84417-01
Case Expansion Monitor Operation
4
MONITOR FUNCTIONS
CASE EXPANSION - The Case Expansion
Monitor continuously monitors the expansion
of the machine case o n both sides o f a
machine. T h e monitor uses signals from two
linear variable differential transducers (LVDT)
mounted on both sides of the machine case.
LVDTs can be oriented so that the expansion
of the machine case is either toward or away
from the LVDT. T h e Case Expansion Monitor
provides a n alarm i f the expansion o f the
machine case is not the same on each side.
OK - When the output voltage of the LVDTs is
within its upper/lower limits, the transducer is
defined a s OK. T h e O K detection circuit
controls the channel OK LED and the monitor
relay drive to the OK Relay. If the monitor has
the Latching Not OK option chosen, a System
Reset is required to reset the OK function.
OK RELAY - The OK Relay is located on the
Power Input Module. Every channel in the rack
must be OK or bypassed to energize the OK
Relay.
DIRECT AND DIFFERENTIAL MODE - The
Case Expansion Monitor can display t h e
expansion of the machine case in two ways,
direct or differential. I n the direct mode, the
monitor shows the amount of expansion as
measured by the LVDTs on both sides of the
machine. T h e t w o measurements a r e
displayed on the bar graphs for channel A and
B. I n t h e differential mode, t h e monitor
displays t h e difference between t h e t w o
measured expansions. T h i s difference i s
displayed on the bar graph for channel A, and
the bar graph for channel B is blanked. The
monitor can
b e toggled between direct
and
differential modes b y pressing t h e MODE
switch.
ALARM - Since alarms for the case expansion
monitor use differential values, alarm setpoints
may b e read when the monitor i s in the
differential mode only. Pressing the Alert or
Danger Switch o n the front panel o f the
monitor causes the corresponding Alert (first-
level alarm) or Danger (second-level alarm) set
points t o b e displayed o n the channel A
bargraph on the front panel. Pressing alarm
switches when the monitor is in direct mode
gives a blank display. W h e n the differential
expansion signal exceeds the preset levels for
the selected time delay, the Alert and Danger
LEDs come on and the appropriate Alert and
Danger alarm relay contacts activate.
FIRST OUT - Separate First Out circuits exist
for Alert and Danger alarms. A monitor with
First Out option selected flashes a channel
alarm LED if that channel was the first channel
in the rack to go into alarm since the last
reset. P r e s s i n g t h e R E S E T s w i t c h
acknowledges the First Out.
ALARM RELAYS - Monitor alarms can b e
programmed for either the latching or non-
latching mode. In the non-latching mode, the
alarm resets automatically when the alarm no
longer exists. In the latching mode, the alarm
condition must be reset manually by pressing
the RESET switch on the front panel of the
System Monitor or by closing external Reset
contacts. The alarm will not reset if the alarm
condition still exists.
DANGER BYPASS - Danger Bypass inhibits the
danger relay drive. Other monitor functions
continue. W h e n Danger Bypass is on, the
Bypass LEDs for both channels are on. This
function c a n b e enabled b y
installing
a
programming jumper on the monitor.
4
•
•
Содержание 3300/48
Страница 5: ...84417 01 C a s e Expansion Monitor Operation Blank Page i v...
Страница 7: ...84417 01 Case Expansion Monitor Operation Blank Page v i...
Страница 25: ......
Страница 29: ...Case Expansion Monitor Maintenance Blank Page i v...
Страница 31: ...Case Expansion Monitor Maintenance 8 4 4 1 8 0 1 Blank Page v i...
Страница 67: ...Case Expansion Monitor Maintenance 8 4 4 1 8 0 1 APPENDIX I SCHEMATICS AND PWA DRAWINGS Appendix...
Страница 71: ...oL w 171 d I 5 57 E a I i g CwQe O Case E x p a n s i o n M o n i t o r S c h e m a t i c Sheet 4 o f 1 1...
Страница 72: ...Case E x p a n s i o n M o n i t o r S c h e m a t i c Sheet 5 o f 11...