Case Expansion Monitor Maintenance
13 I Calibrate Channels
muLT [METER
LVDT
Figure 1
SLIDING
FOOT
FOOT
Me lel 1 M N f l
CIO
lull
SIGNAL
INPUT RELAY
MODULE
84418-01
CAUTION
Both channels will b e bypassed
automatically during calibration.
Machine Protection will b e lost
during calibration. S e e Danger
Bypass section 10.
ZLWARNING
High Voltage present
Could cause shock, bums
or death.
Do Not touch exposed
wires or terminals.
Since the transducer sensitivity can vary as much as + 20%, It is necessary to perform the channel
calibration with the actual transducer to be used with that channel. The user may construct a gauging
tool, if desired, to aid in accurately adjusting the LVDT core position during calibration.
1. Loosen and adjust the LVDT or core mounting components such that the core position can be
adjusted manually throughout the entire indicator expansion measurement range.
2. Connect a multimeter to COM and IN with polarity as shown in Figure 1.
3. Open front panel.
2 1
Содержание 3300/48
Страница 5: ...84417 01 C a s e Expansion Monitor Operation Blank Page i v...
Страница 7: ...84417 01 Case Expansion Monitor Operation Blank Page v i...
Страница 25: ......
Страница 29: ...Case Expansion Monitor Maintenance Blank Page i v...
Страница 31: ...Case Expansion Monitor Maintenance 8 4 4 1 8 0 1 Blank Page v i...
Страница 67: ...Case Expansion Monitor Maintenance 8 4 4 1 8 0 1 APPENDIX I SCHEMATICS AND PWA DRAWINGS Appendix...
Страница 71: ...oL w 171 d I 5 57 E a I i g CwQe O Case E x p a n s i o n M o n i t o r S c h e m a t i c Sheet 4 o f 1 1...
Страница 72: ...Case E x p a n s i o n M o n i t o r S c h e m a t i c Sheet 5 o f 11...