METEO GREEN HE R.S.I.
PROGRAMMABLE PARAMETERS
N°
PAR.
DESCRIPTION PARAMETERS
UNIT OF
MEASURE
MIN
MAX
DEFAULT
(setted in
factory)
PARAMETERS
(setted by techn.
assist. centre)
1
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
2
THIS PARAMETER IS NOT influential
10-16-20-26-30-34-50-70
20
3
INSULATION LEVEL OF BUILDING
min
5
20
5
10
DHW MODE
0 (OFF)
1 (Instantaneous)
2 (Mini-tank)
3 (External water-tank with thermostat)
4 (External water-tank with sensor)
5 (DS built-in storage tank)
6 (3S built-in storage tank)
3
11
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
60
12
WATER TANK MAXIMUM SET-POINT
°C
40
80
60
13
DELIVERY TERMPERATURE EXT. WATER TANK
°C
50
85
80
14
DELTA EXTERNAL WATER TANK (ON)
°C
0
10
5
20
HEATING MODE
0 (OFF)
1 (ON)
2 (not used)
3 (CONNECT AP)
4 (not used)
5 (not used)
6 (CONNECT AT/BT)
7 (Remote panel + CONNECT AT/BT)
8 (Remote panel + zone valves)
1
21
HEATING CIRCUIT MAXIMUM SET-POINT
°C
40
80
80
22
MINIMUM HEATING SET POINT
°C
20
39
20
23
MAXIMUM HEATING FAN SPEED
rpm
G20 G31
25kW 60** 60**
35kW 60** 59**
MAX
24
MINIMUM HEATING FAN SPEED
rpm
G20 G31
25kW 12** 19**
35kW 12** 19**
MIN
25
DIFFERENTIAL HEATING POSITIVE
°C
2
10
6
26
DIFFERENTIAL HEATING NEGATIVE
°C
2
10
6
28
MAX HEATING POWER REDUCTION TIMER
min
0
20
15
29
FORCED HEATING SHUT DOWN TIMER
min
0
20
5
30
HEATING TIMER RESET FUNCTION
-
0 (NO)
1 (YES)
0
31
MAXIMUM HEATING SET POINT 2CH (II circuit)
°C
40
80
45
32
MINIMUM HEATING SET POINT 2CH (II circuit)
°C
20
39
25
35
DIFFERENTIAL HEATING POSITIVE 2CH
°C
2
10
3
36
DIFFERENTIAL HEATING NEGATIVE 2CH
°C
2
10
3
40
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
41
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
42
S.A.R.A. FUNCTION
0 (OFF)
1 (AUTO)
1
43
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
44
THERMOREGULATION FUNCTION
0 (OFF)
1 (AUTO)
1
45
INCLINATION THERMOREGULATION CURVE
(OTC)
-
2,5
40
20
46
THERMOREGULATION FUNCTION 2CH
0 (OFF)
1 (AUTO)
1
47
INCLINATION THERMOREGULATION CURVE
(OTC) 2CH
-
2,5
40
10
48
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
0
50
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
51
HEAT REQUEST TYPE CH1 (I circuit)
-
0
1
0
52
HEAT REQUEST TYPE CH2 (II circuit)
-
0
1
0
61
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
4
62
HEATING ANTIFREEZE FUNC. DELIVERY TEMP.
(ON)
°C
0
10
6
63
WATER TANK ANTIFREEZE FUNC. DELIV. TEMP.
(ON)
°C
0
10
6
65
EXTERNAL SENSOR REACTIVITY
0 (very fast)
255 (very slow)
20
85
SEMI-AUTOMATIC FILLING
0 (disabled)
1 (enabled)
0
86
AUTOMATIC FILLING PRESSURE (ON)
bar
0,4
1,0
0,6
87
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
0
90
VARIABLE SPEED PUMP
-
0
100
41
92
enable post-circulation from dhw to heating
-
0
1
0
93
duration of post-circulation from dhw to heating
-
1
255
5
94
pump in continual mode ch1 (circuit 1)
-
0
1
0
95
pump in continual mode ch2 (circuit 2)
-
0
1
0
** The value is expressed on the display in rpm/100 (example 3.600 = 36)
Some defaults may be different from what is indicated in the table for updates to the board