TABLE 2
ELECTRICAL SPECIFICATIONS
TABLE 3
SOURCE SIDE WATER COIL PRESSURE DROPS
(Based upon 15% Methanol in Heating Mode @ 50°F)
+75°C copper wire ++ HACR type circuit breaker
MODEL
GW024
GW036
GW048
GW060
GW070
Electrical Ratings (Volts/Hz/Phase)
208/230-60-1
Operating Voltage Range
253-197 VAC
Minimum Circuit Ampacity
16.9
21.4
28.8
36.1
39.4
+Field Wire Size
10
8
6
6
6
Ground Wire Size
12
12
10
10
10
++Delay Fuse of Circuit Breaker Max.
25
35
50
60
60
COMPRESSOR
Volts
208/230-60-1
Rated Load Amps (230/208)
8.2 / 9.2
12.2 / 14.0
17.6 / 20.3
21.8 / 24.1
29 / 32
Branch Circuit Selection Current
11.7
15.3
21.2
27.1
29.7
Locked Rotor Amps (230/208)
58.3
83.0
104.0
152.9
179.2
Flow Center (Based upon DORFC-2)
Volts
208/230-60-1
Amps
2.14
Desuperheat Pump Motor
Volts
208/230-60-1
Amps
0.15
Model
GPM
GW024
GW036
GW048
GW060
GW070
PSID
Ft. Hd.
PSID
Ft. Hd.
PSID
Ft. Hd.
PSID
Ft. Hd.
PSID
Ft. Hd.
4
.93
2.15
5
1.55
3.58
1.57
3.62
6
2.17
5.01
2.19
5.05
1.63
3.75
7
2.79
6.44
2.81
6.48
2.21
5.10
8
3.48
8.03
3.56
8.21
2.80
6.45
1.76
4.06
9
4.17
9.62
4.31
9.94
3.38
7.80
2.20
5.08
10
0
5.18
11.95
4.12
9.49
2.64
6.09
2.6
6.07
11
6.05
13.96
4.85
11.19
3.08
7.11
3.1
7.17
12
5.70
13.15
3.58
8.25
3.6
8.28
13
6.55
15.11
4.07
9.39
4.1
9.39
14
4.63
10.67
4.6
10.58
15
5.18
11.95
5.1
11.77
16
5.74
13.23
5.7
13.12
17
6.3
14.46
18
6.9
15.81