Beretta CIAO AT Скачать руководство пользователя страница 9

9

ENGLISH

b

In this case, the anti-freeze and anti-blocking systems are deactivated.

b

Drain the heating and domestic water system if there is any risk of freezing.

4.8 

Setting the thermoregulation

Thermoregulation only works with the outdoor sensor connected (an optional accessory) 

therefore once installed, connect it to the special connections provided on the boiler 

terminal board (see wiring diagram); at this point set the parameter P13 different from 0 

after evaluating the value to be set, explanation follows.

This enables the THERMOREGULATION function.

In this type of operation, the CH setpoint is calculated according to the outdoor temperature 

(t ext) and the Kd factor, which depends on the value set in parameter P13 - see graph.

Choice of the compensation curve

-

Choose the thermoregulation curve that best matches your installation needs - see graph 

1 - taking into account the outdoor temperature and the CH delivery temperature.

-

Using the curve of graph 1, 

fi

 nd the 

Kd

 value.

-

Having obtained the Kd value, use graph 2 to determine the correspondence with the

P13

 value.

Enter the value obtained in parameter P13, referring to paragraph "4.11 Parameter access 

procedure (tS)". The CH compensation curve maintains a theoretical room temperature of 

20 °C for outdoor temperatures b20 °C and –20 °C. 

Above and below this range the CH setpoint is limited to the maximum and minimum by the 

value set in the parameter table.

If the room temperature is lower than the desired value, it is advisable to create a higher 
order curve and vice versa. 

4.9  

Additional 

functions

PRE-HEATING (FASTER HOT WATER): 

This function keeps the water in the domestic hot water exchanger hot, to reduce standby 

times when a request is made. 

-

By pressing the RESET and CH+ keys for more than 3 seconds it is possible to enable

or disable the preheating function. At the beginning of the function the display shows FH 

and the pump starts immediately.

RESET

+

-

RESET

-

The display shows FH and On alternately

-

Press RESET and CH+ to disable the function.

The preheating function is not available in the following cases:

-

following a lockout caused by an anomaly, for a period of 10 seconds

-

if a heat demand is in progress

-

during post circulation of the pump.

b

By activating the function, the absolute thermostats are enabled at the same time.

Air vent

The circulator is cyclically switched on at maximum speed for 10 seconds and switched off 
for 10 seconds to remove air contained in the circuit. During this function, the display shows 
F33 and heat demand is disabled for 120 seconds.

This function can be activated under the following conditions:

-

after manual reset following anomaly A02

-

when the CH water pressure is restored to normal level after anomaly A04

-

after anomaly A18 (circulation control) has been reset. 

This function can be deactivated by pressing the RESET button for 5 seconds.

4.10 Installer/con

fi

 guration mode

By pressing the RESET button for 10 seconds, it is possible to access the Installer/
Con

fi

 guration mode.

b

The operation is not allowed with the boiler in the OF state.

"tS" begins to 

fl

 ash on the display.

By pressing the CH+ or CH- buttons it is possible to navigate the following menus.

tS

Parameter input 

In

Info

Hi

Alarms log

rE

Reset alarms

4.11  Parameter access procedure (tS)

-

Press RESET for 10 seconds, "tS" begins to 

fl

 ash on the display.

-

Press MODE to con

fi

 rm entry to the parameters menu. The display shows the 

fi

 rst pa-

rameter, P00.

MODE

MODE

-

Use the CH+ and CH- keys to scroll through the parameter list, once you have made a

choice press MODE to con

fi

 rm.

+

-

MODE

MODE

-

use the DHW+ and DHW- buttons to adjust the parameter value, then press MODE to
save. The value 

fl

 ashes twice to con

fi

 rm the save action.

+

-

MODE

MODE

By pressing the RESET button for 1 second it is possible to exit the parameter modi

fi

 cation 

Содержание CIAO AT

Страница 1: ...Installer and user manual CIAO AT EN INSTALLER AND USER MANUAL PL INSTRUKCJA OBS UGI I INSTALACJI KOT A GAZOWEGO...

Страница 2: ...ained Instrukcja instalacji i u ytkowania 3 21 Elementy funkcyjne kot a 78 Schemat elektryczny 79 Grupa hydrauliczna 80 Wysoko podnoszenia pompy obiegowej 82 Kocio CIAO AT spe nia podstawowe wymagania...

Страница 3: ...the appliance from the main power supply by turning the system s main switch to OFF by setting the boiler to OFF a Do not modify the safety or adjustment devices without the manufacturer s authorisat...

Страница 4: ...for condensation exhaust connection This product is designed to prevent the escape of gaseous products of combustion through the condensation drain pipe with which it is equipped this is obtained by...

Страница 5: ...rticles b Once the appliance has been installed check the connections are sealed according to current installation regulations 3 11 Releasing the circulator Press the MODE button to select the OFF sta...

Страница 6: ...temperature adjustment increases the CH value decreases the CH value Domestic hot water DHW temperature adjustment increases the DHW value decreases the DHW value MODE Button for selecting summer wint...

Страница 7: ...peat this operation during routine and extraordinary maintenance operations MAX 50 mm 4 3 Operating modes Repeatedly pressing the MODE button displays in sequence the possible operating modes OFF WINT...

Страница 8: ...w supply voltage abnormal mains frequency A80 Fan defective or not connected fan wiring fault A34 CH NTC sensor over temperature A74 Fault A04 Low water pressure together with the error code the symbo...

Страница 9: ...ble or disable the preheating function At the beginning of the function the display shows FH and the pump starts immediately RESET RESET The display shows FH and On alternately Press RESET and CH to d...

Страница 10: ...applicable C 5 3 9 Not applicable to this model P21 Not applicable 0 0 1 0 disabled P22 if P21 1 Not applicable rpm x10 140 140 180 if P01 0 G20 1000 140 if P01 1 G31 P23 if P21 1 Not applicable rpm x...

Страница 11: ...em the procedure can be followed in DHW mode by turning on at least one hot water tap after activating the function as explained previously making sure that the DHW setpoint is set to the maximum valu...

Страница 12: ...em s general switch close the fuel and water taps of the heating and domestic hot water system To ensure that product characteristics and efficiency remain intact and compliance with current regulatio...

Страница 13: ...lockout symbol 6 2 Operating modes Repeatedly pressing the MODE button displays in sequence the possible operating modes OFF WINTER SUMMER CH ONLY DO NOT SET THIS CONFIGURATION OFF MODE MODE WINTER MO...

Страница 14: ...ture C 20 70 4 Burner output 0 100 5 Not used KOhm 0 99 6 Fan speed 0 3 0 Off 1 Min 2 Med 3 Max 7 Interval remaining before mainte nance 52 weeks To exit the Info menu press RESET for 1 second or pres...

Страница 15: ...II2H3P Voltage supply V Hz 230 50 Protection level IP X5D Losses at the flue with burner off burner on 0 12 3 78 Heating operation Pressure Maximum temperature bar C 3 90 Minimum pressure for standar...

Страница 16: ...in wall diameter mm 130 Twin flue gas outlet pipes Diameter mm 80 Maximum length m 14 14 Losses for a 45 90 bend m 1 1 5 Forced open installation B22P B52P Diameter mm 80 Maximum length m 14 Nox clas...

Страница 17: ...me P4 24 0 kW At 30 of rated heat output and low temperature regime P1 7 6 kW Useful efficiency At rated heat output and high temperature regime 4 86 1 At 30 of rated heat output and low temperature r...

Страница 18: ...personelem a Nie wolno dotyka urz dzenia b d c boso lub gdy cz ci cia a s mokre a Nie wolno wykonywa adnych rob t technicznych lub czyszczenia je eli urz dzenie nie zosta o od czone od sieci zasilani...

Страница 19: ...kocio nie przechowywa substancji atwopalnych atwo nagrzewaj ce si ciany np drewniane musz by pokryte w a ciw izolacj ochronn 3 6 Instrukcjapod czeniaprzewoduodprowadzeniakondensatu Produkt ten zosta z...

Страница 20: ...bokr tem jak pokazano na rys 2 W o y na miejsce korek i nacisn przycisk MODE tryb aby wybra dany tryb pracy b Aby unikn uszkodzenia element w podczas tej czynno ci nale y zachowywa najwy sz ostro no r...

Страница 21: ...C O zmniejszanie warto ci C O Regulacja temperatury ciep ej wody u ytkowej C W U zwi kszanie warto ci C W U zmniejszanie warto ci C W U MODE Przycisk wyboru funkcji LATO ZIMA WY CZONY Wej cie do trybu...

Страница 22: ...powoduje wy wietlanie dost pnych tryb w pracy WY CZONY OFF ZIMA LATO WY CZNIE C O NIE U YWA MODE MODE OFF WY MODE MODE ZIMA MODE MODE LATO Zima Aby aktywowa funkcj ZIMA nale y wciska przycisk MODE do...

Страница 23: ...ci nienia w uk adzie 1 i 1 5 bar ci g a obecno kodu b du A04 mo e by spowodowana interwencj ogranicznika ci nienia kondensatu zablokowany syfon lub odp yw kondensatu W takim przypadku konieczne jest...

Страница 24: ...podgrzewania jest dost pna w nast puj cych przypadkach po zablokowaniu spowodowanym nieprawid owo ci przez 10 sekund przy trwaj cym zapotrzebowaniu na ogrzewania podczas pracy pompy w trybie obiegu k...

Страница 25: ...1 P23 je eli P21 1 Nie dotyczy obr min x 10 100 100 140 je eli P01 0 G20 100 je eli P01 1 G31 P24 je eli P21 1 Nie dotyczy obr min x 10 110 110 140 je eli P01 0 G20 115 je eli P01 1 G31 b Parametry ko...

Страница 26: ...analiza tora spalin i ponownie za o y zdemontowane wcze niej elementy 4 15 Przezbrajanie na inny rodzaj gazu Przezbrojenie kot a z jednego rodzaju gazu na inny mo na przeprowadzi nawet po zainstalowa...

Страница 27: ...przepisami urz dzenie musi by poddawane systematycznym kontrolom w regularnych odst pach czasu Podczas konserwacji przestrzega instrukcji podanych w rozdziale 1 OSTRZE ENIA I BEZPIECZE STWO Zazwyczaj...

Страница 28: ...olejno przycisku MODE umo liwia wy wietlanie dost pnych tryb w pracy WY CZONY OFF ZIMA LATO WY CZNIE C O NIE U YWA OFF WY MODE MODE ZIMA MODE MODE LATO Zima Aby aktywowa funkcj ZIMA nale y wciska przy...

Страница 29: ...c palnika 0 100 5 Parametr nieu ywany kOhm 0 99 6 Pr dko wentylatora 0 3 0 Wy 1 Min 2 r 3 Maks 7 Czas pozosta y do konserwacji 52 tygodnie Aby wyj z menu informacji nacisn przycisk RESET na 1 sekund l...

Страница 30: ...eznaczenia II2E3P PL Napi cie zasilania V Hz 230 50 Poziom ochrony przeciwpora eniowej IP X5D Strata kominowa przy wy czonym palniku w czonym palniku 0 12 3 78 FUNKCJA C O Maksymalne ci nienie Tempera...

Страница 31: ...m 80 80 CO2 5 0 5 5 NOx b w poni ej p p m 20 25 Temperatura spalin C 60 62 U redniona warto z zakresu pracy w r nych warunkach Pr ba wykonana z koncentrycznym przewodem koncentrycznym 60 100 o d ugo...

Страница 32: ...o energetyczna ogrzewania pomieszcze s 87 Wytworzone ciep o u ytkowe Przy znamionowej mocy cieplnej i w systemie wysokotemperaturowym P4 24 0 kW Przy znamionowej mocy cieplnej na poziomie 30 i w syste...

Страница 33: ...way electric valve 26 Pressure gauge 27 Domestic hot water NTC sensor 16 27 12 PL Budowa kot a AF Wej cie z w AC Wyj cie c w u M Zasilanie c o R Powr t c o 1 Zaw r nape niania 2 Zaw r zwrotny 3 Zaw r...

Страница 34: ...Domestic hot water NTC sensor 7 Water pressure switch 8 Domestic hot water heat exchanger 9 Limit thermostat 10 Primary NTC sensor 11 Post exchanger thermal fuse 12 Capacitor 13 Primary heat exchange...

Страница 35: ...y Verde Zielony g v to zielony A Zworka TA OT styk bezpotencja owy BRT14 P yta steruj ca z wy wietlaczem cyfrowym i zintegrowanym transformatorem zap onowym F Bezpiecznik 3 15A F X1 X5 Z cza TR1 Trans...

Страница 36: ...36 8 EN Measured in mm PL Wymiary w mm 5 6 EN Indoor installation PL Monta wewn trz 7 9 50 50 93 5 65 47 75 73 75 65 60 1 4 0 M AC G AF R water gas woda gaz dimensions in mm wymiary w mm...

Страница 37: ...P 12 A B A B M4 S E t arancione arancione rosa rosa TA OT Contatto privo di tensione UWAGA Elementy systemu kominowego wraz ze schematami znajduj si w Katalogu Produkt w Beretta UWAGA Elementy systemu...

Страница 38: ...d11 B C A P13 Kd D 14 A B C D EN Graph 1 thermoregulation graph for main area with temperature range 35 80 C CH delivery temperature C Outdoor temperature C Graph 2 PL Wykres 1 wykres regulacji pogodo...

Страница 39: ...20176972 03 21 Ed 1 EN RANGE RATED EN 15502 The max CH input of this boiler has been adjusted to_____ kW equivalent to _____ rpm max CH fan speed Date___ ____ ____ Signature _____________________ Boi...

Отзывы: