2
Installation
7
©
Moffat Ltd, January 2007
Revision 1/
Blue Seal Evolution Series Gas Salamander
6.
Connect gas supply to the appliance. A suitable jointing compound which resists the breakdown
action of LPG must be used on every gas line connection, unless compression fittings are used.
7.
Check all gas connections for leakages using soapy water or other gas detecting equipment.
8.
Check gas operating pressure is as shown in “Specifications” section.
9.
Adjust the regulator spring adjusting nut to set the gas operating pressure at the correct value
shown in the “Specifications” section.
NOTE: The operating pressure to be measured at the manifold test point and with all burners
operating at the “High Flame” setting.
10. Turn off the mains gas supply and bleed the gas out of the appliance gas lines.
11. Turn on the gas supply and the appliance.
12. Verify the operating pressure remains correct (Re-adjust the regulator if required).
Commissioning
1.
Before leaving the new installation;
a. Check the following functions in accordance with the operating instructions specified in the
“Operation” section of the User manual.
•
Light the Pilot Burners.
•
Light the Main Burners.
•
Check the Low Fire burner operation.
•
Check the High Fire burner operation.
•
Check the Racking System operation.
b. Ensure that the operator has been instructed in the areas of correct lighting, operation, and
shutdown procedure for the appliance.
2.
The User manual must be kept by the owner for future reference, and a record of
Date of
Purchase,
Date of Installation
and
Serial Number of Unit
recorded and kept with the manual.
(These details can be found on the Rating Plate attached to the R/H side panel (refer to
the “Gas Connection” section).
NOTE: If for some reason it is not possible to get the unit to operate correctly, shut off the
gas supply and contact the supplier of this unit.
WARNING:
D
O
NOT
USE
A
NAKED
FLAME
TO
CHECK
FOR
GAS
LEAKAGES
.