Boiler functions

 

 

Semi-automatic filling

 

The boiler features a semi-automatic filling device which turns on by pressing 
the 

button  when  the  corresponding  symbol 

is  shown  on  the  display 

(&IG. 13).

 

If this condition occurs it means that the system is incorrectly pressurised 
though the boiler will continue to work regularly. Press the circuit filling button 

to start-up the filling sequence.

 

Press the circuit filling button 

a second time to interrupt the filling sequen- 

ce

During  filling,  the  drops  of  the  circuit  filling  symbol  and  the  growing 

pressure value appear on the display in a cascade sequence

.

 

After filling, the  symbol is displayed for a few moments and then turns off

.

 

Note

 

$URING lLLING, THE BOILER DOES NOT PERFORM OTHER FUNCTIONS. &OR EXAMPLE, IF

 

there is a request for domestic hot water, the boiler is unable to provide it 
until filling has finished

.

 

Note

 

If circuit pressure reaches 0.6 bar, the pressure value flashes on the display 
(&IG. 14); IF IT FALLS BELOW A MINIMUM SAFETY VALUE (o.3 BAR), FAULT CODE 41 
APPEARS ON THE DISPLAY (&IG. 15) FOR A CERTAIN TIME, FOLLOWING WHICH, IF THE

 

fault persists, fault code 40 is displayed (see chapter on 

“Troubleshooting”). 

In the event of fault 40, press     to reset and then 

to start filling the circuit. 

After fault 40 has been resolved, the boiler will carry out an automatic vent 
CYCLE LASTING FOR ABOUT 2 MINUTES: THE WORDING h3&v WILL APPEAR ON THE DISPLAY

 

(&IG. 16) AND THE hFUNCTION SELECTION INDICATORSv  will light up in sequence. 

Press button 

to stop the automatic vent cycle.

 

If you have to fill the system several times, contact the Technical Service 
Centre to check whether the heating circuit is watertight (see if there are 
any leaks).

 

 
 

 

 

 

 

 

 

 

 
 
 
 
 

 

Information

 

Press   , THE DISPLAY TURNS OFF AND JUST THE WORD )N&/ APPEARS (&IG. 17). 0RESS

 

the button to view operating information. Press the button again to move 
on to the next piece of information. If the button is not pressed, the system 
automatically exits the function.

 

 
 

 

INF2

 

It is possible to display information, which may be useful for the Technical Assistance Centre, by pressing   the button 

for 10 seconds: the code 

“INF2”

 

appears on the display.

 

 

INF2 list

 

Step

 

Description

 

Display

 

2 digits

 

Display

 

4 digits

 

1

 

Input probe temperature

 

xx

 

01

 

—#

 

2

 

Return probe temperature

 

xx

 

02

 

—#

 

3

 

&IRST SANITARY PROBE TEMPERATURE (*)

 

xx

 

03

 

—#

 

4

 

Not used in this model

 

xx

 

Cond

 

—#

 

5

 

FUMES PROBE TEMPERATURE

 

xx (**)

 

05

 

 

6

 

Second heating system probe temperature

 

xx

 

06

 

—#

 

7

 

Domestic hot water flow rate (***)

 

xx

 

07

 

l/min

 

8

 

Ventilator speed /100

 

xx

 

&!.

 

 

9

 

Not used in this model

 

xx

 

09

 

 

10

 

Not used in this model

 

xx

 

10

 

 

11

 

Exchanger cleaning counter status

 

bH

 

xxxx

 

 

12-19

 

Historic alarm codes

 

xx

 

HIS0-HIS7

 

 

 

Note (*): 

if the SAN probe is faulty or disconnected, in the place of the value “- -” is displayed.

 

(**): 

if the display also shows the dot (.), the temperature of the fumes probe is 100+displayed value

 

(***): 

IF THE mOW RATE IS >1o L/MIN # ! X L/MIN WHERE ! = 1o n " = 11 n # = 12 APPEARS ON THE DISPLAY

 

13

 

14

 

16

 

12 

Содержание Exclusive GREEN HE C.S.I. 35 kW

Страница 1: ...DEL INSTALADOR Y DEL USUARIO PT MANUAL DO USUARIO E DO INSTALADOR HU TELEPiTOI ES FELHASZNAL6I KEZIKONYV RO MANUAL DE INSTALARE SI UTILIZARE SI NAVODILA ZA VGRADITEV PRIKLJUCITEV IN UPORABO PL INSTRUK...

Страница 2: ...2004 108 EEC Niskonapi ciowe wyroby elektryczne 2006 95 EEC Norma dotyczqca kotU6w kondensacyjnych 677 l w CE lnstrukcja instalacji i uzytkowania 148 Budowa kotUa 172 Obieg hydrauliczny 173 174 Schema...

Страница 3: ...trical devices or equipment such as switches appliances etc should not be used if there is a smell of gas or fumes If there is a gas leak open all the doors and windows to ventilate the area turn off...

Страница 4: ...DE P90 1 In this mode the modulating circulation unit works constantly at maximum speed It is used on plants with a high load loss in which the boiler s head must be used as much as possible in order...

Страница 5: ...articles After installation make sure that all the joints have been made airtight conforming to standard installation practices 7 ELECTRIC CONNECTION To access the electrical connections proceed as fo...

Страница 6: ...conditions C53 7ALL OR ROOF SEPARATE EXHAUSTION AND SUCTION IN DIFFERENT PRESSURE AREAS Exhaustion and suction must never be located on opposite walls C63 Exhaustionandsuctionwithseparatelycertifieda...

Страница 7: ...ic power 7 88 116 88 116 Category II2H3P II2H3P II2H3P II2H3P Supply voltage V Hz 230 50 230 50 230 50 230 50 Protection level IP X5D X5D X5D X5D Chimney losses with burner off on 0 10 2 16 0 08 2 30...

Страница 8: ...n revolutions at slow start revs min 3 700 3 700 Maximum number of fan revolutions revs min 6 000 6 000 Minimum number of fan revolutions revs min 1 200 1 900 EXCLUSIVE GREEN C S I 35 kW Diaphragm num...

Страница 9: ...le 4HE DISPLAY WILL LOOK LIKE IG 2 If the test is unsuccessful the boiler will not work and a 0 will flash on the display In this case contact the Technical Assistance Centre The boiler turns on in th...

Страница 10: ...tion has been made the modification is memorised and the display returns to the delivery temperature read by the probe Working the boiler Adjust the ambient thermostat to the required temperature appr...

Страница 11: ......

Страница 12: ...work at minimum power to increase the water temperature to a safe value 35 The symbol lights up on the display circulator anti block one operating cycle is performed every 24hours Switching off for lo...

Страница 13: ...INUTES THEWORDINGh3 vWILLAPPEARONTHEDISPLAY IG 16 AND THE hFUNCTION SELECTION INDICATORSv will light up in sequence Press button to stop the automatic vent cycle If you have to fill the system several...

Страница 14: ...nfo 5 displays the set heating temperature in reference to the second circuit only if it is connected S A R A function Fig 21 If the winter mode is selected the S A R A Automatic Ambient Adjustment Sy...

Страница 15: ...water gauge If the pressure is insufficient 0 4 bar red area proceed with the filling OPERATIONS DESCRIBED IN THE CHAPTER h ILLING AND EMPTYING THE SYSTEMSv F THE SYSTEM S PRESSURE IS SUFlCIENT o 6 B...

Страница 16: ...perations the select functions button acts as an ENTER confirm button the button acts as an ESCAPE escape button If no confirmation is given within 10 seconds the value is discarded and returns to the...

Страница 17: ...5 30 4 4 2 2 3 4 5 4 o 1 YES 0 31 8 5 4 3 4 0 4 2 CIRCUIT 40 80 45 32 5 4 3 4 0 4 2 CIRCUIT 20 39 25 40 7 4 2 34 4 0 2 4 o 1 54 2 1 41 4 3 0 2 4 2 3 4 53 4 3 4 9 1 42 3 2 5 4 o 1 54 1 43 4 3 0 2 4 2 3...

Страница 18: ...M DELIVERY TEMPERATURE 5 4 3 4 0 4 PARAMETER 44 Enable thermoregulation function The connected external temperature probe combined with PARAMETER 44 provides the following operating modes 84 2 02 4 AN...

Страница 19: ...n phases 4URN THE DOMESTIC HOT WATER SELECTOR TO SEQUENTIALLY SCROLL THE 2 4 3 26 PHASES 1 gas type don t modify this parameter 2 boiler power minor parameter 3 insulation level of building only if ex...

Страница 20: ...rm the value you have set by pressing ENTER XITTHE 2 4 3 26 FUNCTIONBYPRESSING 3 0 4HEBOILERRETURNSTOTHEh v STATUS To reset press the button Disconnect the pressure gauge and tighten the pressure tap...

Страница 21: ...sure the main heat exchanger is clean and free of any residuals or obstruction Check and clean where necessary the condensation trap to make sure it works properly lMPORTANT always switch off the pow...

Страница 22: ...e emissions Qnrisc 35 HE 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 HEATING HEAT CAPACITY K7 Heat capacity curve fan rpm Qnrisc 35 HE 6500 6000 5500 5000 4500 4000 3500 3000 2500 2000 1500 1000...

Страница 23: ...are SI SESTAVNI DELI KOTLA 1 Filling tap C S I 2 Pressuretransducer 3 Discharge valve 4 Three way solenoid valve 5 Safety valve 6 Circulation pump 7 Lower air vent valve 8 Hydrometer 9 Siphon 10 Retur...

Страница 24: ...bi boilers HE C S I EN MULTI WIREDIAGRAM ES ESQUEMA DE CONEXIONES 04 2 4 0 HU T BBVEZET KES RAJZ RO SCHEMA ELECTRICA MULTIFILARA SI ELEKTRI NA SHEMA PL SCHEMAT ELEKTRYCZNY COMBI BOILERS CSI With on de...

Страница 25: ...xternal connections inlow voltage M2 Terminal board supplementary pump connection M3 M6 Terminal board for external connections inhigh voltage M4 Terminal board water tank sensor connection R S I OPE...

Страница 26: ...he connections forthe low voltage functions to the 10 pole low voltage connections terminal board M10 as indicated in the diagram Fit the P O S DHW time clock as shown in the diagram after removing th...

Страница 27: ......

Страница 28: ...m ben RO dimensiuni in mm SI mere v mm PL wymiary w mm C B MB EN A condensate outlet C water gas ES A salida condensado C gas agua PT A sa da condensada C gua g s HU A kondenzvfz elvezetesIC vfz gaz R...

Страница 29: ...EXCLUSIVE GREEN HE C S I R S I 183 F R S I 1 9 C S I R S I C C A A D B F E D F 1 6 1 8 C S I E 1 7 A G F E 27...

Страница 30: ...R POWIETRZA DO SPALANIA Z POMIESZCZENIA 1 14 EN CONCENTRIC DUCT FOR FUMES OUTLET AIR INTAKE ES CONDUCTO CONC NTRICO PARA SALIDA DE HUMOS ENTRADA DE AIRE PT DUTO CONC NTRICO PARA SA DA DE FUMA A ENTRA...

Страница 31: ...T W SPALANIA M B D UGO PRZEWODU ZASYSANIA POWIETRZA m M F EXCLUSIVE GREEN 35 HE M M M F EN M spring F horizontal flap ES Muelle M F aleta horizontal PT mola M aba horizontal F HU M rug6 F vfzszintes z...

Страница 32: ...Registration of this product is required under the terms of warranty Please ensure you complete and return the commissioning declaration registration with this boiler to activate your warranty SERVIC...

Отзывы: