Data Definition Profibus DP
Cyclic Output Data
Variable
name
Description
Type
Size
Mould Level
Current Mould Level unit: %/mm/inch (selectable)
Float
32 Bit
Detector
Raw Value
Current Detector Raw Value unit: GAMMAcast -
Pulses per Second (CPS)
ECcast – Millivolt (mV)
Float
32 Bit
Detector
Temperature
Current Detector Temperature
Unit: °C/°F (selectable)
Float
32 Bit
Calibration
Index
Currently used calibration [0 ... 7] (decimal)
(Calibration curve, alarm thresholds, time constant,
etc.)
Byte
8 Bit
System
Status
System Status. This field contains binary coded
information:
Bits 0-2: Main state of the system
Bit 0; 0x1 (1): RUN/MEASUREMENT RUNNING
Bit 1; 0x2 (2): STOP
Bit 2; 0x4 (4): ERROR
Bit 3: Warning
Bit 3; 0x0 (0): NO WARNING
Bit 3; 0x1 (1): WARNING
Bits 4-11: Stop condition
Bit 4-11; 0x00 (0): Not in STOP state
Bit 4; 0x01 (1): No detector found
Bit 5; 0x02 (2): Detector Offline
Bit 6;0x04 (4): Test Mode
Bit 7;0x08 (8): Calibration running
Bit 8;0x10 (16): Full Adjustment running
Bit 9;0x20 (32): Empty Adjustment running
Bits 12-19: Alarms
Bit 12-19; 0x00 (0) No alarm running
Bit 12; 0x01 (1): Detector Over Temperature
Bit 13; 0x02 (2): Min. Fill Level
Bit 14; 0x04 (4): Max. Fill Level
Bit 15; 0x08 (8): Gating mode (time constant)
Bit 16; 0x10 (16): Trim Adjust Up running [only ECcast]
Bit 17; 0x20 (32): Trim Adjust Down running [only
ECcast]
Bits 20-31: Error number
A 12 Bit unsigned integer number representing the
number of the actual error
Error# < 1000: LB 452 error
Error# > 1000: Detector error
Unsigne
d
Integer
32 Bit
136 Bit
= 17 Bytes
Cyclical Input Data
Содержание castxpert LB 452
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ...c 2 Safety 14 Rev 04 03 2015 b ...
Страница 22: ......
Страница 40: ......
Страница 120: ......
Страница 138: ......
Страница 140: ...c 10 Decommissioning 140 Rev 04 03 2015 b ...
Страница 146: ...c 11 Technical Information 146 Rev 04 03 2015 b 11 4 c LB 452 Connections Rear Overview ...
Страница 147: ...c 11 Technical Information b Rev 04 03 2015 147 11 5 c LB 452 Connections Measuring channel base module ...
Страница 148: ...c 11 Technical Information 148 Rev 04 03 2015 b 11 6 c LB 452 Connections Measurement ChannelEx tension Module ...
Страница 151: ...c 12 Declaration of Conformity b Rev 04 03 2015 151 12Declaration of Conformity ...
Страница 152: ...c 12 Declaration of Conformity 152 Rev 04 03 2015 b ...
Страница 155: ...c 13 Index b Rev 04 03 2015 155 ...