27
ENGLISH
PLANT
PLANT
- select the type of domestic hot water =FLUX SWITCH.
PLANT
FLUX SWITCH
FLUX METER
- Once the guided procedure is finished, the REC10 will go to the initial
screen.
Continue with the configuration as follows:
- access technical parameters as explained in section “4.1 Access to
technical parameters”,
using the password SERVICE
- With the
“up”
and
“down”
keys select PARAMETERS, confirming the
selection ok
- next change the following parameters:
ENABLE FILLING: set to 1.
Then proceed with the reprogramming of the boiler, carrying out the
operations described in the section
“5.2 Programming the boiler”
.
5.21
REPLACING THE REC10
(Control interface)
Configuration operations need to be carried out by
a professionally
qualified engineer
When replacing the REC10 MASTER, at the subsequent restart it displays
an initial screen with the firmware revision.
Pressing
“ok”
starts a guided procedure for configuring the system, see
section “5.20 System configuration”. Follow the procedure and carry out the
FROM AKM type of configuration.
MULTI ZONE CONTROLLER
REC10 V01.26
PRESS ANY KEY
TO CONTINUE
SELECT THE TYPE
OF CONFIGURATION
FROM AKM
NEW
5.22 REPLACING THE
AKM01
(Main PCB board)
Configuration
operations should be carried out by a professionally qualified
engineer. The system continually carries out a consistency control
between the saved configuration data on the AKM01 PCB board and those
saved in the REC10; therefore, when replacing the AKM01 electronic board,
it can happen that the system detects an inconsistency between the data
saved on the AKM01 and that in the REC10. In this case, the latter will ask
the user which of the two configurations is to be considered valid; selecting
to recover the configuration from the REC10 itself it is possible to avoid
reconfiguring the machine:
- With the
“up”
and
“down”
keys select REC10, confirming the selection.
5.23
Parameters combustion check
Although the parameters of the combustion control system ACC (Activate
Combustion Control) are preset in the factory, the simultaneous
replacement of both electronic boards (AKM and REC 10 MASTER) could
make necessary the re-programming these parameters
.
- Access technical parameters as explained in section “4.1 Access to
technical parameters” setting the password SERVICE
- With the
“up”
and
“down”
keys select COMBUSTION CHECK,
confirming the selection
TECHNICAL
PARAMETERS
VENT CYCLE
EXHAUST PROBE RESET
ALARM HISTORY
COMBUSTION CHECK
SERVICE
- Select the GAS TYPE
- Set this parameter depending on the type of gas of the boiler. The values
for this parameter are NG = NATURAL GAS - LPG = LPG
COMBUSTION CHECK
GAS TYPE
BOILER TYPE
COMBUSTION OFFSET
SERVICE
- Select BOILER TYPE
- Set this parameter depending on the type of boiler as shown in the table
BOILER TYPE
A
B
C
SERVICE
SELECT THE TYPE
OF CONFIGURATION
FROM AKM
REC10
BOILER TYPE
EXCLUSIVE 25C
A
EXCLUSIVE 30C
B
EXCLUSIVE 35C
C