EIB Alarm Central Unit, surface-
mounted
75730010
Technical
Documentation
© Gebr.Berker 2005
Version: 18.08.2005
Page: 17 / 81
(Subject to prior change)
75730010.doc
Part 9
Function scope (continued)
•
A fire fault signal (collective signal from all fire detectors) can be transmitted through an EIB object.
•
An armed/disarmed state signal can be transmitted through the "armed/disarmed state signal to the ATD" EIB ob-
ject and a fault signal through the "fault signal to the ATD" EIB object.
•
You can parameterize up to four independent display units (e. g. info display unit). Such display units can be as-
signed to different arming areas (arming areas 1 to 4/fire/attack).
You may also use more than four display units, the latter then having to be connected in parallel. In such case, the
areas to be viewed on the display units connected in parallel, however, will be the same since the group addresses
of a display group will be assigned several times.
•
You can interconnect several alarm central units to keep under surveillance any possibly larger areas (manufactur-
ing halls, shopping centres). For this purpose, two objects for mutual heartbeat checking of the alarm central units
are available. It will be checked whether the life sign of the sending partner alarm central unit comes in at some
monitoring interval. If such telegram does not arrive a parameterizable fault or alarm signal will be raised by the
other alarm central unit.
•
All detectors assigned can be monitored for presence within a monitoring period. If one of the detectors does not re-
spond within the sampling interval a fault or sabotage signal will be raised, depending on the state of the system.
•
In the event of an attack or an intrusion, you can transmit a silent alarm only through the alarm transmission device.
To recognize the alarm could be transmitted without any problems it is possible for the alarm transmission devices
to pass forward to the alarm central unit any transmission error which might have occurred. For this purpose, the
"ÜG-R" wired (checkback) input or the "ATD checkback input" EIB object is available. For sabotage and attack, you
can parameterize the response of the alarm central unit to a transmission error signalled. Thus, the flashlight, the
indoor and the outdoor siren can be additionally activated should any error occur.
•
Through EIB objects (e. g. by a DCF-77 receiver), you can synchronize the system clock integrated into the alarm
central unit. As an alternative, the PC time can be transmitted to the alarm central unit through the ETS plug-in. The
changeover from summer to winter time and vice versa will be done automatically by the alarm central unit.
•
Various events (arming, alarm, fault) will be logged together with their date and time and saved. You can read out this
event log via the ETS plug-in. In this connection, you can either save the read-out data into a file or print it out.
•
In the detector test mode, you can check all detectors of the alarm system without raising any alarm or the like.
During the test of the detectors (magnetic contacts. motion detectors, fire detectors, attack pushbuttons, etc.), the
latter will be kept in the display units until you deactivate the detector test mode.