OPERATION OF THE HEAT RECOVERY
UNIT
The pump module is a very simple device containing basic
controls and a circulating pump. Heat is transferred from
the hot refrigerant (discharge gas) to the cool water.
The operation of the Desuperheater Pump Module is
controlled first by the operation of the Geothermal
Heat Pump and secondly by internal controls with
desuperheater logic control. A low voltage signal sent in
tandem to the signal to energize the compressor contactor
is connected to the desuperheater logic control board, and
acts as the primary on/off switch for the circulating pump.
Also connected to this board is a temperature overlimit
device which shuts down the desuperheater once inlet
water has exceeded 125°F so the water cannot create a
scald condition.
There are also two (2) thermistor sensors connected to
the control board. These thermistors are measuring and
controlling to ensure there is a positive heat differential
across the water being circulated. When operating in
Part Load Condition, there are certain conditions (source
temperatures versus hot water temperatures) that potential
exists where heat could transfer into the refrigeration
system instead of the refrigeration system into the hot
water. Through the control board logic, these thermistors
ensure there is at least a 2° positive differential between
entering/leaving water temperatures, and will shut down
the pump accordingly.
START UP AND CHECK OUT
Be sure all shut off valves are open and all power supplies
are on. Open a hot water faucet to permit any air to bleed
from the plumbing.
NOTE:
The inherent design of this pump for maximum
efficiency means this pump is not self-priming. It is
imperative to check the air has been adequately bled from
the system. There is a bleed-port built into desuperheater
coil water system that should be utilized after the
household water system has been fully restored. The
bleed port is located on the water-tube on the top of the
desuperheater exchange coil (above cooling expansion
valve in the GW-Series products).
Turn ON the heat pump system and verify the circulating
pump will operate. Feel the “WATER TO UNIT” and
“WATER FROM WATER HEATER” tubes for noticable
difference in temperature. Turn OFF the system and
verify that the circulating pump stops.
NOTE:
When checking the refrigerant operating
pressures of the ground source heat pump the
desuperheater must be turned off. With the desuperheater
operating, a wide variance in pressure can result, giving
the service technician the indication there is a charge
problem when the unit is operating correctly.
MAINTENANCE
CLEANING THE HEAT EXCHANGER
– If scaling of
the coil is strongly suspected, the coil can be cleaned with
a solution of phosphoric acid (food grade acid or liquid ice
machine cleaner {pre-mix phosphoric acid}). Follow the
manufacturer’s directions for the proper mixing and use of
cleaning agent.
DESUPERHEATER (POTABLE HOT WATER ASSIST)