EIB Alarm Central Unit, surface-
mounted
75730010
Technical
Documentation
© Gebr.Berker 2005
Version: 18.08.2005
Page: 2 / 81
(Subject to prior change)
75730010.doc
Part 9
Illustration:
F
4
F
3
F
2
F
1
Melder
Sabo
R-Sabo
GND
ÜG (-)
12V / 0,1A
ÜG-R
ÜG-S/U
ÜG-E
ÜG-F
ÜG-Ü
ÜG-S
GND
12V / 0,1A
Blitz (-)
ASIR (-)
ISIR (-)
12V (+)
12V (+)
12V (+)
J1
GND
X2
X3
L
P
1
Betrieb
LED
Prog
S
a
b
o
A
C
2
3
0
V
X10
5
1
3
2
8
4
8
6
J2
9
F
5
7
L
P
2
-
-
+
Dimensions:
Width:
210 mm
Height:
270 mm
Depth:
73 mm
Controls:
1 Programming key and programming LED.
2 EIB connection.
3 Sabotage contact (cover contact).
4 9 red LEDs to indicate the output states: alarm transmission device (ÜG = ATD), outdoor siren (Asir), indoor siren
(Isir), flashlight and potential-free relay contact (LED lit = output active).
5 Mains voltage fuse (F4 = 3.15 A, slow-blow).
6 Actuator output fuses (F1
BCU sec. part
= 100 mA, slow-blow/F2
add. +12 V supply
= 100 mA, slow-blow/
F3
transm. unit
= 100 mA, slow-blow).
7 "Reverse battery protection" fuse (F5 = 3.15 A, fast-blow).
8 Jumper J1, "bus voltage failure in the armed state", "Betrieb" (device ON) LED.
The green LED indicates the status of the bus voltage. If it is blinking the bus voltage has failed or the device is
being programmed. In this case, the response of the alarm central unit can be set with jumper J1 (refer to "Re-
sponse to Bus Failure").
9 Although jumper J2 has no function, it must be inserted (its position is irrelevant).