Bosch Security Systems | 10/03 | 43488E
EN |
18
D9412G/D7412G
| Operation & Installation Guide |
3.4
Installing the Assembly
1.
Place the assembly over the inside back of the
enclosure, aligning the large rectangular openings of
the mounting skirt with the mounting hooks of the
enclosure. Slide the assembly down so it hangs on
the hooks. See Figure 2.
2. Remove the tape from the #6 x 1/4-in. screw in the
mounting tab on the assembly. The screw passes
through the mounting tab and into the skirt
mounting hole in the enclosure. Tighten the screw
to secure the assembly in the enclosure.
3. Connect earth ground to the panel before making
any other connections. See Section 3.5 Connecting
Earth Ground.
3.5
Connecting Earth Ground
3.5.1
Terminal
To help prevent damage from electrostatic charges or
other transient electrical surges, connect the system to
earth ground at Terminal 10 before making other
connections. A grounding rod or cold water pipe are
recommended earth ground references.
Do not use
telephone or electrical ground
for the earth ground connection. Use
1.8 mm (14 AWG) to 1.5 mm (16 AWG)
wire when making the connection.
Do not connect
other panel terminals to
earth ground.
3.5.2
Ground Fault Detect Enable
Ground fault detect capability is available
only on firmware versions 6.10 or higher.
Ground Fault is defined as “a circuit impedance to Earth
Ground of approximately 95 kilohms or less.” The
panel detects a ground fault on Terminals 1 to 9 and
Terminals 11 to 32 if the Ground Fault Detect Enable
jumper (S4) (see Figure 3) is locked (closed) and a non-
zero value is entered in Area 5 Silent Alarm Relay. See
the D9412G/D7412G Program Entry Guide. When the
jumper is in the unlocked (open) position, the panel does
not detect ground fault conditions. If a ground fault
condition occurs, the command centers display
SERVC
GND FAULT
and the panel transmits a Trouble Report
Ground Fault Area
(Modem IIIa
2
format only). For the
panel to detect a ground fault condition, the panel must
see the ground fault for a minimum of 30 consecutive
seconds. When the panel recognizes the ground fault
condition is corrected, a Restoral Report is sent. For the
restoral condition to be met, the ground fault must be
corrected for between 5 and 45 consecutive seconds.
3.0 Installation
The 9000 Series Control Panels log and
print a Ground Fault event as a Trouble
Point 256.
3.5.3
Locking the Reset Pin
Locking the reset pin disables the panel (see Figure 4).
The system ignores the command centers and points
while disabled.
CALL FOR SERVICE
appears in
command center displays while the pin is locked down.
On-board relays (Terminals 6, 7, and 8) and off-board
relays deactivate when the panel is reset. There is power
at Terminal 8 when the relay is deactivated. Activation
interrupts power at that terminal. The relays remain
deactivated while the reset pin is locked in the disable
position.
Releasing the reset pin from the closed position resets
the panel. The panel resets all its timers, counters,
indexes, and buffers. Any points that restore after a reset
is performed do not generate Restoral Reports.
If the reset pin is placed in the disable position when all
areas are armed, there must be an entry in the Answer
Armed program item. See RAM Parameters in the
D9412G/D7412G Program Entry Guide).
Locking the pin in the disable position allows powering
up of the panel and charging the battery while the
detection devices and command centers are being
installed.
Figure 3: Ground Fault Detect
GROUND FAULT DETECT
Enabled
Disabled
PHONE
LED
RED
ON WHEN
COMMUNICATING
OFF WHEN IDLE
LOOP START
PHONE MONITOR SELECT
GROUND START
Requires
Relay Model
D136 in Ground
Start Socket
GND START
1
3
2
1 - With S4 closed, panel detects ground faults.
2 - With S4 open, panel does not detect ground faults.
3 - S4, Ground fault detect enable.
Содержание D7412G
Страница 1: ...D9412G D7412G EN Operation Installation Guide Control Panels ...
Страница 2: ...Bosch Security Systems 10 03 43488E EN 2 D9412G D7412G Operation Installation Guide ...
Страница 10: ...Bosch Security Systems 10 03 43488E EN 10 D9412G D7412G Operation Installation Guide 1 0 Introduction Notes ...
Страница 36: ...Bosch Security Systems 10 03 43488E EN 36 D9412G D7412G Operation Installation Guide 7 0 On Board Points Notes ...
Страница 56: ...Bosch Security Systems 10 03 43488E EN 56 D9412G D7412G Operation Installation Guide Notes 10 0 Arming Devices ...
Страница 60: ...Bosch Security Systems 10 03 43488E EN 60 D9412G D7412G Operation Installation Guide Notes 11 0 SDI Devices ...