57
The automatic running time detection function is activated in the
software.
The N conductor terminals of the pertaining outputs are connected
as shown (Fig. 5).
Programming runs must be performed only in the manual control
mode or with the commissioning software.
Move the blinds/shutters into the upper limit-stop position (per-
form a reference run).
The upper limit-stop position is reached.
Move the blinds/shutters in the manual control mode into the
lower limit-stop position.
Move the blinds/shutters in the manual control mode into the
upper limit-stop position.
The running times are now stored.
The shutter actuator stores the blind/shutter positions permanently.
Without stored running times, the shutter actuator sets for each
output the internal flag ‚Invalid position‘ which can be read out.
In operation, the shutter actuator can adapt itself to changes in
the running times of the blinds/shutters that are due, for instance,
to ageing of the drives. The slat running time is taken into ac-
count. The modified times are stored permanently only in the
manual control mode.
Commisioning
GB
Содержание 7531 40 18
Страница 6: ...6 Bedienung D 2...
Страница 14: ...14 Anschluss D 3...
Страница 38: ...38 GB Operation 2...
Страница 46: ...46 GB Connection 3...
Страница 70: ...70 Bediening NL 2...
Страница 78: ...78 Aansluiting NL 3...
Страница 97: ...97 Notes...
Страница 98: ...98 Notes...
Страница 99: ...99 Notes...