EIB Alarm Central Unit, surface-
mounted
75730010
Technical
Documentation
© Gebr.Berker 2005
Version: 18.08.2005
Page: 13 / 81
(Subject to prior change)
75730010.doc
Part 9
System monitoring objects:
Object
Function
Name
Type
Flag
203
System monitoring
ATD checkback input fault
1-bit
C, W, (R)
1)
226
All safeguarding areas
Detector test
1-bit
C, W, (R)
1)
227
Heartbeat check
5)
Heartbeat check input
1-bit
C, W, (R)
1)
228
Heartbeat check
5)
Heartbeat check output
1-bit
C, T, (R)
1)
229
System monitoring
Alarm central unit fault
1-bit
C, T, (R)
1)
Display control objects:
6)
Object
Function
Name
Type
Flag
207
Info display unit 1
Line 1
14-byte
C, T, (R)
1)
208
Info display unit 1
Line 2
14-byte
C, T, (R)
1)
209
Info display unit 1
Line 3
14-byte
C, T, (R)
1)
210
Info display unit 2
Line 1
14-byte
C, T, (R)
1)
211
Info display unit 2
Line 2
14-byte
C, T, (R)
1)
212
Info display unit 2
Line 3
14-byte
C, T, (R)
1)
213
Info display unit 3
Line 1
14-byte
C, T, (R)
1)
214
Info display unit 3
Line 2
14-byte
C, T, (R)
1)
215
Info display unit 3
Line 3
14-byte
C, T, (R)
1)
216
Info display unit 4
Line 1
14-byte
C, T, (R)
1)
217
Info display unit 4
Line 2
14-byte
C, T, (R)
1)
218
Info display unit 4
Line 3
14-byte
C, T, (R)
1)
219
Info display unit 1
Selection
1-bit
C, W, (R)
1)
220
Info display unit 2
Selection
1-bit
C, W, (R)
1)
221
Info display unit 3
Selection
1-bit
C, W, (R)
1)
222
Info display unit 4
Selection
1-bit
C, W, (R)
1)
Date/time control objects:
Object
Function
Name
Type
Flag
223
System clock
Time
3-byte
C, W, (R)
1)
224
System clock
Date
3-byte
C, W, (R)
1)
1)
For the objects selected (L) the current object status can be read out (setting L flag).
2)
The detector objects will be created dynamically in dependence on the parameterized detectors of the individual
safeguarding areas (fire, attack, SA 1 - 4). The names of the communication objects and the object table will
change correspondingly.
3)
The assignment of the "wired detector input" object to one of the four safeguarding areas can be freely param-
eterized in dependence on the configuration.
4)
These objects will be created dynamically in dependence on the parameterized arming areas.
5)
The "heartbeat check" objects can be disabled or enabled through a parameter.
6)
The info display objects are visible in dependence on the parameterized info display units.