10
List of parameters
Parameter
Description
Unit of
measure
Default
Range
Notes
P00
Hydraulic con
fi
guration
--
2
2..5
2 = combi boiler
3 = not applicable
4 = not applicable
5 = not applicable
P01
Gas type
--
0 NG
1 LPG
0..1
0 = methane (G20)
1 = GPL (G31)
P02
System type
--
0
0..1
0 = HT (high temperature)
1 = not used
P03
Ignition ramp time
Min
1
0..30
0 = disabled
P04
Delay to prevent water hammer
Sec
2
0..20
0 = disabled
P05
CH OFF time
Min
3
0..10
0 = disabled
P06
Post-circulation pump in CH
Min
3
0..10
0 = disabled
P07
Post-circulation pump in DHW
Min
1
0..10
0 = disabled
P08
Minimum power DHW
%
0
0..100
P09
Minimum power CH
%
0
0..100
P10
Maximum power CH
%
100
0..100
P11
Maximum power DHW
%
100
0..100
P12
Not applicable
--
1
0..1
0 = disabled
P13
Outdoor sensor coef
fi
cient
--
0
0..30
0 = disabled
P14
MIN setpoint CH
°C
25
20..40
if P02 = 1 not used
30
if P02 = 0 (HT)
P15
MAX setpoint CH
°C
45
40..55
if P02 = 1 not used
80
40..88
if P02 = 0 (HT)
P16
MAX setpoint DHW
°C
60
45..75
if P00 = 2
--
--
if P00
≠
2
P17
Maximum circulator speed
%
100
60..100
not used
P18
Starting delay CH
Sec
0
0..199
P19
Enable gas valve trim
--
0
0..1
0 = disabled
P20
Not applicable
°C
5
3..9
Not applicable to this model
P21
Not applicable
--
0
0..1
0 = disabled
P22 (if P21=1)
Not applicable
rpm x10
140
140..180
if P01= 0 (G20)
1000
140
if P01= 1 (G31)
P23 (if P21=1)
Not applicable
rpm x10
100
100..140
if P01 = 0 (G20)
100
if P01= 1 (G31)
P24 (if P21=1)
Not applicable
rpm x10
110
110..140
if P01= 0 (G20)
115
if P01 = 1 (G31)
b
The boiler parameters must only be set or modi
fi
ed by professionally quali
fi
ed personnel. The manufacturer shall not be liable for malfunctions or damage caused by improper
con
fi
guration of the appliance.
mode.
By pressing the RESET button for 10 seconds, you can exit the installer mode.
If no key is pressed within 15 minutes, parameter mode is automatically exited.
4.12 Info menu (In)
b
Access to the menu is not allowed with the boiler in the OF state.
Access the Info menu as follows:
-
Press the RESET button for 10 seconds to enter con
fi
guration mode. "tS" begins to
fl
ash
on the display.
-
Press the CH+ or CH- buttons to navigate the menu and select the Info menu (In).
+
-
-
Press MODE to con
fi
rm, the display shows the
fi
rst Info parameter.
-
Press the CH+ or CH- buttons to select the parameter number.
-
The parameter value is shown alternately with the parameter number (2 seconds each).
Info list
1 DHW sensor temperature
°C
0..125
2 CH sensor temperature
°C
0..125