EXCLUSIVE GREEN HE C.S.I. - R.S.I.

 

 

 

To Purge air from the heating system & boiler 

(Fig. 1.10) 

 

We recommend carrying out the sequence of 
operations below during installation and after 
exceptional maintenance 

 

1. Using a spanner open the manual air vent valve located above the air 

box; the tube supplied with the boiler must be connected to the valve 
to let out the water into a container.

 

2.    Open the manual system filling valve 

 

3.  Switch on the boiler leaving the gas valve closed; 

 

4.  Use the room thermostat or the remote control panel to activate request

 

for heat so that the three-way will turn to heating

 

INSTALLATION “SEALED” (TYPE C)

 

This  boiler  is  a  C-type  appliance  (sealed  chamber)  and  must  be  safely 
connected  to  fume  exhaustion  duct  and  burning  air  suction  duct,  both 
terminating outside; This appliance cannot operate without these ducts.

 

Concentric outlets (Ø 60-100) (Fig. 1.14)

 

Concentric ducts may be placed in the most suitable direction for installation 
requirements but special care must be taken as regards the and the length 
of the Flue.

 

Horizontal

 

                                                                                                                         

 

5.  Activate request for hot water as follows:

 

turn on a tap for 30 seconds every minute so that the three-way cycles 
from heating to domestic hot water and vice versa about ten times    
(here the boiler will go into alarm as it lacks gas and will have to be reset 
each time this happens

6.  Continue the sequence until water only comes out of the manual air vent 

valve; close the manual air vent valve at this point;

 

7.  Make sure the system is at the correct pressure (1- 1.2 bar is ideal);

 

8.  Close the manual system filling valve;

 

9.     Open the gas valve and ignite the boiler

 

 

9 - FUMES EXHAUSTION AND BURNING AIR SUCTION 

 

EXHAUSTION CONFIGURATIONS (Fig. 1.11-1.12)

 

Boiler is homologated for the following exhaustion configurations:

 

B23P-B53P - 

Suction in room and discharge outside

 

C13  - 

Concentric  wall  exhaustion.  Pipes can  separately  start  from  boiler, 

but outlets must be concentric or close enough to be subject to similar wind 
conditions (within 50 cm)

 

C23 - 

Concentric exhaustion in common chimney (suction and exhaustion 

in the same chimney)

 

C33 - 

#ONCENTRIC ROOF EXHAUSTION. /UTLETS LIKE #13

 

C43 - 

Exhaustion and suction in common separate chimneys, but subject 

to similar wind conditions

 

C53 - 

7ALL OR ROOF SEPARATE EXHAUSTION AND SUCTION IN DIFFERENT PRESSURE AREAS.

 

Exhaustion and suction must never be located on opposite walls

 

C63 - 

Exhaustion and suction with separately certified and sold pipes (1856/1)

 

C83 - 

Single or common chimney exhaustion and wall suction

 

C93 

– 

Exhaust on roof (similar to C33) and air

 

Refer to regulations in force for exhaustion of combustion products.

 

Boiler is provided for without fume exhaustion/air suction kit, since forced 
draught sealed chamber accessories can be used, as they better adapt to 
installation characteristics.

 

&OR FUME EXTRACTION AND BURNING AIR RESTORATION IN BOILER, USE ORIGINAL PIPES  OR

 

other EC-certified pipes with equivalent characteristics; check connection is 
correct as shown on instructions fume accessories provided for with. More 
appliances can be connected to a single chimney, provided that all appliances 
are condensing type.

 

“FORCED OPEN” INSTALLATION (TYPE B23P-B53P, intake inside

 

and outlet outside) - Fumes outlet duct Ø 80 mm (Fig. 1.13)

 

The fumes outlet duct can be aimed in the most suitable direction for instal- 
lation needs. To install follow the instructions supplied with the kit.

 

 

In this configuration, the boiler is connected to the Ø 80 mm fumes outlet 

duct by means of a Ø 60-80 mm adaptor.

 

 

In this case, the combustion supporting air is taken from the room    in

 

which the boiler is installed, which must be a suitable and ventilated 
technical room.

 

Non-insulated fumes outlet ducts are potential sources of danger.

 

0ROVISION MUST BE MADE FOR A 1% SLOPE OF THE FUMES OUTLET DUCT TOWARDS

 

the boiler.

 

Vertical

 

 

 

Max linear length concentric

 

duct Ø 60-100 mm

 

Pressure drop for each

 

bend (45°/90°) [m]

 

25 C.S.I.-R.S.I.

 

8,85 m

 

 

1,3 / 1,6

 

35 C.S.I.-R.S.I.

 

8,85 m

 

linear length means without bends,  

Allow 0.5 m per bend in total length calculation. 

 

The Flue outlet pipe MUST SLOPE BY 1% TOWARDS the condensate collector (boiler)- 

 
CAUTION 

Exhaust fume outlets are potential hazards.

 

The boiler automatically adapts ventilation according to the type of 
installation and the length of the duct.

 

       

Do not obstruct or narrow the combustion air inlet duct in any way. 

 

To install follow the instructions supplied with the kit. 

 

 

 
 

.

 

 
 

 

Max length fumes

 

outlet duct Ø 80 mm

 

Pressure drop for each

 

bend (45°/90°) [m]

 

25 C.S.I.-R.S.I.

 

50 m

 

 

1 / 1,5

 

35 C.S.I.-R.S.I.

 

60 m

 

 

Max linear length concentric

 

duct Ø 60-100 mm

 

Pressure drop for each

 

bend (45°/90°) [m]

 

25 C.S.I.-R.S.I.

 

7,85 m

 

 

1,3 / 1,6

 

35 C.S.I.-R.S.I.

 

7,85 m

 

 

Содержание Exclusive GREEN HE C.S.I. 35 kW

Страница 1: ...DEL INSTALADOR Y DEL USUARIO PT MANUAL DO USUARIO E DO INSTALADOR HU TELEPiTOI ES FELHASZNAL6I KEZIKONYV RO MANUAL DE INSTALARE SI UTILIZARE SI NAVODILA ZA VGRADITEV PRIKLJUCITEV IN UPORABO PL INSTRUK...

Страница 2: ...2004 108 EEC Niskonapi ciowe wyroby elektryczne 2006 95 EEC Norma dotyczqca kotU6w kondensacyjnych 677 l w CE lnstrukcja instalacji i uzytkowania 148 Budowa kotUa 172 Obieg hydrauliczny 173 174 Schema...

Страница 3: ...trical devices or equipment such as switches appliances etc should not be used if there is a smell of gas or fumes If there is a gas leak open all the doors and windows to ventilate the area turn off...

Страница 4: ...DE P90 1 In this mode the modulating circulation unit works constantly at maximum speed It is used on plants with a high load loss in which the boiler s head must be used as much as possible in order...

Страница 5: ...articles After installation make sure that all the joints have been made airtight conforming to standard installation practices 7 ELECTRIC CONNECTION To access the electrical connections proceed as fo...

Страница 6: ...conditions C53 7ALL OR ROOF SEPARATE EXHAUSTION AND SUCTION IN DIFFERENT PRESSURE AREAS Exhaustion and suction must never be located on opposite walls C63 Exhaustionandsuctionwithseparatelycertifieda...

Страница 7: ...ic power 7 88 116 88 116 Category II2H3P II2H3P II2H3P II2H3P Supply voltage V Hz 230 50 230 50 230 50 230 50 Protection level IP X5D X5D X5D X5D Chimney losses with burner off on 0 10 2 16 0 08 2 30...

Страница 8: ...n revolutions at slow start revs min 3 700 3 700 Maximum number of fan revolutions revs min 6 000 6 000 Minimum number of fan revolutions revs min 1 200 1 900 EXCLUSIVE GREEN C S I 35 kW Diaphragm num...

Страница 9: ...le 4HE DISPLAY WILL LOOK LIKE IG 2 If the test is unsuccessful the boiler will not work and a 0 will flash on the display In this case contact the Technical Assistance Centre The boiler turns on in th...

Страница 10: ...tion has been made the modification is memorised and the display returns to the delivery temperature read by the probe Working the boiler Adjust the ambient thermostat to the required temperature appr...

Страница 11: ......

Страница 12: ...work at minimum power to increase the water temperature to a safe value 35 The symbol lights up on the display circulator anti block one operating cycle is performed every 24hours Switching off for lo...

Страница 13: ...INUTES THEWORDINGh3 vWILLAPPEARONTHEDISPLAY IG 16 AND THE hFUNCTION SELECTION INDICATORSv will light up in sequence Press button to stop the automatic vent cycle If you have to fill the system several...

Страница 14: ...nfo 5 displays the set heating temperature in reference to the second circuit only if it is connected S A R A function Fig 21 If the winter mode is selected the S A R A Automatic Ambient Adjustment Sy...

Страница 15: ...water gauge If the pressure is insufficient 0 4 bar red area proceed with the filling OPERATIONS DESCRIBED IN THE CHAPTER h ILLING AND EMPTYING THE SYSTEMSv F THE SYSTEM S PRESSURE IS SUFlCIENT o 6 B...

Страница 16: ...perations the select functions button acts as an ENTER confirm button the button acts as an ESCAPE escape button If no confirmation is given within 10 seconds the value is discarded and returns to the...

Страница 17: ...5 30 4 4 2 2 3 4 5 4 o 1 YES 0 31 8 5 4 3 4 0 4 2 CIRCUIT 40 80 45 32 5 4 3 4 0 4 2 CIRCUIT 20 39 25 40 7 4 2 34 4 0 2 4 o 1 54 2 1 41 4 3 0 2 4 2 3 4 53 4 3 4 9 1 42 3 2 5 4 o 1 54 1 43 4 3 0 2 4 2 3...

Страница 18: ...M DELIVERY TEMPERATURE 5 4 3 4 0 4 PARAMETER 44 Enable thermoregulation function The connected external temperature probe combined with PARAMETER 44 provides the following operating modes 84 2 02 4 AN...

Страница 19: ...n phases 4URN THE DOMESTIC HOT WATER SELECTOR TO SEQUENTIALLY SCROLL THE 2 4 3 26 PHASES 1 gas type don t modify this parameter 2 boiler power minor parameter 3 insulation level of building only if ex...

Страница 20: ...rm the value you have set by pressing ENTER XITTHE 2 4 3 26 FUNCTIONBYPRESSING 3 0 4HEBOILERRETURNSTOTHEh v STATUS To reset press the button Disconnect the pressure gauge and tighten the pressure tap...

Страница 21: ...sure the main heat exchanger is clean and free of any residuals or obstruction Check and clean where necessary the condensation trap to make sure it works properly lMPORTANT always switch off the pow...

Страница 22: ...e emissions Qnrisc 35 HE 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 HEATING HEAT CAPACITY K7 Heat capacity curve fan rpm Qnrisc 35 HE 6500 6000 5500 5000 4500 4000 3500 3000 2500 2000 1500 1000...

Страница 23: ...are SI SESTAVNI DELI KOTLA 1 Filling tap C S I 2 Pressuretransducer 3 Discharge valve 4 Three way solenoid valve 5 Safety valve 6 Circulation pump 7 Lower air vent valve 8 Hydrometer 9 Siphon 10 Retur...

Страница 24: ...bi boilers HE C S I EN MULTI WIREDIAGRAM ES ESQUEMA DE CONEXIONES 04 2 4 0 HU T BBVEZET KES RAJZ RO SCHEMA ELECTRICA MULTIFILARA SI ELEKTRI NA SHEMA PL SCHEMAT ELEKTRYCZNY COMBI BOILERS CSI With on de...

Страница 25: ...xternal connections inlow voltage M2 Terminal board supplementary pump connection M3 M6 Terminal board for external connections inhigh voltage M4 Terminal board water tank sensor connection R S I OPE...

Страница 26: ...he connections forthe low voltage functions to the 10 pole low voltage connections terminal board M10 as indicated in the diagram Fit the P O S DHW time clock as shown in the diagram after removing th...

Страница 27: ......

Страница 28: ...m ben RO dimensiuni in mm SI mere v mm PL wymiary w mm C B MB EN A condensate outlet C water gas ES A salida condensado C gas agua PT A sa da condensada C gua g s HU A kondenzvfz elvezetesIC vfz gaz R...

Страница 29: ...EXCLUSIVE GREEN HE C S I R S I 183 F R S I 1 9 C S I R S I C C A A D B F E D F 1 6 1 8 C S I E 1 7 A G F E 27...

Страница 30: ...R POWIETRZA DO SPALANIA Z POMIESZCZENIA 1 14 EN CONCENTRIC DUCT FOR FUMES OUTLET AIR INTAKE ES CONDUCTO CONC NTRICO PARA SALIDA DE HUMOS ENTRADA DE AIRE PT DUTO CONC NTRICO PARA SA DA DE FUMA A ENTRA...

Страница 31: ...T W SPALANIA M B D UGO PRZEWODU ZASYSANIA POWIETRZA m M F EXCLUSIVE GREEN 35 HE M M M F EN M spring F horizontal flap ES Muelle M F aleta horizontal PT mola M aba horizontal F HU M rug6 F vfzszintes z...

Страница 32: ...Registration of this product is required under the terms of warranty Please ensure you complete and return the commissioning declaration registration with this boiler to activate your warranty SERVIC...

Отзывы: