![Berker 75730010 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/berker/75730010/75730010_technical-documentation-manual_2737474006.webp)
EIB Alarm Central Unit, surface-
mounted
75730010
Technical
Documentation
© Gebr.Berker 2005
Version: 18.08.2005
Page: 6 / 81
(Subject to prior change)
75730010.doc
Part 9
Wiring diagram:
Terminal assign-
ment:
Alarm indicators
Alarm indicators can be directly connected to the EIB alarm central unit - terminal strip X3.
As an alternative, you can connect alarm indicators to the EIB via suitable actuators and trig-
ger them by telegrams (refer to 'Object description').
Integrate the sabotage contacts of the alarm indicators into the sabotage circuit (refer to
'Sabotage security').
the red LEDs opposite to the terminals indicate when an output is being triggered (output
being triggered = LED is lit).
GND
12V / 0,1A
Blitz (-)
ASIR (-)
ISIR (-)
12V (+)
12V (+)
12V (+)
GND
X3
Terminal
Function
Relay
Potential change-over contact facilitating the switching of a load.
Switching capacity: 12 VAC/DC, 6 A, max.
12V/0.1A/GND
+12 V connection for the supply of external alarm components
(e. g. to be switched via the relay). Max. load 100 mA (1.2 W).
12 V (+)/Blitz (-)
For the connection of a flashlight. Can be activated in the event of
alarm without any time limit until disarming takes place (depending on
parameter).
12 V (+)/ASIR (-)
For the connection of an outdoor siren. In the event of alarm, it may be
on for a max. period of 180 s (triggering period depending on parame-
ter).
12 V (+)/ISIR (-)
For the connection of an indoor siren. In the event of alarm, it should
be on for a max. period of 180 s (triggering period depending on pa-
rameter).