Beretta CIAO AT Скачать руководство пользователя страница 6

6

0

5

10

15

20

25

30

0

5

10

15

20

25

30

35

Air suction pipe length (m)

Flue gas pipe length (m)

3.13   Filling and emptying the system

Once the hydraulic connections have been carried out, you can 

fi

 ll the heating system.

FILLING the heating system

This procedure must be carried out when the system is cold and the boiler is OFF, and 

consists of the following operations:

-

open the automatic air vent valve cap (

A

) by two or three turns

-

make sure the cold water inlet tap is open

B

C

A

-

open the 

fi

 lling tap (

B

) until the pressure indicated by the water pressure gauge is be-

tween 1 and 1.5 bar. Once 

fi

 lling is complete, close the 

fi

 lling tap. 

b

The safety valve outlet (

C

) must be connected to a suitable collection system. The 

manufacturer is not responsible for possible damage due to safety valve operation.

NOTE:

 The boiler has an ef

fi

 cient air separator so no manual air venting intervention is 

needed.

NOTE:

 The burner switches on only if the air relief phase is 

fi

 nished.

EMPTYING the heating system

To empty the system, proceed as follows:

-

switch off the boiler

-

connect the hose supplied as standard to the boiler drain valve (

C

)

-

loosen the boiler drain valve (

C

)

-

open the air vent valve to allow continuous air venting

-

drain the lowest points of the system.

3.14 

  Control  panel

RESET

+

+

-

-

MODE

Button functions

Holding down the CH-, CH+, DHW- and DHW+ buttons scrolls the values, while a single press 
displays them one by one.

+

-

Heating water (CH) temperature adjustment:

+ increases the CH+ value

- decreases the CH- value

+

-

Domestic hot water (DHW) temperature 

adjustment:

+ increases the DHW+ value

- decreases the DHW- value

MODE

Button for selecting summer/winter mode, CH 

only and OFF.

Enter Functions mode

RESET

Button for resetting the non-volatile alarm status 

(press <1 sec.).

Enable/disable INSTALLER/BOILER 

CONFIGURATION mode (press 10 sec.).

Exit Functions mode

RESET

MODE

By pressing the RESET and MODE buttons 

simultaneously for 5 seconds, it is possible to 

enable/disable the combustion analysis mode 

(see "4.14 Combustion analysis").

RESET

+

+

-

By pressing the RESET button and the CH+ 
button (> 3 seconds) in normal operation (NO 
lockout), it is possible to enable/disable the 
preheating mode. 

MODE

 + 

+

-

Pressing the CH+ and MODE buttons 
simultaneously for 5 seconds takes you into the 
adjustment procedure

Access for SERVICE

The icon indicates

connection to an OT device

entry into the info menu

CH active, 

fl

 ashes if CH demand is in progress 

DHW function active, 

fl

 ashes if DHW demand in progress

presence of 

fl

 ame, in case of 

fl

 ame lockout the icon shows 

need for maintenance (see "4.18 Maintenance indicator (

)")

modulation range,    = 0 to 50%,
                                        = 51% to 100%

need for 

fi

 lling

CH water temperature 

DHW temperature sampling

OFF mode

parameter display. See paragraph "4.11 Parameter access 
procedure (tS)"

fault display. See paragraph "4.5 Warning lights and faults"

display current function. See paragraph "4.9 Additional functions"

display alarms log. See paragraph "4.13 Alarms log"

• t3: pause time between each ignition attempt
• t4: pause time after alarm reset less than 30 sec.
• t5: pause time after alarm reset more than 30 sec.

Содержание CIAO AT

Страница 1: ...Installer and user manual CIAO AT EN INSTALLER AND USER MANUAL PL INSTRUKCJA OBS UGI I INSTALACJI KOT A GAZOWEGO...

Страница 2: ...ained Instrukcja instalacji i u ytkowania 3 21 Elementy funkcyjne kot a 78 Schemat elektryczny 79 Grupa hydrauliczna 80 Wysoko podnoszenia pompy obiegowej 82 Kocio CIAO AT spe nia podstawowe wymagania...

Страница 3: ...the appliance from the main power supply by turning the system s main switch to OFF by setting the boiler to OFF a Do not modify the safety or adjustment devices without the manufacturer s authorisat...

Страница 4: ...for condensation exhaust connection This product is designed to prevent the escape of gaseous products of combustion through the condensation drain pipe with which it is equipped this is obtained by...

Страница 5: ...rticles b Once the appliance has been installed check the connections are sealed according to current installation regulations 3 11 Releasing the circulator Press the MODE button to select the OFF sta...

Страница 6: ...temperature adjustment increases the CH value decreases the CH value Domestic hot water DHW temperature adjustment increases the DHW value decreases the DHW value MODE Button for selecting summer wint...

Страница 7: ...peat this operation during routine and extraordinary maintenance operations MAX 50 mm 4 3 Operating modes Repeatedly pressing the MODE button displays in sequence the possible operating modes OFF WINT...

Страница 8: ...w supply voltage abnormal mains frequency A80 Fan defective or not connected fan wiring fault A34 CH NTC sensor over temperature A74 Fault A04 Low water pressure together with the error code the symbo...

Страница 9: ...ble or disable the preheating function At the beginning of the function the display shows FH and the pump starts immediately RESET RESET The display shows FH and On alternately Press RESET and CH to d...

Страница 10: ...applicable C 5 3 9 Not applicable to this model P21 Not applicable 0 0 1 0 disabled P22 if P21 1 Not applicable rpm x10 140 140 180 if P01 0 G20 1000 140 if P01 1 G31 P23 if P21 1 Not applicable rpm x...

Страница 11: ...em the procedure can be followed in DHW mode by turning on at least one hot water tap after activating the function as explained previously making sure that the DHW setpoint is set to the maximum valu...

Страница 12: ...em s general switch close the fuel and water taps of the heating and domestic hot water system To ensure that product characteristics and efficiency remain intact and compliance with current regulatio...

Страница 13: ...lockout symbol 6 2 Operating modes Repeatedly pressing the MODE button displays in sequence the possible operating modes OFF WINTER SUMMER CH ONLY DO NOT SET THIS CONFIGURATION OFF MODE MODE WINTER MO...

Страница 14: ...ture C 20 70 4 Burner output 0 100 5 Not used KOhm 0 99 6 Fan speed 0 3 0 Off 1 Min 2 Med 3 Max 7 Interval remaining before mainte nance 52 weeks To exit the Info menu press RESET for 1 second or pres...

Страница 15: ...II2H3P Voltage supply V Hz 230 50 Protection level IP X5D Losses at the flue with burner off burner on 0 12 3 78 Heating operation Pressure Maximum temperature bar C 3 90 Minimum pressure for standar...

Страница 16: ...in wall diameter mm 130 Twin flue gas outlet pipes Diameter mm 80 Maximum length m 14 14 Losses for a 45 90 bend m 1 1 5 Forced open installation B22P B52P Diameter mm 80 Maximum length m 14 Nox clas...

Страница 17: ...me P4 24 0 kW At 30 of rated heat output and low temperature regime P1 7 6 kW Useful efficiency At rated heat output and high temperature regime 4 86 1 At 30 of rated heat output and low temperature r...

Страница 18: ...personelem a Nie wolno dotyka urz dzenia b d c boso lub gdy cz ci cia a s mokre a Nie wolno wykonywa adnych rob t technicznych lub czyszczenia je eli urz dzenie nie zosta o od czone od sieci zasilani...

Страница 19: ...kocio nie przechowywa substancji atwopalnych atwo nagrzewaj ce si ciany np drewniane musz by pokryte w a ciw izolacj ochronn 3 6 Instrukcjapod czeniaprzewoduodprowadzeniakondensatu Produkt ten zosta z...

Страница 20: ...bokr tem jak pokazano na rys 2 W o y na miejsce korek i nacisn przycisk MODE tryb aby wybra dany tryb pracy b Aby unikn uszkodzenia element w podczas tej czynno ci nale y zachowywa najwy sz ostro no r...

Страница 21: ...C O zmniejszanie warto ci C O Regulacja temperatury ciep ej wody u ytkowej C W U zwi kszanie warto ci C W U zmniejszanie warto ci C W U MODE Przycisk wyboru funkcji LATO ZIMA WY CZONY Wej cie do trybu...

Страница 22: ...powoduje wy wietlanie dost pnych tryb w pracy WY CZONY OFF ZIMA LATO WY CZNIE C O NIE U YWA MODE MODE OFF WY MODE MODE ZIMA MODE MODE LATO Zima Aby aktywowa funkcj ZIMA nale y wciska przycisk MODE do...

Страница 23: ...ci nienia w uk adzie 1 i 1 5 bar ci g a obecno kodu b du A04 mo e by spowodowana interwencj ogranicznika ci nienia kondensatu zablokowany syfon lub odp yw kondensatu W takim przypadku konieczne jest...

Страница 24: ...podgrzewania jest dost pna w nast puj cych przypadkach po zablokowaniu spowodowanym nieprawid owo ci przez 10 sekund przy trwaj cym zapotrzebowaniu na ogrzewania podczas pracy pompy w trybie obiegu k...

Страница 25: ...1 P23 je eli P21 1 Nie dotyczy obr min x 10 100 100 140 je eli P01 0 G20 100 je eli P01 1 G31 P24 je eli P21 1 Nie dotyczy obr min x 10 110 110 140 je eli P01 0 G20 115 je eli P01 1 G31 b Parametry ko...

Страница 26: ...analiza tora spalin i ponownie za o y zdemontowane wcze niej elementy 4 15 Przezbrajanie na inny rodzaj gazu Przezbrojenie kot a z jednego rodzaju gazu na inny mo na przeprowadzi nawet po zainstalowa...

Страница 27: ...przepisami urz dzenie musi by poddawane systematycznym kontrolom w regularnych odst pach czasu Podczas konserwacji przestrzega instrukcji podanych w rozdziale 1 OSTRZE ENIA I BEZPIECZE STWO Zazwyczaj...

Страница 28: ...olejno przycisku MODE umo liwia wy wietlanie dost pnych tryb w pracy WY CZONY OFF ZIMA LATO WY CZNIE C O NIE U YWA OFF WY MODE MODE ZIMA MODE MODE LATO Zima Aby aktywowa funkcj ZIMA nale y wciska przy...

Страница 29: ...c palnika 0 100 5 Parametr nieu ywany kOhm 0 99 6 Pr dko wentylatora 0 3 0 Wy 1 Min 2 r 3 Maks 7 Czas pozosta y do konserwacji 52 tygodnie Aby wyj z menu informacji nacisn przycisk RESET na 1 sekund l...

Страница 30: ...eznaczenia II2E3P PL Napi cie zasilania V Hz 230 50 Poziom ochrony przeciwpora eniowej IP X5D Strata kominowa przy wy czonym palniku w czonym palniku 0 12 3 78 FUNKCJA C O Maksymalne ci nienie Tempera...

Страница 31: ...m 80 80 CO2 5 0 5 5 NOx b w poni ej p p m 20 25 Temperatura spalin C 60 62 U redniona warto z zakresu pracy w r nych warunkach Pr ba wykonana z koncentrycznym przewodem koncentrycznym 60 100 o d ugo...

Страница 32: ...o energetyczna ogrzewania pomieszcze s 87 Wytworzone ciep o u ytkowe Przy znamionowej mocy cieplnej i w systemie wysokotemperaturowym P4 24 0 kW Przy znamionowej mocy cieplnej na poziomie 30 i w syste...

Страница 33: ...way electric valve 26 Pressure gauge 27 Domestic hot water NTC sensor 16 27 12 PL Budowa kot a AF Wej cie z w AC Wyj cie c w u M Zasilanie c o R Powr t c o 1 Zaw r nape niania 2 Zaw r zwrotny 3 Zaw r...

Страница 34: ...Domestic hot water NTC sensor 7 Water pressure switch 8 Domestic hot water heat exchanger 9 Limit thermostat 10 Primary NTC sensor 11 Post exchanger thermal fuse 12 Capacitor 13 Primary heat exchange...

Страница 35: ...y Verde Zielony g v to zielony A Zworka TA OT styk bezpotencja owy BRT14 P yta steruj ca z wy wietlaczem cyfrowym i zintegrowanym transformatorem zap onowym F Bezpiecznik 3 15A F X1 X5 Z cza TR1 Trans...

Страница 36: ...36 8 EN Measured in mm PL Wymiary w mm 5 6 EN Indoor installation PL Monta wewn trz 7 9 50 50 93 5 65 47 75 73 75 65 60 1 4 0 M AC G AF R water gas woda gaz dimensions in mm wymiary w mm...

Страница 37: ...P 12 A B A B M4 S E t arancione arancione rosa rosa TA OT Contatto privo di tensione UWAGA Elementy systemu kominowego wraz ze schematami znajduj si w Katalogu Produkt w Beretta UWAGA Elementy systemu...

Страница 38: ...d11 B C A P13 Kd D 14 A B C D EN Graph 1 thermoregulation graph for main area with temperature range 35 80 C CH delivery temperature C Outdoor temperature C Graph 2 PL Wykres 1 wykres regulacji pogodo...

Страница 39: ...20176972 03 21 Ed 1 EN RANGE RATED EN 15502 The max CH input of this boiler has been adjusted to_____ kW equivalent to _____ rpm max CH fan speed Date___ ____ ____ Signature _____________________ Boi...

Отзывы: