MK LIT (E5) 01/2021
page 97/172
Use the Section editor to configure the operation lines.
Section view.
Select the field “Functions on/off”.
“Functions on/off” entry menu.
Mark / unmark the checkbox of the desired
function to activate / deactivate it and press
the
Confirm
icon.
The controller returns to the section view.
Activated operation line: switching status “1” (On)
Deactivated operation line: switching status “0” (Off)
The operation lines count from right to left.
Example:
Activated operation line “Switching output 3” = 0000000000000
1
00
Deactivated operation line “Switching output 3” = 0000000000000
0
00
17.7.4 Setpoint entry
•
Select the field “Temperature” and enter the desired temperature setpoint.
Setting range: -50 °C /
-58°F
up to 110 °C /
230 °F:
Confirm entry with
Confirm
icon. The controller returns to the section view.