MK LIT (E5) 01/2021
page 71/172
For control reasons the refrigeration machine starts with a delay time. The refrigeration ma-
chine also turns off with a 5 minutes delay. This explains why the compressor may remain op-
erating also during positive temperature jumps.
11.5 Controller settings upon start up
The window “Language selection” enables the
language selection
, in case that it’s activated in the “Start-
up” menu. Afterwards occurs a request of the
time zone
and the
temperature unit
.
The controller will function in the
operating mode
, which was active before the last shut-down. It controls
temperature in fixed value operating mode to the last entered values and in the program mode to the set
points achieved beforehand.
Locked operation
Provided that the user administration has been activated by the assignment of passwords for the different
authorization types, the
controller operation
is first locked after turning on the unit, recognizable by the
closed lock icon in the header.
In the locked view the controller provides all display functions. No setting functions are available.
The setpoints are shaded (light grey) in normal display. Changing them by direct entry in the fixed value
operating mode is not possible. The functional icons for setpoint entry and program start in the footer are
without function.
After turning on the unit, user log-in is required to operate the controller (chap. 19.2)
Operation without user log-in / without password-protection
If the password function has been deactivated, after turning on the unit without user log-in there are those
controller functions available, which correspond to the highest authorization level without a password pro-
tection. There is no lock icon in the header.
Содержание 9020-0402
Страница 159: ...MK LIT E5 01 2021 page 159 172 30 7 Dimensions LIT MK 240 dimensions mm...
Страница 160: ...MK LIT E5 01 2021 page 160 172 LIT MK 720 dimensions mm...
Страница 161: ...MK LIT E5 01 2021 page 161 172 31 Certificates and declarations of conformity 31 1 EU Declaration of Conformity...
Страница 162: ...MK LIT E5 01 2021 page 162 172...
Страница 163: ...MK LIT E5 01 2021 page 163 172...
Страница 165: ...MK LIT E5 01 2021 page 165 172...
Страница 166: ...MK LIT E5 01 2021 page 166 172 31 3 Safety concept certificate from T V S d...
Страница 173: ......