EFFECT

CAUSE

REMEDY

A delayed activation of the ventilation respect to 

the new temperature or function settings.

The circuit valve needs some time to open and 

as a result the hot or cold water takes time to 

circulate in the appliance.

Wait for 2 or 3 minutes to open the circuit valve.

The appliance does not activate the ventilation.

No hot or cold water in the system.

Check that the water boiler or cooler are 

functioning correctly.

The ventilation does not activate even if there is 

hot or cold water in the hydraulic circuit.

The hydraulic valve remains closed.

Dismount the valve body and check if the water 

circulation is restored. 
Check the working efficiency of the valve by 

powering it separately with 230V. If it activates 

the problem could be the electronic control.

The fan motor is blocked or burnt out.

Check the windings of the motor and thefree 

rotation of the fan.

The micro-switch that stops the ventilation when 

the filter grill is opened does not close correctly.

Check that by closing the grill the micro-switch 

contact is activated.

The electrical connections are not correct.

Check the electrical connections.

The appliance leaks water during the heating 

function.

Leaks in the hydraulic connections of the system.

Check the leak and fully tighten the connections.

Leaks in the valve unit.

Check the state of the gaskets.

There are formations of dew on the front panel.

Thermal insulation unstuck.

Check the correct positioning of the thermo-

acoustic insulation paying attention to that in the 

front above the finned battery.

There are drops of water on the air outlet grill.

In situations of high humidity (>60%) 

condensation could form, especially at the 

minimum ventilation speeds.

As soon as the humidity starts falling the 

phenomenon disappears. In any case the 

presence of a few drops of water in the appliance 

does not indicate a malfunction.

The appliance leaks water only during the cooling 

function.

The condensation bowl is blocked.

Slowly pour a bottle of water in the low part of 

the battery to check the drainage; if necessary, 

clean the bowl and/or increase the inclination of 

the drainage pipe.

The condensation discharge does not need an 

inclination for correct drainage.

The connection pipes and the valve unit are not 

insulated well.

Check the insulation of the pipes.

The appliance makes a strange noise.

The fan touches the structure.

Check the clogging of filters and clean them if 

necessary

The fan is unbalanced.

The unbalancing causes excessive vibrations of 

the machine; replace the fan.

Check the clogging of filters and clean them if 

necessary

Clean the filters

Содержание Tivano Series

Страница 1: ...Ventilconvettore riscaldamento raffrescamento e deumidificazione Cooler convector heating cooling and dehumidificationr TIVANO EN IT Manuale Installatore Installation Manual...

Страница 2: ...talia Repubblica di San Marino Citt del Vaticano a partire dalla data di acquisto del prodotto stesso Conservare la documentazione di acquisto fiscalmente valida del prodotto da presentare all Assiste...

Страница 3: ...zia esterna 20 24 Pulizia filtro aspirazione aria 20 25 Consigli per il risparmio energetico 21 26 Anomalie e rimedi 22 27 Tabella delle anomalie e dei rimedi 22 EN The following symbols are used in t...

Страница 4: ...urezza e di prevenzione degli infortuni Rispettare le leggi in vigore nel Paese in cui viene installata la macchina relativamente all uso e allo smaltimento dell imballo dei prodotti impiegati per pul...

Страница 5: ...oni Bianco RAL 9003 Tutti i modelli sono per sistemi a 2 tubi Le unit in abbinamento con i vari controlli a bordo hanno una impostazione di fabbrica con parametri per velocit massima a 1700 giri min P...

Страница 6: ...aria mandata reversibile H Bacinella raccolta I Schienale strutturale L Mantello frontale M Fianchi laterali smontabili N Filtro aria P Microventilatore versione R EN 4 Identification Technical Tag T...

Страница 7: ...wer consumption e W 15 1 23 2 26 4 36 40 3 Corrente massima assorbita Maximum current consumption e A 0 14 0 21 0 24 0 35 0 38 Potenza elettrica assorbita alla minima velocit Power consumption at mini...

Страница 8: ...0 5 1 0 5 3 5 3 0 2 5 2 0 1 5 1 0 0 9 0 8 0 7 0 6 8 0 7 0 6 0 5 0 4 5 4 0 15 10 9 0 25 20 0 0 0 2 4 5 1 2 3 Perdita di carico kPa Pressure drop kPa Perdita di carico kPa Pressure drop kPa Portata d ac...

Страница 9: ...20 20 E mm 400 400 400 400 400 F mm 2500 2500 2500 2500 2500 Dimensioni di ingombro Dimensions Tivano Tivano R L mm 723 923 1123 1323 1523 Peso netto Net weight Tivano Tivano R Kg 17 20 23 26 29 Tiva...

Страница 10: ...ondizioni normali con funzioni diminima temperatura dell acqua in riscaldamento 30 C e massima in raffrescamento 20 C La scheda prevede anche il funzionamento privo di sonda nel qual caso le soglie di...

Страница 11: ...a versione con effetto radiate se disponibile 2k M1 motore ventilatore DC inverter CV uscita elettrovalvola termostato SV commutatore di velocit termostato H2 sonda temperatura acqua 10k TA termostato...

Страница 12: ...ore Etichette garanzia ricambi Dima in carta Supporti metallici Adattatori da 3 4 a Eurokonus Cablaggio versione R A Fianchetto sinistro B Fianchetto destro EN 9 Product delivery 10 Handling and trans...

Страница 13: ...gura sono indicate le distanze minime di montaggio del ventilconvettore da pareti e mobili presenti nell ambiente EN 12 Installation Preliminary instructions The place of installation must be determin...

Страница 14: ...a e sinistra alto e basso Montare l unit verificando il corretto aggancio sulle staffe e la sua stabilit A Tasselli B Staffe EN 14 Vertically mounted When mounting on the floor with support feet refer...

Страница 15: ...tubo di scarico L eventuale contropendenza della linea di scarico pu provocare perdite d acqua A Tasselli B Staffe C Viti D Tubo di drenaggio EN 15 Ceiling or horizontal installation Tivano only A Do...

Страница 16: ...ella rete fognaria si consiglia di realizzare un sifone per impedire la risalita dei cattivi odori verso gli ambienti La curva del sifone deve essere EN A Eurokonus adapter 16 Hydraulic connections Th...

Страница 17: ...modo da impedire gocciolamenti di condensa all esterno della bacinella di raccolta stessa Coibentare il tubo di scarico della condensa della bacinella per tutta la sua lunghezza A Raccordo di scarico...

Страница 18: ...l detentore sul gruppo idraulico sia aperto Se ci si trova in mancanza di alimentazione elettrica e la termovalvola gi stata alimentata precedentemente sar necessario utilizzare l apposito cappuccio p...

Страница 19: ...il reaching the nominal value for the system Check the hydraulic seal of the gaskets It is advisable to repeat these operations after the appliance has been running for a few hours and periodically ch...

Страница 20: ...in ambiente normalmente pulito Estrazione celle filtranti Estrarre il filtro tirando in senso orizzontale verso l esterno A Filtro B Lembo inferiore C Sede del filtro EN 22 Maintenance 23 Cleaning the...

Страница 21: ...cali da climatizzare Limitare per quanto possibile in estate l irradiazione diretta dei raggi solari negli ambienti da climatizzare utilizzare tende tapparelle ecc EN Cleaning filtering seats Suck up...

Страница 22: ...one riscaldamento Perdite nell allacciamento idraulico dell impianto Controllare la perdita e stringere a fondo i collegamenti Perdite nel gruppo valvole Verificare lo stato delle guarnizioni Sono pre...

Страница 23: ...s in the hydraulic connections of the system Check the leak and fully tighten the connections Leaks in the valve unit Check the state of the gaskets There are formations of dew on the front panel Ther...

Страница 24: ...di tutta la sua produzione le caratteristiche estetiche e dimensionali i dati tecnici gli equipaggiamenti e gli accessori possono essere soggetti a variazione The manufacturer strives to continuously...

Отзывы: