display command center appropriate for use as a single area command center with up to eight points The D1255 and D720 are also available in white D1255W and D720W or red D1255R and D720R versions See the command center s User s Guide for operational information 10 2 1 Assigning the Command Center an Address Switches on the command center assign an address 1 to 8 to the command center The add...

Страница 54: ...egulated power limited power supply for Fire Protective Signaling Units and Commercial Residential Burglar Units The D8132 is not UL Listed as a stand alone power supply 10 0 Arming Devices Control Panel and D8132 or other power supply must share COMMON Note that Figure 26 shows the common form the D8132 Module connected to both the command center s common and the common on the control panel Any s...

Страница 55: ...y switches connect the EOL resistor for the point at the keyswitch so the switch shorts the resistor when it operates An open on the circuit produces an alarm if the area is armed and a trouble if it is disarmed See Figure 27 10 4 4 Keyswitch Operation Maintained Contact If the point to which the keyswitch is connected is programmed for a maintained contact an open on the arming circuit arms the a...

Страница 56: ...Bosch Security Systems 10 03 43488E EN 56 D9412G D7412G Operation Installation Guide Notes 10 0 Arming Devices ...

Страница 57: ...the printer and the D9131A printer paper supply printer selected on line and printer power The panel sends an SDI Failure Report to the receiver if it fails to communicate with the printer interface and SERVC PRINTER displays at the command center The report to the receiver includes the address of the troubled D9131A to indicate which printer needs service If an SDI device is supervised and SDI A ...

Страница 58: ...le with the D9412G D7412G panels and is used for several different applications When using SDI Address 88 only connect one listed devices at a time 11 6 1 D9133DC Direct Connect Programming Module Use the D9133DC Direct Connect Programming Module to locally program the D9412G D7412G panels In addition the D9133DC allows diagnostic and history retrieval D9133DC is not UL Listed Connecting the D9133...

Страница 59: ...am Entry Guide The D9133TTL E can be installed up to 305 m 1000 ft from the panel using 18 AWG 1 2 mm wire 11 6 3 Address Settings Place a jumper over Pin 8 for the D9133TTL E SDI Address 88 to be used for RAM IV and or enhanced communications in a LAN WAN environment 11 6 4 Supervision Supervision of the D9133DC D9133TTL E and D9133TTL TR at SDI Address 88 is available through programming that en...

Страница 60: ...Bosch Security Systems 10 03 43488E EN 60 D9412G D7412G Operation Installation Guide Notes 11 0 SDI Devices ...

Страница 61: ... complete information on using the D5200 programmer To connect and disconnect the programmer 1 Lock the Reset Pin see Figure 30 2 Connect the D5200 Data Power cord into the programmer connector 3 Perform the desired programming function send or receive program 4 Disconnect the programmer 12 1 1 Programmer Access Reports When a program is sent to the panel the panel sends a Prog Access OK Report 10...

Страница 62: ...Bosch Security Systems 10 03 43488E EN 62 D9412G D7412G Operation Installation Guide Notes 12 0 Programmer Accessory Connections ...

Страница 63: ...tus LED yellow 2 Low Battery LED red 3 Color coded battery leads 4 Ground fault detect enable 5 Telephone cord connector 6 Phoneline monitor select jumper 7 Ground start relay Figure 32 D9412G Faceplate 8 Phone LED red 9 Point 8 ground fault detect enable disable 10 Operation monitor LED green 11 Accessory connector 12 Programming connector 13 Reset pin ...

Страница 64: ...yellow 2 Low Battery LED red 3 Color coded battery leads 4 Ground fault detect enable 5 Telephone cord connector 6 Phoneline monitor select jumper 7 Ground start relay Figure 33 D7412G Faceplate 8 Phone LED red 9 Point 8 ground fault detect enable disable 10 Operation monitor LED green 11 Accessory connector 12 Programming connector 13 Reset pin ...

Страница 65: ...ion and Household Fire Warning Systems and under the limits of the Local Authority Having Jurisdiction National Fire Protection Association Batterymarch Park Quincy MA 02269 Printed information describing proper installation operation testing maintenance evacuation planning and repair service is to be provided with this equipment D9412G Control Communicator is UL Listed For Central Station Local R...

Страница 66: ...for Local Central Station Remote Station and Household Fire Warning Systems and under the limits of the Local Authority Having Jurisdiction National Fire Protection Association Batterymarch Park Quincy MA 02269 Printed information describing proper installation operation testing maintenance evacuation planning and repair service is to be provided with this equipment D9412G Control Communicator is ...

Страница 67: ... National Fire Alarm Code for Local Central Station Remote Station and Household Fire Warning Systems and under the limits of the Local Authority Having Jurisdiction National Fire Protection Association Batterymarch Park Quincy MA 02269 Printed information describing proper installation operation testing maintenance evacuation planning and repair service is to be provided with this equipment D9412...

Страница 68: ...he types of initiating circuits the panel has been approved for are A M W SS VOLTAGE RANGES Open 3 7 5 0 VDC Normal 2 0 3 0 VDC Short 0 0 1 3 VDC GRN Reset Pin Disable All Except Battery Charging And Programming PERIPHERAL DEVICE CONNECTIONS RED POWER YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 N F P A Style 3 5 Signaling Line Circuits PROG CONN 46729G LOOP START GND STA...

Страница 69: ...ystem is Intended To Be Checked By A Qualified Technician At Least Every 3 Years The types of initiating circuits the panel has been approved for are A M W SS VOLTAGE RANGES Open 3 7 5 0 VDC Normal 2 0 3 0 VDC Short 0 0 1 3 VDC GRN Reset Pin Disable All Except Battery Charging And Programming PERIPHERAL DEVICE CONNECTIONS RED POWER YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX ...

Страница 70: ...n and Household Fire Alarm and Central Station Local Police Station Connect and Household Burglar Alarm System is Intended To Be Checked By A Qualified Technician At Least Every 3 Years The types of initiating circuits the panel has been approved for are A M W SS VOLTAGE RANGES Open 3 7 5 0 VDC Normal 2 0 3 0 VDC Short 0 0 1 3 VDC GRN Reset Pin Disable All Except Battery Charging And Programming P...

Страница 71: ...9 0 1 3 5 6 069 0 5 6 109 2 3 5 6 030 0 1 3 5 070 0 5 110 2 3 5 031 0 1 3 6 071 0 6 111 2 3 6 032 0 1 3 072 0 112 2 3 033 0 1 4 5 6 073 1 2 3 4 5 6 113 2 4 5 6 034 0 1 4 5 074 1 2 3 4 5 114 2 4 5 035 0 1 4 6 075 1 2 3 4 6 115 2 4 6 036 0 1 4 076 1 2 3 4 116 2 4 037 0 1 5 6 077 1 2 3 5 6 117 2 5 6 038 0 1 5 078 1 2 3 5 118 2 5 039 0 1 6 079 1 2 3 6 119 2 6 040 0 1 080 1 2 3 120 2 041 0 2 3 4 5 6 08...

Страница 72: ...3 4 5 6 146 0 1 3 4 5 186 0 4 5 226 2 3 4 5 147 0 1 3 4 6 187 0 4 6 227 2 3 4 6 148 0 1 3 4 188 0 4 228 2 3 4 149 0 1 3 5 6 189 0 5 6 229 2 3 5 6 150 0 1 3 5 190 0 5 230 2 3 5 151 0 1 3 6 191 0 6 231 2 3 6 152 0 1 3 192 0 232 2 3 153 0 1 4 5 6 193 1 2 3 4 5 6 233 2 4 5 6 154 0 1 4 5 194 1 2 3 4 5 234 2 4 5 155 0 1 4 6 195 1 2 3 4 6 235 2 4 6 156 0 1 4 196 1 2 3 4 236 2 4 157 0 1 5 6 197 1 2 3 5 6 ...

Страница 73: ...omponents Ordered Separately 16 Control Panel Assembly 15 D D1218 Battery 21 D125B 43 D129 43 D192C 43 D192G 43 D268 D269 Independent Zone Control 55 D279A Independent Zone Control 55 D5200 Programmer 15 20 D7412G Faceplates 64 Wiring Diagrams 68 69 70 D811 Arm Status Relay Module 51 D8125 POPEX Connecting to the D7412G 40 Connecting to the D9412G 39 Installing 38 D8125 POPIT Modules 38 D8127 POPI...

Страница 74: ... Phone Lines 19 27 Dialing Format 28 Dual Phone Line Switcher 29 Ground Start 29 Jacks 14 27 Phone Line Monitor 28 Rng Indicator 28 Seizure 14 27 Status LED 31 Point Address Charts ZONEX 1 71 ZONEX 2 72 Point Chart Label 20 Installing 20 Points 14 Off board 14 37 On board 14 19 33 Sensor Loops 33 Standard Features 14 POPEX 19 37 Wiring 38 POPITs 37 38 Testing 48 Wiring 19 38 Power AC Power Status ...

Страница 75: ...nals 21 Sensor Loops 33 Serial Interface Module 58 Service Walk Test 20 Specifications 12 Standard Features 14 System Overview 11 T Telephone Connections 19 27 Testing Off board Points 48 Service Walk 20 Testing the System 20 Tips Notes Cautions Warnings 8 Transformer 19 21 Transformer Enclosure 21 Type Styles 8 V Verification Reset Relay 26 W Warnings 8 Watchdog Feature 30 Wiring 19 Command Cente...

Страница 76: ...Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 USA www boschsecurity us Customer Service 800 289 0096 Technical Support 888 886 6189 2003 Bosch Security Systems 43488E ...

Отзывы: