Manual 2100-583G
Page
13 of 48
NOTE:
All double o-ring fittings require “hand
tightening only”. Do not use a wrench or pliers as
retainer nut can be damaged with excessive force.
NOTE:
Apply provided petroleum jelly to o-rings to
prevent damage and to aid in insertion.
PIPING ACCESS TO UNIT
Water Piping to and from the unit enters the unit cabinet on
either the front or rear-side through the ability to relocate the
control panel. See Figure 3 of the cabinet.
LOOP CONNECTIONS
are a special double o-ring fitting
with a retainer nut that secures it in place. (It is the same
style of fitting used for the flow center connection on ground
loop applications.)
Various fittings are available so you may then connect to the
unit with various materials and methods. These methods
include 1" barbed fitting (straight and 90°), 1" MPT (straight
and 90°), and 1¼" hot fusion fitting (straight only). See
Product Specification Sheet.
LOAD CONNECTIONS
are standard 1" Female Pipe
Thread allowing for any standard 1" Male Pipe Threaded
fittings to be utilized to make the connection.
DESUPERHEATER CONNECTIONS
are standard ½"
Female Pipe Thread allowing for any standard ½" Male Pipe
Threaded fittings to be utilized to make the connection.