Boiler functions
Semi-automatic filling
The boiler features a semi-automatic filling device which turns on by pressing
the
button when the corresponding symbol
is shown on the display
(&IG. 13).
If this condition occurs it means that the system is incorrectly pressurised
though the boiler will continue to work regularly. Press the circuit filling button
to start-up the filling sequence.
Press the circuit filling button
a second time to interrupt the filling sequen-
ce
.
During filling, the drops of the circuit filling symbol and the growing
pressure value appear on the display in a cascade sequence
.
After filling, the symbol is displayed for a few moments and then turns off
.
Note
$URING lLLING, THE BOILER DOES NOT PERFORM OTHER FUNCTIONS. &OR EXAMPLE, IF
there is a request for domestic hot water, the boiler is unable to provide it
until filling has finished
.
Note
If circuit pressure reaches 0.6 bar, the pressure value flashes on the display
(&IG. 14); IF IT FALLS BELOW A MINIMUM SAFETY VALUE (o.3 BAR), FAULT CODE 41
APPEARS ON THE DISPLAY (&IG. 15) FOR A CERTAIN TIME, FOLLOWING WHICH, IF THE
fault persists, fault code 40 is displayed (see chapter on
“Troubleshooting”).
In the event of fault 40, press to reset and then
to start filling the circuit.
After fault 40 has been resolved, the boiler will carry out an automatic vent
CYCLE LASTING FOR ABOUT 2 MINUTES: THE WORDING h3&v WILL APPEAR ON THE DISPLAY
(&IG. 16) AND THE hFUNCTION SELECTION INDICATORSv will light up in sequence.
Press button
to stop the automatic vent cycle.
If you have to fill the system several times, contact the Technical Service
Centre to check whether the heating circuit is watertight (see if there are
any leaks).
Information
Press , THE DISPLAY TURNS OFF AND JUST THE WORD )N&/ APPEARS (&IG. 17). 0RESS
the button to view operating information. Press the button again to move
on to the next piece of information. If the button is not pressed, the system
automatically exits the function.
INF2
It is possible to display information, which may be useful for the Technical Assistance Centre, by pressing the button
for 10 seconds: the code
“INF2”
appears on the display.
INF2 list
Step
Description
Display
2 digits
Display
4 digits
1
Input probe temperature
xx
01
—#
2
Return probe temperature
xx
02
—#
3
&IRST SANITARY PROBE TEMPERATURE (*)
xx
03
—#
4
Not used in this model
xx
Cond
—#
5
FUMES PROBE TEMPERATURE
xx (**)
05
6
Second heating system probe temperature
xx
06
—#
7
Domestic hot water flow rate (***)
xx
07
l/min
8
Ventilator speed /100
xx
&!.
9
Not used in this model
xx
09
10
Not used in this model
xx
10
11
Exchanger cleaning counter status
bH
xxxx
12-19
Historic alarm codes
xx
HIS0-HIS7
Note (*):
if the SAN probe is faulty or disconnected, in the place of the value “- -” is displayed.
(**):
if the display also shows the dot (.), the temperature of the fumes probe is 100+displayed value
(***):
IF THE mOW RATE IS >1o L/MIN # ! X L/MIN WHERE ! = 1o n " = 11 n # = 12 APPEARS ON THE DISPLAY
13
14
16
12