Installation, Operation and Maintenance Manual
VCIOM-15345-EN Rev. 1
February 2022
63
Customizing Biffi EHO
Section 8: Customizing Biffi EHO
Menu Name
Menu
Key
Configuration/
Calibration Value
Default
Action
CALIBRATE UPPER LIMIT FOR ANALOG
INPUT CHANNEL
Calibrate the the analog input channel with
an external current source. External current
source needs to be connected to source
20 mA equivalent signal when this menu is
being flashed. The signal has to be in the
range 3.6 mA - 22 mA.
iU
Yes/No
N/A
UPPER LIMIT VALUE CALIBRATED
(CALIBRATION STATUS)
If the input value is valid, the device will
return success.
cU
N/A
Analog Input Calibration
Status. Not Searchable/
Configurable
CALIBRATION FAILED (CALIBRATION STATUS)
If the input value is invalid, the device will
return fail. The Biffi EHO will maintain the
previous calibrated value.
cF
N/A
Analog Input Calibration
Status. Not Searchable/
Configurable
ANALOG OUTPUT 1 CALIBRATION
Calibrate Analog Output 1 Channel
.
o1
Yes/No
N/A
CALIBRATE LOWER LIMIT OF ANALOG
OUTPUT 1
Calibrate the Analog Output 1 Channel for
4 mA equivalent value. The Channel Output
needs to be monitored externally.
oL
Yes/No
N/A
ANALOG OUTPUT 1 CALIBRATION CHOICE
Select if the Analog Output 1 needs to be
increased or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 1
The Analog Output can be changed based
on selection at cC menu. 'Yes' option at
this menu means Accept the Output. 'No'
option at this menu will Increase or
Decrease the Output.
c1
Yes/No
N/A
LOWER LIMIT CALIBRATED
(CALIBRATION STATUS)
The Analog Output 1 channel is calibrated
for the desired output.
cL
N/A
Analog Input Calibration
Status. Not Searchable/
Configurable
CALIBRATION FAILED (CALIBRATION STATUS)
Calibration for Analog Output 1 channel
has failed. The Biffi EHO will maintain the
previous calibrated value.
cF
N/A
Analog Input Calibration
Status. Not Searchable/
Configurable
CALIBRATE UPPER LIMIT OF ANALOG
OUTPUT 1
Calibrate the Analog Output 1 Channel for
20 mA equivalent value.
Note: The channel output needs to be
monitored externally.
oU
Yes/No
N/A
ANALOG OUTPUT 1 CALIBRATION CHOICE
Select if the Analog Output 1 needs to be
increased or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 1
The analog output can be changed based
on selection at [c][C] menu. 'Yes' option at
this menu means the out- put is accepted.
'No' option at this menu will increase or
decrease the output.
c1
Yes/No
N/A
UPPER LIMIT CALIBRATED
(CALIBRATION STATUS)
The Analog Output 1 channel is calibrated
for the desired output.
cU
N/A
Analog Output 1
Calibration Status. Not
Searchable/Configurable
CALIBRATED FAILED (CALIBRATION STATUS)
Calibration for Analog Output 1 channel
has failed. The Biffi EHO will maintain the
previous calibrated value.
cF
N/A
Analog Output 1
Calibration Status. Not
Searchable/Configurable
ANALOG OUTPUT 2 CALIBRATION
Calibrate Analog Output 2 Channel.
o2
Yes/No
N/A