![BMC GW024 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/bmc/gw024/gw024_installation-instructions-manual_2779590028.webp)
Manual 2100-583G
Page
28 of 48
F
R
F
R
F
R
51
19374
76
10247
101
5697
52
18867
77
10000
102
5570
53
18375
78
9760
103
5446
54
17989
79
9526
104
5326
55
17434
80
9299
105
5208
56
16984
81
9077
106
5094
57
16547
82
8862
107
4982
58
16122
83
8653
108
4873
59
15710
84
8449
109
4767
60
15310
85
8250
110
4663
61
14921
86
8057
111
4562
62
14544
87
7869
112
4464
63
14177
88
7686
113
4367
64
13820
89
7507
114
4274
65
13474
90
7334
115
4182
66
13137
91
7165
116
4093
67
12810
92
7000
117
4006
68
12492
93
6840
118
3921
69
12183
94
6683
119
3838
70
11883
95
6531
120
3757
71
11591
96
6383
121
3678
72
11307
97
6239
122
3601
73
11031
98
6098
123
3526
74
10762
99
5961
124
3452
75
10501
100
5827
FIGURE 13
INLET & OUTLET THERMISTOR TEMPERATURE CURVES
TEMPERATURE F VS. RESISTANCE R OF TEMPERATURE SENSOR
DESUPERHEATER CONTROL BOARD
SEQUENCE OF OPERATION
The desuperheating control board will make a
determination whether or not to energize the pump relay
inclusive on the control board.
A. It will constantly monitor inputs from two
temperature sensors, Inlet & Outlet water sensors.
B. It will constantly monitor the “CC” Compressor
Contactor Signal (only energized when compressor
is operating).
C. Upon acknowledgement of “CC” signal, and
following two minutes, the control board will
energize the pump relay.
D. After 1½ minutes, based upon temperature difference
between Outlet & Inlet sensors, and the presence of
“CC” signal, the following will take place:
•
If temperature difference is greater than 3°F, the
control will continue to energize the pump relay.
•
If temperature difference is less than 3°F, then the
control will de-energize the pump relay.
• The control will next wait 10 minutes before
repeating first bullet point.
E. The Over Temperature Limit Switch is placed in
series with line voltage. Therefore, continuity
between “L” of line voltage and “L” of pump
output is forced broken when the Over Temperature
Limit Switch opens (see wiring diagram).
F. The 3-amp fuse is put in series with the “R”
connection to the board. Whenever the fuse is
blown, the control board will lose power and
consequently, the relay will disengage.
DESUPERHEATER (POTABLE HOT WATER ASSIST)